| Sl No | Description | Qty | Unit | AMAN CONSTRUCTION CO L3 | A Z ELECTRICAL L2 | Siddhivinayak Enterprises L1 |
|---|---|---|---|---|---|---|
| 1.00Online UPS- Input supply: Three Phase, Output supply: Three Phase - 10 kVA ( Each Power module shall be < 10 KVA) | ||||||
| 1.01 | Supplying, installation, Testing & Commissioning of of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 deg C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swappable (allow for the replacement or addition ofbattery modules without shutting down the entire system) modular PowerSupply (UPS) system with N+1 modules (N denotes total number of moduels
requird for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch alongwith provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant.
International standards such as IEC/EN/VDE. The operating efficiency of theUPS systems shall be >96% while operating on battery mode and deliveringquality power to the 100% non-linear loads. Current total harmoniceffect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC (inductor (L) and a capacitor (C)) filters shall be included in UPS cost),extreme power factor kit to be included to limit the input power factor (PF) to0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall bekva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC :3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt,50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output.d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage.f)Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Overtemperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit /Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data:No. of power failures / Transfers to Bypass / Total Running time, etc. i) MainsMode of Operation /Battery Mode of Operation / Bypass feeding the load /UPS Fault /Battery charging and discharging, overload, battery voltage and
battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPSOverload, Fault, Shutdown, Input Over, Under Voltage, Output Over, UnderVoltage, Battery Over, Under Voltage, Over Load and short circuit, OverTemperature. The UPS should have QR code which should contain | 1 | each | 2,47,851.54 ₹2,47,851.54 | 2,39,078.04 ₹2,39,078.04 Lowest | 2,52,023 ₹2,52,023 |
| 2.00 | SITC 12V+26AH battery(make: Exide, Luminous, microtek or equivalent) all complete as per direction of EIC | 30 | each | 1,36,684.8 ₹1,36,684.8 | 1,31,846.4 ₹1,31,846.4 | 1,00,800 ₹1,00,800 Lowest |
| 3.00 | SITC of Invertor : Inverter Type: Pure Sine Wave Model No. : JM SW 2500=/24V Make : Microtek, Luminous Equivalent Display: LCD display all complete as per direction of EIC | 2 | each | 51,802.6 ₹51,802.6 | 49,968.88 ₹49,968.88 | 19,720 ₹19,720 Lowest |
| 4.00 | SITC of 63A MCCB(make Havells)confirming to IS/IEC 60947-2 all complete as per instruction of EIC all complete as per direction of EIC | 2 | each | 75,936 ₹75,936 | 73,248 ₹73,248 | 10,600 ₹10,600 Lowest |
| 5.00 | SITC of C63A MCB(make Legrands)confirming to IS/IEC 60947-2 all complete as per instruction of EIC all complete as per direction of EIC | 20 | each | 70,003.6 ₹70,003.6 | 67,525.6 ₹67,525.6 | 4,200 ₹4,200 Lowest |
| 6.00 | SITC of 160 aH Battery (make: Livguard, Luminous or equivalent, warrenty:36 months) | 8 | each | 1,43,367.2 ₹1,43,367.2 | 1,38,292.24 ₹1,38,292.24 Lowest | 1,51,552 ₹1,51,552 |
Tender Value
₹6.4 L
EMD Value
₹12,843
Closing Date
18 Aug 2025, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Regional Director
SAI NSRC Lucknow
SITC of 10KVA 3-phase UPS including batteries and invertors for various locations at SAI NSRC Lucknow.
2025_SAI_872361_1
SAI/NSR CL/LKO/I NFRA/NIT-LKO ELCT/2025-26/ CN 67940
Limited
Electrical Works
Works
30 days
SAI NSRC Lucknow
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹12,843
Yes
19 Aug 2025
7 Aug 2025
19 Aug 2025
7 Aug 2025
18 Aug 2025
7 Aug 2025
7 Aug 2025 - 14 Aug 2025
Online UPS- Input supply: Three Phase, Output supply: Three Phase - 10 kVA ( Each Power module shall be < 10 KVA)
Supplying, installation, Testing & Commissioning of of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 deg C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swappable (allow for the replacement or addition ofbattery modules without shutting down the entire system) modular PowerSupply (UPS) system with N+1 modules (N denotes total number of moduels requird for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch alongwith provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant. International standards such as IEC/EN/VDE. The operating efficiency of theUPS systems shall be >96% while operating on battery mode and deliveringquality power to the 100% non-linear loads. Current total harmoniceffect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC (inductor (L) and a capacitor (C)) filters shall be included in UPS cost),extreme power factor kit to be included to limit the input power factor (PF) to0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall bekva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC :3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt,50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output.d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage.f)Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Overtemperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit /Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data:No. of power failures / Transfers to Bypass / Total Running time, etc. i) MainsMode of Operation /Battery Mode of Operation / Bypass feeding the load /UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPSOverload, Fault, Shutdown, Input Over, Under Voltage, Output Over, UnderVoltage, Battery Over, Under Voltage, Over Load and short circuit, OverTemperature. The UPS should have QR code which should contain
SITC 12V+26AH battery(make: Exide, Luminous, microtek or equivalent) all complete as per direction of EIC
SITC of Invertor : Inverter Type: Pure Sine Wave Model No. : JM SW 2500=/24V Make : Microtek, Luminous Equivalent Display: LCD display all complete as per direction of EIC
SITC of 63A MCCB(make Havells)confirming to IS/IEC 60947-2 all complete as per instruction of EIC all complete as per direction of EIC
SITC of C63A MCB(make Legrands)confirming to IS/IEC 60947-2 all complete as per instruction of EIC all complete as per direction of EIC
SITC of 160 aH Battery (make: Livguard, Luminous or equivalent, warrenty:36 months)
A Z ELECTRICAL (BID ID -3267897)
AMAN CONSTRUCTION CO (BID ID -3267914)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .