| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.8 LAccepted-AOC A T ROAD CHABUA DIBRUGARH ASSAM 786184 | DIBRUGARH | ASSAM | 786184 | ₹47.8 L | L1 | Accepted-AOC Accepted being L1 |
| 2 | L2₹51.8 L+₹4.0 L (8.40%)Rejected-Finance A T ROAD CHABUA NEAR ST LUKAS HOSPITAL PO CHABUA DIST DIBRUGARH ASSAM 786 184 | CHABUA | DIBRUGARH | ASSAM | 786184 | ₹51.8 L+₹4.0 L (8.40%) | L2 | Rejected-Finance Rejected being L2 |
| 3 | L3₹52.7 L+₹4.9 L (10.2%)Rejected-Finance NAV PUKHARI ROAD MILLAN PALLY PO DIST TINSUKIA ASSAM 786 125 | TINSUKIA | DIBRUGARH | ASSAM | 786125 | ₹52.7 L+₹4.9 L (10.2%) | L3 | Rejected-Finance Rejected being L3 |
Tender Value
₹47.7 L
EMD Value
₹95,000
Closing Date
21 Apr 2025, 6:00 pmClosed
GE (AF) CHABUA
GE (AF) CHABUA, POST-CHABUA AIR FIELD, DIST-DIBRUGARH, ASSAM-786102
REPAIR/ REPLACEMENT OF CERTAIN E/M WORKS AT ALG PASIGHAT STATION UNDER GE (AF) CHABUA
2025_MES_701764_1
653
Open Tender
Civil Works
Item Rate
270 days
GE (AF) CHABUA, POST-CHABUA AIR FIELD, DIST-DIBRUG
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (AF) CHABUA
₹95,000
Yes
25 May 2025
19 Mar 2025
23 Apr 2025
19 Mar 2025
21 Apr 2025
2 Apr 2025
19 Mar 2025 - 26 Mar 2025
Amount
Taking down copper /aluminium point wiring (light, fan, bell,socket or power) complete including fixture and fittings such as switches , ceiling roses , pendent , regulators, sockets, light fitting etc . Removing materials to store for keeping in safe custody or for taking credit ( credit a for above items should be made as per condition seperately ) and making good distrubed surfaces of walls, floors etc.
Taking down carefully copper/aluminium Sub main wiring of any size from surface/concealed /existing conduit of any height and removing materials at site and making good disturbed surfaces of walls, floors roofs etc complete all as specified and directed.
Taking down old/unserviceable distribution board by disconnection of electric connection carefully SPN DBs/TPN DBs/ Main Switch including old unserviceable MCCBs/ MCBs, Isolators, etc and making good to disturbed surface complete all as specified and directed at site.
M&L for point wiring with 2.5 Sq mm single core PVC insulated FRLSH unsheathed copper multi stranded conductor and including PVC casing caping ISI marked of size 20/25mm inclusive of tees ,bend ,elbows etc including sunk Anodized pressed steel box 1.6 mm thick concealed in wall with white laminated colour 3 mm thick sheet cover of suitable size complete including PVC insulated multi stranded copper conductor 2.5 Sq mm as earth wire to common earth dolly for connection to ceiling rose to earth terminal incl cutting, chasses and making good disturbed surface to match with existing finish with plaster for One light /Fan point controlled by one one way switch complete all as specified and directed at site.
All as per ser item No. 4 here-in-before but point wiring for 5 amp ind socket with 2 x 2.5 sqmm for phase and neutral 1 x 2.5 sqmm for earth continuity wire.
All as per ser item No. 4 here-in-before but point wiring for 15 amp ind socket with 2 x 2.5 sqmm for phase and neutral 1 x 2.5 sqmm for earth continuity wire.
All as per ser item No. 4 here-in-before but point wiring for 15 amp ind socket with 2 x 4 sqmm for phase and neutral 1 x 4 sqmm for earth continuity wire.
S&F Switch Piano type single pole 5 amp 230 v complete all as specified and directed at site.
S&F socket outlet 2 in 1 , 5 pin, 5 amp complete all as specified and directed at site.
S&F Switch Piano type single pole 15 amp 230 v complete all as specified and directed at site.
S&F socket outlet 2 in 1 , 6 pin,5 and 15 amp complete all as specified and directed at site.
S&F ceiling rose surface type Bakelite 65x50 mm three terminals complete all as specified and directed at site.
S&Fixing stepped type electronic fan regulator flushType complete all as specified and directed at site.
M&L for lamp holder , PVC /Polycarbonate type with back plate suitabl for batten fittings.
S&F in repair switch modular type, one way, 10 ams, 1 module 230 v complete all as specified and directed at site.
S&F in repair switch modular type, one way, 16 ams, 1 module 230 v complete all as specified and directed at site.
S&F in repair socket outlet,modular type ,multipurpose,multipin, 6 amps, 2 module, 230 v complete all as specified and directed at site.
S&F in repair socket outlet,modular type ,multipurpose,multipin, 6 amps/16 amps , 2 module, 230 v complete all as specified and directed at site.
S&F in repair modular type fan regulator,two module, 230 v complete all as specified and directed at site.
Supply and Fixing in replacement LED light fittings 36 watt Recess Mounting type with LED driver, mounting arrangement (Recess suitable for, 2x2 Grid, Hanging) including electric connection complete all as specified and directed at site.
Supply and Fixing in replacement LED light fittings 36 watt surface Mounting type with LED driver, mounting arrangement including electric connection complete all as specified and directed at site.
Supply and fixing in replacement LED lights fitting 1x 20W, 220V,AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed at site.
Supply and fixing in replacement of surface mounted LED slim ceiling light fitting extruted aluminium housing and milky diffuser suitable for 1'x1' ceiling cell of 18 watt inluding provision of PVC insulated sheathed round flexible wire complete all as specified and directed at site.
Supply and fixing in replacement surface and wall mounted LED batten fitting energy efficient fittings 10 watt complete , inluding provision of PVC insulated sheathed round flexible wire complete all as specified and directed.
Supply and fix in repair round shape 15 watt 220 volts AC surface type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with 2/3 core flexible wire complete.
Supply and fixing LED light fitting 2 x 16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with 2/3 core flexible wire complete all as specified.
Supply and fix MCB DB TPN 4 way double door with metal door suitable for housing of MCBs grouting/flush in wall and making good to disturbed surfaces incl fixing material/accessories complete all as specified and directed at site.
Supply and fix MCB DB SPN 8 way double door with metal door suitable for housing of MCBs grouting/flush in wall and making good to disturbed surfaces incl fixing material/accessories complete all as specified and directed at site.
Supply and fix MCB DB SPN 12 way double door with metal door suitable for housing of MCBs grouting/flush in wall and making good to disturbed surfaces incl fixing material/accessories complete all as specified and directed at site.
Supply and fix in repair factory made sheet metal enclosure single pole & neutral with a two pin & earth plug and socket of 20 amps capacity complete all as specified and directed at site.
S&F in repair MCCB 63 Amps, 415 V, 16KA 4 pole with thimbles/lugs and nut,bolts complete all as specified and as directed.
S&F in repair MCB SP 240 volt 6 to 32 Amps 'C' series 10 KA complete all as specified and directed at site.
S&F in repair MCB SPN 240 volt 32 Amps 'C' series 10 KA complete all as specified and directed at site.
S&F in repair MCB SPN 240 volt 40 to 63 Amps 'C' Series 10 KA complete all as specified and directed at site.
S&F in repair MCB TPN 415 volts,40 to 63 amps 'C' Series 10 KA complete all as specified and directed at site.
M&L for sub main wiring with 2 x 6 sqmm (nominal area) PVC insulated and unsheathed cables with stranded copper conductor (FRLS), including two run of continuous PVC insulated FRLS copper stranded cable of size 6 sqmm for earth wire in and including surface heavy duty PVC casing capping complete all as specified and directed at site.
M&L for sub main wiring with 2 x 4 sqmm (nominal area) PVC insulated and unsheathed cables with stranded copper conductor (FRLS), including two run of continuous PVC insulated FRLS copper stranded cable of size 4 sqmm for earth wire in and including surface heavy duty PVC casing capping complete all as specified and directed at site.
M &L for GI Earthing complete with GI earth plate electrode 60cm x 60cm x 6 mm buried directly in ground verticvally to depth not less than 2.25 mtr below ground level and with top edge of the plate at a depth not less than 1.5 mtr below ground level, size of dipth 0.90 x 0.9 x 2.25 mtr ,earth plate connected to galvanised earth wire of size 4.00 mm dia 7.5 mtr long by means of brazing nuts, bolts, check nuts, & washers ,testing of completion (drawn in earth lead protection pipe light gade GI of size 15 mm dia) by means brazing at both edges with vertical plane of electrode all as shown in plate No 5 of SSR Part - I connected to earthing lead with Main switch/main control board,filling with charcoal dust 200 Kg, and common salt 100 KG , including necessary excavation and earth work in any type of soil ,perforated watering pipe,funnel with wire mesh,earth lead protection pipe light grade PCC chamber 1:3:6 type C1 (for even finish on both the faces) and RCC cover 1:2:4 Type B1,450 x450 x50 mm thick with 6 mm dia CTD bars 150 mm c/c with 2 Nos of handles of 10 mm dia steel rod all as specified and directed and testing on completion and connected to equipment with lugs and screw nuts etc all as specified and directed by EIC
S&F Blanking Plates for covering of MCCB DB open space complete all as specified and directed at site.
S&F in replacement of LED security light energy saving & environmental friendly long life made up of pressure die-cast housing with toughened glass and high power LEDs with secondary optics and IP66 protection of 90 W capacity after taking down the old unserviceable one complete all as specified and directed . Make : Havells/Crompton/Philips
Taking down geyser of any capacity from wall mountings after disconnecting electrical and water connections to carry out repairs and after repair fixing the same and making electrical and water connections, testing and commissioning complete all as specified and directed at site. Note : Replacement of parts carried out will be measured and paid separately under respective items.
Taking out complete internal assembly i.e. inner tank,inlet and outlet assembly,heating element,thermostate etc of geyser of capacity 25 ltr,de-scaling the inner tank using appropriate chemical (descaling agent),cleaning and washing complete accessories,reassembling the same position complate all as specified and directed at site.
Repair of copper /steel inner container of geyser of 25 ltr capacity by necessary welding/brazing to check the water leakage, testing by applying specified air pressure to ensure leak proof, reassembling of geyser complete all as specified and as directed.
Supply and fix in repair of apparatus plate assembly of brass suitable for 25 ltr capacity geyser with collar,gasket, inlet and outlet facilities, housing to accommodate heating element, thermostate,thermal cut out complete all as specified and directed at site. Note : Cost of drilling work, fixing accessories like nuts,bolts,washer/check nut etc and taking down and refixing of geyser are deemed to be included in the quoted rate.
M&L for painting of geyser up to 25 ltr with one coat of white paint as per existing colour using spray machine painting with synthetic enamel paint including cleaning, washing of surfaces complete all as specified and directed at site.
Supply and fixing in repair thermostate switch for geyser 25 ltr capacity complete all as specified and directed at site.
Supply and fixing in repairs heating element 1.5 KW,AC 230 volts (Cup/Triangular type) complete all as specified and directed at site.
Supply and fixing in repairs heating element 2 KW,AC 230 volts (Cup/Triangular type) complete all as specified and directed at site.
Supply and fix in repair safety valve /fusible plug (brass) 15 mm bore for geyser complete all as specified and directed at site.
S&F in repairs PVC insulated sheathed copper conductor 2.5 sqmm 3 core as in connecting wire of geyser complete all as specified and directyed at site
Supply and fixin repair PVC heavy duty hot and cold water pipe 450 mm long fixed both side with brass ferrule nuts for 25 ltr capacity geysers for inlet/outlet pipe complete all as specified and directed at site.
S&F in repair neon indicator lamp (red/green) round/rectangular type for geyser complete all as specified and directed at site.
Supply and fix electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc complete all as specified and directed at site.Make : Havells (Model Fabia)/Jaquar ( Model Elena prime) / V-Guard (Model Pebble) Note : Old unsv Geyser will be deposited to MES store yard.
Materials and labour for rewinding of ceiling Fan complete upto 1400 mm sweep with heavy duty super enamelled copper winding wire of existing gauge including all insulation materials, varnishing, heating, greasing etc. cutting and removing the old burnt winding complete all as specified and as directed . Note :-replacement of unserviceable parts like capacitor, bearing ,bush, hanging clamp,reel & nut bolt etc measured and paid separately.
All as per item no 54 here in before but Exhaust Fan upto 300 mm sweep complete all as specified and as directed by engineer in charge.
All as per item no 54 here in before but Exhaust Fan 380 mm sweep complete all as specified and as directed by engineer in charge.
All as per item no 54 here in before but Exhaust Fan 450 mm sweep complete all as specified and as directed by engineer in charge.
Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed at site.Note : Old unsv ceiling fan will be deposited to MES store yard
Supply and fix exhaust fan, steel body AC Single Phase, 230 V of size 300 mm sweep with blades and frame and louvers complete all as specified and directed at site. Note : Old unsv ceiling fan will be deposited to MES store yard
M&L for painting of ceiling fan complete upto 1400 mm sweep with one coat of white paint/existing fan using spray machine painting with synthetic enamel paint including cleaning, washing of surfaces complete all as specified and directed at site.
Supply and fixing in repair ball bearing 6201 suitable for 1200 mm sweep ceiling fan complete all as specified and directed at site.
Supply and fixing in repair ball bearing 6202 suitable for 1200 mm sweep ceiling fan complete all as specified and directed at site.
Supply and fixing in repair Gun metal bush suitable for 1200 mm sweep ceiling fan complete all as specified and directed at site.
Supply and fixing in repair rubber insulator (reel type) complete all as specified and directed at site.
Supply and fixing in repair Capacitor 2.5 mfd epoxy filled type copper wound complete all as specified and directed at site.
Supply and fixing in repair Capacitor 3.15 mfd epoxy filled type copper wound complete all as specified and directed at site.
Supply and fixing in repair Capacitor 4 mfd epoxy filled type copper wound complete all as specified and directed at site.
M&L for dehydration & filteration of voltage stabilizer oil by dehydration plant (bringing plant at site) including testing of sample before and after dehydration and filteration to achieved 40 KV at 2.5 mm gap complete all as specified and directed by Engr-in-ChargeNote : (i) The filteration of the voltage stabilizer /isolation transformer oil shall be carried out at different locations of the AF Stn Chabua. (ii) The report before filteration & after filteration to be submitted by contractor . (iii) Oil for topping up will be measured and paid separately. (iv) Centrifuging Machine with all T&P & testing eqpt required for dehydration to be arranged by contractor.
Supply & toping up of new voltage stabilizer oil conforming to IS 335 std having dielectric strength 40 KV at 2.5 mm gap after initial dehydration complete all as specified .
Dismantling and taking out old worn out reversible synchronus servo motor from the voltage stablizer and supply and fix new reversible servo motor single phase 230 Volts suitable for 300 KVA voltage stabilizer complete all as specified and directed.
Dismantling and taking out old worn out I C electronic control card including mother board,PCB from the voltage stablizer of capacity 300 KVA and supply and fix new I C electronic control card with mother board and PCB complete all as specified and directed.
S & F in repairs 12 pin connector suitable for 300 KVA voltage stabilizer complete all as specified and directed.
S & F in repairs R C network suitable for 300 KVA voltage stabilizer complete all as specified and directed.
S & F in repairs main big gear of voltage stabilizer complete all as specified and directed.
S & F in repairs high low voltage cut off circuit suitable for 300 KVA voltage stabilizer complete all as specified and directed.
S & F in repairs bush suitable for 300 KVA voltage stabilizer complete all as specified and directed.
S&F in repair protection relay CSDPR-V2 suitable for 11 KV HT panels SF 6 complete all as specified and directed at site.
Attending any electrical breakdown at ALG Pasighat such as faulty of HT 11KV/12KV HT switch gear,315 KVA dry type transformer ,300 KVA Voltage Stablizer and any other electric break down by attending of auth service engineer to check and rectified the same all as specified and directed at site.. Note :- Spare parts which are required to replace of unserviceable spare parts will be paid under respective item of Sch A
Comprehensive maintenance and servicing of Dry type Transformer 315 KVA 11/0.433KV of Schineider Make consisting in CSS by disconnecting of HT/LT connection, opening of doors etc complete cleaning of the inside compartment, core and coils by vaccum cleaner incl lead supports, tap changer terminal boards, bushings and other insulated surfaces be wiped clean with a dry cloth and all connections must be checked for tightness after cleanining upto the entire satisfication of Engr-in-charge the transformer must be meggered and connecting all connection and necessary testing Complete with U/m Scope of work a) Cleaning of transformer from inside. b) Testing the Transformer for IR Values. c) Checking/servicing/calibration of WTI for healthiness d) Magnetic Balance Test. e) IR Value check before and after the work f) Voltage Ratio Test at 440V. g) DC Logic test h) .Commissioning of Transformer after completion of work j) Test results obtained shall be recorded and produced to the Engr-in-Charge. k) All Measuring equipments and T&P required shall be arranged by the contractor. l) Any item /activity not listed / covered here above and required during /completing the overhauling work will have to be arranged by Contractor himself. m) The rate quoted shall be deemed to include for Disconnection of Transformer HV/LV terminations for testing work and re-connections after completion of repair work .
Taking down Old burnt /Unserviceable HT/LT 95 sqmm underground PVC Cable heavy duty aluminum conductor LT 1100 V grade after disconnecting of electric connection all as specified and directed at site.
Supply and laying in trenches/through pipes under road, floor/ on wall/on pole or any other indicated place & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)with stranded aluminum conductor, 11000 volts grade, of size 3 core 95 sq mm complete all as specified.
Excavation in trenches, in soft/loose soil, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, or for shafts, wells, manholes, pier holes,cable laying, sewage/water lines etc complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers n exc 25cm complete all as specified and directed.
Removing excavated material n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and directed.
Material and labour for sand cushioning with dry river sand in trenches for cushioning of underground cable line including spreading, leveling, well ramming completed all as specified and directed.
M&L sub class B brick,well burn laid bridth-wise along the length the cable laid in trench over sand cushion,laid for ug cable protection complete all as specified and directed at site.
Supply and fix in repair steel tubes, galvanised, light grade, ISI marked 80 mm bore for protection of cable under floor, road and on wall complete.
Cutting bituminous road/path for passing of elect cable through GI pipes and making good to the cut surfaces by concreating with PCC 1:3:6 to match with the adjescent surfaces complete all as directed at site.
M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique/Manual and necessary machine suitable for 80/100 mm GI pipe complete all as specified and directed at site
M&L in repair cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed at site.
M&L in repair cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed at site.
S & Fix in repair power contactors MCX - 44 , 2 NO+2NC 4 pole power contactor complete all as specified and directed at site.
M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr below normal ground level ) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to main GI strip 32 x 6 mm as earth strip by means of bolts ,nuts and washers of galvanised iron or steel as shown in electrical plate No. 3, including exc , and earth work in any type of soil disposal of soil providing alternate layers of charcol and common salt construction of PCC earth chamber in mix 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B1 cover reinforced with 8mm dia MS bars both ways with lift hook made out of 8 mm dia bar, watering arrangement with funneland wire mesh and wateing pipe of 20 mm dia GI light grade and 40 mm dia light grade pipe for earth strip protection and testing on completion complete all as specified and directed at site.
M&L for Earthing complete with copper earth plate electrode 60 cm x 60 cm x 3.15 mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level copper earth strip 32 x 6 mm by mean of nut/bolt and washer of copper as shown in electrical plate no 3 of SSR part I including exc & earth work in any type of soil, disposal of soil, providing alternate layer of charcoal and common salt, construction of pcc earth chamber in mix 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B1 cover reinforced with 8mm dia MS bars both ways with lift hook made out of 8 mm dia bar, watering arrangement with funneland wire mesh and wateing pipe of 20 mm dia GI light grade and 40 mm dia light grade pipe for earth lead protection and testing on completion complete all as specified and directed at site.
M & L for maintenance free chemical earthing system complete with 03 (three) nos copper bonded rods, 17.2 mm dia 3000 mm long electrode buried at suitable distance apart directly in ground, to bore holes of 120 mm dia vertically to a depth not less than 3.60 mtr deep below ground level with top edge of earth electrode at a depth not less than 100 mm below normal ground level, provision of clamps or brazed or both for each copper bonded rods made of copper and copper strip of size 25 x 3 mm & strip connection on the top of the electrode and copper strip of size 25 x 3 mm for inter connection of 03 nos copper bonded rods and laying at least 500 mm below in the ground and further connected to test point terminal block (copper strip and test terminal block shall be measured separately), including back filling of bore holes with advanched earth enhancing compound 96 kilogram (minimum) of Make : Erico or equivalent of Macmet/True Power/Ennov for artificial treatment to soil so as to achieve earth resistance below 01 Ohms as specified in para 19.140 of SSR Part-1 (2009), including provision of earthing pit in PCC(1:3:6) type C1 pre-cast cover RCC slab of size 400 x 400 x 50 mm with one handle made out of 8 mm dia round bar, including necessary earth work and three coats of white wash on plastered surface (exposed surfaces) and testing complete all as directed and including necessary earth work and testing complete all as specified and directed. Note:-Taking down old unservicible dipilated chemical earthing are included in quated rate.
S & F in repair Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20 x 15cm size complete all as specified and directed.
S & F in repair Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25 x 20 cm size complete all as specified and directed.
Supply and fixing in repair digital voltmeter, ranging from 0 to 500 Volts, including providing necessary electrical connections (to accommodate in panel board) complete all as directed by the Engr-in-Charge.
Supply and fixing in repair digital ammeter, ranging from 0 to 400 Amps (with CT of suitable ratio), including providing necessary electrical connections (to accommodate in panel board) complete all as directed by the Engr-in-Charge.
S & F in repairs Indicator Lamps (LED type) including providing necessary electrical connections (to accommodate in panel board) complete all as directed by the Engr-in-Charge.
Disconnecting of elect supply and taking out LT switch gear of any make and type and servicing of LT switch gear by cleaning isolating contacts moving parts removing dust particles from bus bar chamber spout gear mechanism and moving parts, repair to motor charge spring mechanism tightening of nut & bolts of entire trolley components all as directed inserting in trolley, testing commissioning and putting on the supply on load complete all as directed. Note :- Spare parts which are required to replace of unserviceable spare parts will be paid under respective item of Sch A
Taking down Old burnt /Unserviceable LT 70 sqmm underground PVC Cable heavy duty aluminum conductor LT 1100 V grade after disconnecting of electric connection all as specified and directed at site.
All as per ser item No 102 (here-in-before) but size of cable 16 sqmm x 4 core
Supply laying & testing of XLPE insulated, armoured, heavy duty electric under ground cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 70 Sqmm nominal cross section x 3.5 core.
All as per ser item No 104 (here-in-before) but size of cable 16 sqmm x 4 core
Taking down old unsv MCCB by disconnection of electric connection carefully from LT panel/LT feeder piller etc complete all as specified and directed at site.
S & F MCCB 4 pole,415 volt 100 Amps with breaking capacity 16 kA, adjustable type 415 V, 50 Hz, all as directed.
S & F MCCB 4 pole,415 volt 200 Amps with breaking capacity 36 kA, adjustable type 415 V, 50 Hz, all as directed.
S & F MCCB 4 pole,415 volt 250 Amps with breaking capacity 36 kA, adjustable type 415 V, 50 Hz, all as directed.
S & F MCCB 4 pole,415 volt 630 Amps with breaking capacity 50 kA, adjustable type 415 V, 50 Hz, all as directed.
Overhauling/servicing of HT switch gear (VCB SF 6) of cap 11 KV comprising of following repairs : (a) Tripping of the breaker,lowering the breaker with raising/lowering handle and pulling out the breaker complete from the panel along with trolly/SF6 for servicing/overhauling. (b) Servicing/inspecting/checking of circuit automatic safety shutter operation for serviceability and replacement of spares if required. (c ) Servicing/inspecting of circuit spout and circuit spout connections for RYB phases and replacement of spares if required. (d) Dismantling and checking of cross bar assembly,fixed contacts and current carrying carrying parts of the breaker,trolley insulated assembly and checking lamination with clamps,epoxy spout,isolator assembly etc. (e) Setting,reassembling,cleaning,adjustment of fixed contacts,main contact,arching contacts and chamber baffle pot assembly,moving contact for proper setting of auxiliary contacts operating mechanism. (f) Servicing/inspecting/checking of secondary sockets/bus bar earthing plug/earthing socket and replacement of spares if required.
M&L 11 KV Lighting arresters expulsion type complete with all fittings,transmission class,discharge capacity 65 kilo amp complete all as specified and directed at site.
M&L in repair triple pole mechanical operated , mounted on insulator with operating mechanisam worked from ground level for current rating 400 amps amps suitable for 11000 volts complete all as specified and directed.
M&L for drop out fuse single pole suitable for 11000 volts grade upto 50 amps complete all as specified and directed.
Attending day to day Street light complaints with skilled electrician (Street lights fitted on poles/buildings/High mast tower at height up to 12 mtr from ground level), repair/replacement of unserviceable accessories like LED drivers, copper/aluminium service connection wires,MCBs complete all as per the instruction of Engineer in Charge. cost of T&P such as required tools, ladders, helmet, etc required for repair of street light/flood light complete all as specified and directed at site.. Note: - (a) Cost of spares and accessories will be measured and paid seperatly under relevent items. (b) Cost for taking down and re-fixing of street lights shall be deemed to be included in the unit rate quoted. (c) Any other items or parts (other than listed in Sch A) required for smooth functioning of street lights/ Security lights on pole from junction box busbar to street light shall be provided by the contractor and rates for the same are deemed to be included in above item here in before nothing extra shall be paid on this account. (d) All the fitting of HPSV/ HVMV LED street light/ flood light will be cleaned once in a month or when required.The rates for which shall be deemed to be included in the unit rate quoted.
Supply and fix in repair LED driver suitable for 45 watt LED street light fitting complete all as specified and directed.
Supply and fix in repair LED driver suitable for 60 watt LED street light fitting complete all as specified and directed.
Supply and fix in repair LED driver suitable for 70 watt LED street light fitting complete all as specified and directed.
Supply and fix in repair LED driver suitable for 90 watt LED street light fitting complete all as specified and directed.
Supply and fix in repair LED driver suitable for 100 watt LED street light fitting complete all as specified and directed.
Supply and fixing steel tubes, galvanised, light grade, ISI marked 50 mm bore for protection of cable under floor, road and on wall complete.
Supply and fix street light GI bracket,bend to 120 degree angle,made out of 40 mm bore,gI pipe,light grade (approx 1.5 mtr in length) including necessary two nos suitable size of clamps with nuts,bolts and washers etc and two coat of synthetic enameled paint over a coat of red oxide primer including taking down the old rusted one complete all as specified and directed.
S&F in repairs junction box 200 x 140 x95 mm in size , made out of thermoplastic sheet having IP 65 protection for outdoor installation fixed on poles with flat aluminium clamps of size 20 x 3 mm, nuts,bolts,washers etc.& taking out of old unsv cable junction box complete all as specified and as directed.site.
Supply and fix in replacement of 1100 volts grade heavy duty cable PVC insulated aluminium stranded conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4 mm suspension GI wire, one twin core cable flat or circular with size 6 sqmm x 2 core complete all as specified and directed at site.
All as per ser item no 124 (here in before) but size of cable 10 sqm x 2 core
S&F in replacement of LED street light energy saving & environmental friendly long life made up of pressure die-cast housing with toughened glass and high power LEDs with secondary optics and IP66 protection of 45 W capacity after taking down the old unserviceable one complete all as specified and directed . Make : Havells/Crompton/Philips
S&F in replacement of LED street light energy saving & environmental friendly long life made up of pressure die-cast housing with toughened glass and high power LEDs with secondary optics and IP66 protection of 60 W capacity after taking down the old unserviceable one complete all as specified and directed . Make : Havells/Crompton/Philips
S&F in replacement of LED street light energy saving & environmental friendly long life made up of pressure die-cast housing with toughened glass and high power LEDs with secondary optics and IP66 protection of 70 W capacity after taking down the old unserviceable one complete all as specified and directed . Make : Havells/Crompton/Philips
S&F in repair post top lantern/Gatelightst top luminaire LED type of 25 W of post top lantern with aluminium die-cast housing cum heat sink in IP-65 protection including all fixinging arrangement complete all as specified and as directed,
M&L for complete servicing of high mast light of any height including general checking, mechanical parts and electrical system and maintenance complete all as specified and as directed for the followings :- (a) Checking and repair of head frame of the high mast poles fitted with wire ropes and cables. (b) Checking and repair of gear box for seal leakage. (c) Checking and repair of lift cables for frayed strands (d) Testing and repairing of lowering device and fully operate to fully down position. (e) Repair and maintenance of any mechnical devices as required. (f) Checking and repairing of all electrcial devices. (g) Checking and repair of luminaires box, control gear and junction box nad tightened properly. (h) Checking and reparing of all screws and nuts properly.
M&L for taking out burnt winding of 3 phase power tool electric motor of high mast fittings from any position, re-winding with super enamelled copper wire of existing size/gauge and varnishing, providing insulating paper and sleeves, etc. and testing for proper functioning on reinstating complete all as specified and as directed. Note : Quoted rate shall be deemed to be inclusive of any minor spares/parts.
S&F in repair flood light fitting mounted on high mast light of 100 watt energy saving,environmental friendly,long life,made up of pressure die-cast aluminium housing with toughened glass and high power LEDs IP66 protection,suitable for highlighting architectural facade and general purpose lighting after taking down the old unsv one complete all as specified and directed. Make : Havells/Crompton/Philips
S&F in repair flood light fitting mounted on high mast light of 150 watt energy saving,environmental friendly,long life,made up of pressure die-cast aluminium housing with toughened glass and high power LEDs IP66 protection,suitable for highlighting architectural facade and general purpose lighting after taking down the old unsv one complete all as specified and directed. Make : Havells/Crompton/Philips
S&F in replacement of MCB SP 240 volt 6 to 32 Amps 'C' series 10 KA complete all as specified and directed at site.
Supply and fix in repair 1.5 sqmm, 2 core PVC insulated & sheathed copper flexible cable suitable for stree light/flood light connction complete all as specified and directed at site
Material and labour for servicing of 320 KVA DG Set by carrying out the following maintenance including testing on completion at connected laod for entire satisfaction of Engr-in-Charge all as specified and directed at site. (i) Draining out engine oil feom the sump by removing drain plug,cleaning the sump throughly and refilling the sump with new engine oil to required level (ii) Replace complete set of fuel filters, oil filters and air filter element. (iii) Draining out complete coolant water mixture from the radiator and refilling the radiator with new coolent and water mixture with proportionate ratio (iv) Draining out diesel from disel tank and storing in cleaned containers,cleaning the tank throughly by removing sediments settled at the bottom and refilling the drained out diesel duly filtered. (v) Check and top up the electrolyte/distilled water in starting batterie cells to maintain the required specific gravity.Cleaning of battery terminals & applying petroleum jelly to battery poles & brass connectors. (vi) Tightening all the fasteners of complete DG set to the required torque. (vii)Tightening of all gaskets, connection of battery terminals, cable connections, foundation bolts, coupling bolts etc including test running and tappet setting of alternator by checking and setting of voltage and frequencies complete. (viii) Maintenance shall be carried out by OEM or authorised dealer of OEM. (Note : Spare parts fuel filter, air filter, oil filter, engine oil, coolent etc will be measured & paid seprately.
Lub Oil Filter
Water Separater
Fuel filter element (Set of two)
Air Filter primary chamber
Air Filter secondary chamber
V' Belt of complete DG Set
Hose pipe
All as per ser item No 136 (here-in-before) but Cap of DG Set 35 KVA
Lub Oil Filter element .Make: OEM
Fuel Filter element.Make: OEM
Air Filter Element. Make: OEM
'V' Belt of complete DG Set
Hose pipe
All as per ser item No 136 (here-in-before) but Cap of DG Set 15 KVA
Fuel Filter element,
Lub Oil Filter element,
Air Filter Element,
Fan Belt of complete DG Set
Hose for water pipe,
Dismantling the defective water pump assembly and supply and fix new water pump assembly suitable for existing DG set of capacity 30/35 KV complete all as specified and directed at site.
Supply and fix in replacement of Turbo charger suitable for 320 KVA Generator set of any ,make and type complete all as per specified and directed at site.
M&L in replacement diesel pipe metal mesh types both side connecting arrangement of length as required on site suitable for 320 KVA DG Set complete all as specified and directed.
S & F in repair hinges of doors of DG set 320 KVA capacity including welding of defective portion and provision of fixing of new MS hinges of suitable size for hanging of door complete all as directed by Engr-in -charge.
Supply and fix in replacement of battery 12 volt, 180 AH, of Make : Exide or equivalent model of Make : Amron/Sukom.
Supply and fix in replacement of battery 12 volt, 88/90 AH, of Make : Exide or equivalent model of Make : Amron/Sukom.
Supply only Engine oil 15 W 40 to top up/ refilling of all DG set of various capacity, model & location here-in-before as per the direction of Enger-in-charge.(Make: Gulf/Castrol/HP).
M&L for drain out old coolant from radiator and topup of best quality pre mixed coolants in radiator of any capacity DG set complete all as specified and directed at site.
Supply and fix in replacement of four pole Change over switch with open execution, advance neutral on load ,current rating 630 Amps,415 volts complete all as specified and directed at site.
Dismantling of 24 volt self starter from DG set of capacity 320 KVA and shifting to workshop and back for and including carrying out following repair works ,Note: Spares to be measured and paid under respective items here in after
Armature
Brush
Carbon soldering
Solonoid switch Assy
Carbon recker
Drive assembly
Field coil assebly
De-scaling of radiator assembly by carefully from the engine,transporting to civil workshop and removing the sediments,scales and rust etc by means of chemical cleaning,high pressure water washing and air cleaning, arresting the leakages by gas welding/soldering with suitable material, and re-assembling the same with new gaskets including replacement of radiator cap(whereever required) and transporting to the site, fixing to the engine for DG set of capcity 320 KV and testing for satisfactory performance complete all as specified and directecd at site.
All as per ser item No 149 (here-in-before) but Cap of DG Set 35 KVA
All as per ser item No 149 (here-in-before but Cap of DG Set 15 KVA
Supply & fix in repair of AVR suitable for 15 KVA DG Set complete all as specified and as directed Make:OEM
Supply & fix in repair of AVR suitable for 320 KVA DG Set complete all as specified and as directed Make:OEM
S & F in repairs DG control unit suitable for 320 KVA DG set Kirloskar make DG sets incl neccessary connections and testing complete all as directed.
Dismantling the defective fuel injectors & FIP from the engine and material and labour for repair/calibration of fuel injectors , nozzle repair with pressure check including replacement of barrel plunger,Nozzels,)element,dilevery valve, Injector,cups,'O' rings etc as per site requirement of 320 KVA DG set complete all as specified and directed at site.
All as per ser item No 155 (here-in-before) but Cap of DG Set 35 KVA
All as per ser item No 155 (here-in-before) but Cap of DG Set 15 KVA
M&L for complete painting of 320 KVA DG set of make:- Kirloskar with alternator,Engine,base plate by using heat resistant paint with spray gun over existing surface as per existing colour code after taking out old paint ,dirt and dust from the DG set complete body, alternator and engine complete all as specified and directed by Engr-in-Charge.
All as per ser item No 158 (here-in-before) but Cap of DG Set 35 KVA
All as per ser item No 158 (here-in-before) but Cap of DG Set 15 KVA
Servicing of AMF panel of DG Set 320 kVA by OEM i.e auth dealer of installed at AF Stn Chabua by cleaning the complete panel with suitable cleaning agennt,removing dust particles by using high speed blower and checking the controller relays,timer, contactors for proper functioning,replacing defective spare parts,replacement of defective wires of exixting size up to 2 mtr,tightening of all connections and applying jelly on contractors complete all as specified and directed by Engr-in-Charge Note : Spare parts required will be measured and paid separately as supply only but cost of small wire s shall be included in the quotated rates.
AMF Relay procom
Auxillary Relay 24 volt 2 C/O and Base
Battery charger 24 Volt
CT coils 5/100
Material & Labour for servicing/maintenance of fire alarm control Panel (FACP),upto 32 bit microprocessor based intelligent addressable fire alarm control system with single loop with battery backup ( 2 x24) Hrs,17 AH SMC battery ones in three months all as specified and directed
Dismantling,Servicing of multisensor detector with heat and smoke combination photoelectric as per exact locations with the help of manufacturer's instructions and testing for exact fault locations including cleaning through air blower then reinstalling complete all as specified and directed .
Supply and fixing in repair indoor addressable detectors complying with and type certified to EN-54 addressable type multisensor detector with heat and smoke combination photoelectric/optical with base self built intelligence complete all as specified and directed.
Disconnection fro socket outlets split type/window AC of capacity upto 2 ton of any brand,servicing by dusting,cleaning of indoor and outdoor units,rectifying gasleakage by applying necessary brazing,adjusting and rectifying faulty operation of elect and electronic remote control panels,replacing of perished elect wires for proper connection from voltage stabilizer, reinstalling the units to its original position,replacement of remote cell and testing complete all as specified and directed by Engr-in-Charge. Note : Spare parts shall be measured & paid separately under relevant items.
All as per ser item No 165 (here-in-before) but refrigerators of capacity upto 310 ltr complete all as specified and directed by Engr-in-Charge.
All as per ser item No 165 (here-in-before) but deep freezer of capacity upto 310 ltr complete all as specified and directed by Engr-in-Charge.
Servicing of cassette type split AC of capacity up to 3 ton of any brand,servicing by dusting,cleaning of indoor and outdoor units,rectifying gasleakage by applying necessary brazing,adjusting and rectifying faulty operation of elect and electronic remote control panels,replacing of perished elect wires for proper connection from voltage stabilizer, reinstalling the units to its original position,replacement of remote cell and testing complete all as specified and directed by Engr-in-Charge. Note : Spare parts shall be measured & paid separately under relevant items.
Supply & fix in repairs condenser coil of capacity 2 ton Split AC complete all as specified and directed by Engr-in-Charge.
Supply & fix in repairs condenser coil of capacity 1.5 ton Split AC complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair capacitor 45+6 mfd suitable for 1.5 Ton AC complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair capacitor 55+6 mfd suitable for 2 Ton AC complete all as specified and directed by Engr-in-Charge.
Supply & Fix in repair relay suitable for split Ac upto 2 Ton capacity complete all as specified and directed by Engr-in-Charge.
Supply & fix in repair 1.5 Ton Split Type AC indoor unit complete all as specified and directed by Engr-in-Charge.
Supply & fix in repair 1.5 Ton Split Type AC outdoor unit with reciprocating compressor complete all as specified and directed by Engr-in-Charge.
Supply & fix in repair 2 Ton Split Type AC indoor unit complete all as specified and directed by Engr-in-Charge.
Supply & fix in repair 2 Ton Split Type AC outdoor unit with reciprocating compressor complete all as specified and directed by Engr-in-Charge.
S&F in replacement of compressor unit suitable for 1.5 Ton Split type AC including necessary gas charging . Note : The rate quoted by the tendred shall be inclusive of cost of refrigerant Gas ( 134A) as required for the Split type AC.
S&F in replacement of compressor unit suitable for 2 Ton Split type AC including necessary gas charging . Note : The rate quoted by the tendred shall be inclusive of cost of refrigerant Gas (134A) as required for the Split type AC.
S&F in replacement of compressor unit suitable for 40/80 Ltr water Cooler including necessary gas charging . Note : The rate quoted by the tendred shall be inclusive of cost of refrigerant Gas the charging Gas (134A) as required for the water Cooler.
S&F in replacement of compressor unit suitable for 190 Ltr refrigerator including necessary gas charging . Note : The rate quoted by the tendred shall be inclusive of cost of refrigerant Gas the charging Gas (134A) as required for the refrigerator.
Supply& fix in repair blower Fan (PVC) for split type AC upto 2 ton complete all as specified and directed by Engr-in-Charge.
Supply & Fix in repair fan motor for Split type AC upto 2.0 ton complete all as specified and directed by Engr-in-Charge.
Supply & Fix in repair swing motor for lower shutter of AC upto 2.0 ton capacity complete all as specified and directed by Engr-in-Charge.
M&L for Gas charging of refrigerant 134A complete all as specified and directed by Engr-in-Charge.
Supply and fix in repairs PCB board suitable for 1.5 Ton split type AC complete all as specified and directed by Engr-in-Charge.
Supply and fix in repairs PCB board suitable for 2 Ton split type AC complete all as specified and directed by Engr-in-Charge.
Supply and fix in repairs PCB board suitable for 3 Ton castle type AC complete all as specified and directed by Engr-in-Charge.
Taking down carefully u/s PCB at existing AC and repair and refixing at the same split AC capacity 1.5 ton complete all as specified and directed by Engr-in-Charge.
Taking down carefully u/s PCB at existing AC and repair and refixing at the same split type AC capacity 2 ton complete all as specified and directed by Engr-in-Charge.
Supply & fix in replacement remote for split/window type AC up to 2 ton capacity complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair display board for upto 2 Ton AC complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair Sensor for indoor unit upto 2 Ton AC complete all as specified and directed by Engr-in-Charge.
Taking out voltage styabilizer by disconnecting existing cable for u/s stabilizer of upto 5 KVA capacity including repairing/replacement of push on switch,relay transistor,diode,voltmeter,indicator lamp,high low cutout complete parts along with testing and commissioning and transporation charges from site to workshop and back complete all as specified and directed by Engr-in-Charge.
Taking out voltage styabilizer by disconnecting existing cable for u/s stabilizer of upto 7.5 KVA capacity including repairing/replacement of push on switch,relay transistor,diode,voltmeter,indicator lamp,high low cutout complete parts along with testing and commissioning and transporation charges from site to workshop and back complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair copper pipe 1/2" dia complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair copper pipe 1/4" dia complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair brass service valve 1/2" dia complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair brass service valve 1/4" dia complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair water cooler tape capacity 40/80 ltr of any make/model complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair thermostate switch of refrigerator/deep freezer of capacity 280/310 ltr of any make/model complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair over load relay of refrigerator/deep freezerof capacity 280/310 ltr of any make/model complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair heavy duty AC stand /outdoor unit mounting bracket suitable for 1.5/2 Ton AC including PCC and masonry work complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair over load relay of water cooler of capacity 40/80 ltr of any make/model complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cooling coil of refrigerator/deep freezer of capacity up to 310 ltr of any make/model complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair relay of refrigerator/deep freezer of capacity upto 310 ltr of any make/model complete all as specified and directed by Engr-in-Charge.
S&F in repair, insulation tube (size 1/4''/1/2'') for split type AC s to insulation copper pipe complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair factory made sheet metal enclosure single pole & neutral with a two pin & earth plug and socket of 20 amps capacity complete all as specified and directed by Engr-in-Charge.
M/s Sashi Enterprise (BID ID -3285520)
M/s Pramillabh Construction (BID ID -3285466)
Bidder Name
kabitaconstruction
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .