Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.2 LAccepted-AOC | ₹31.2 L | L1 | Accepted-AOC BEING L1 |
| 2 | L2₹31.8 LRejected-Finance H NO 698 SECTOR 10 PANCHKULA HARYANA 134109 | PANCHKULA | PANCHKULA | HARYANA | 134109 | ₹31.8 L | L2 | Rejected-Finance OTHER THAN L1 |
| 3 | L3₹97.2 LRejected-Finance | ₹97.2 L | L3 | Rejected-Finance OTHER THAN L1 |
| 4 | L4₹39.4 LRejected-Finance | ₹39.4 L | L4 | Rejected-Finance OTHER THAN L1 |
| 5 | L5₹42.0 LRejected-Finance | ₹42.0 L | L5 | Rejected-Finance OTHER THAN L1 |
| Sl No | Description | Qty | Unit | ASIA ENTERPRISES L3 | KULBHUSHAN AGGARWAL L5 | M/S JIWAN SINGH L4 | M/S VIRENDER SADHOTRA L1 | bharat contrectors L2 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, laying, testing and commissioning HT XLPE cable, insulated, screended, PVC bedded, galvanised steel strip or wire armoured, electic power cable (heavy duty) with multistaranded aluminium conductor, conforming to IS : 7098 (Part II), 11000 Volts "E" grade, cross sectional area 3 core x 120 sqmm (Earthed) laid in trenches/ ducts/under plinth floors passing through pipes etc, fixed on wall complete all as specified and directed. | 400 | Running Metre | 1,600 ₹6.4 L | 1,225 ₹4.9 L | 1,322 ₹5.3 L | 1,500 ₹6 L | 1,100 ₹4.4 L |
| 2.00 | Supply, laying & testing of LT cable XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts, grade cross sectional area 185sqmm 3.5 core, complete all as specified and directed. | 100 | Running Metre | 1,900 ₹1.9 L | 1,575 ₹1.6 L | 1,952 ₹2.0 L | 1,500 ₹1.5 L | 1,500 ₹1.5 L |
| 3.00 | S & F Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11.00 metres long) with necessary excavation, foundation and coping including applying two coats of of exterior weather proof paint of approved colour to pole and to MS cross arms, cable protection pipe, brackets etc with two coats of Aluminium Paint over a coat of red oxide primer including Synthetic enamel Painting in alternate lines of Yellow & Black Strips min of 6 Nos (each Strip 200 mm wide) at bottom of pole complete all as specified and directed. Note:- Earth work, Cement Concrete etc. will be measured and paid under approprite Items. | 6 | Each | 32,000 ₹1.9 L | 23,500 ₹1.4 L | 26,500 ₹1.6 L | 26,000 ₹1.6 L | 20,000 ₹1.2 L |
| 4.00 | M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed | 4.8 | Quintal | 12,000 ₹57,600 | 9,900 ₹47,520 | 5,500 ₹26,400 | 14,000 ₹67,200 | 10,000 ₹48,000 |
| 5.00 | M & L of lightening arresters nominal discharge current Peak 65 KA rating, suitable for operation on HT 11000 volts system, comprising of zinc oxide disks, electrodes, fibre re-in forced composite structure, non tracking weather resistant shedded heat shrinked polymeric housing for withstanding from the effects of pollution, rain, heat and with moisture seal , stainless steel bolts and nuts, stainless steel end fitting cups and fixing arrangements complete all as specified and directed. | 3 | Set of three | 5,000 ₹15,000 | 5,000 ₹15,000 | 2,500 ₹7,500 | 12,000 ₹36,000 | 5,000 ₹15,000 |
| 6.00 | M&L for Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron strep 32 x 6 mm as earthing lead by mean of nut/bolt and washer of galvanized iron or steel drawn through 40 mm dia light grade GI pipe as shown in electrical plate no 3 of SSR part I of 2009 including necessary excavation and earth work GI pipe 20mm dia light grade for watering PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to panel board as indicated including testing complete. Note:- (i) Item includes the cost of 7.5 metre GI pipe for protection of earth lead. (ii) Item includes the cost of 7.5 metre GI earth lead. (iii) The required resistance of Earthing shall be 2 ohm or less than 2 ohm, If not found to the required resisstance, the contractor has to reorganised for required resistance and the cost for the same included in the quoted rate and no extra shall be paid on failure of getting required resistance. | 24 | Each Set | 4,000 ₹96,000 | 4,500 ₹1.1 L | 2,800 ₹67,200 | 6,500 ₹1.6 L | 4,500 ₹1.1 L |
| 7.00 | Supply, installation, connecting electrically & commissioning switch air break, gang operated, tripple pole mounted on insulators 15 Nos and steel frame with operating mechanism in worked from ground level, drop out fuse, for current rating upto 400 amps and working voltage 11000 volts all as required at site complete all as specified and directed. | 2 | Each | 22,000 ₹44,000 | 18,000 ₹36,000 | 14,500 ₹29,000 | 7,200 ₹14,400 | 12,000 ₹24,000 |
| 8.00 | Supply anf fixing of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqm complete all as specified and directed. | 4 | Each | 3,000 ₹12,000 | 3,500 ₹14,000 | 2,500 ₹10,000 | 6,300 ₹25,200 | 10,000 ₹40,000 |
| 9.00 | Supply and installation, commissioning and testing CPRI approved OEM made main LT Panel. The panel shall be made of modula CRCA ENCLOSURES including MCCBs and Indicator lamps which shall be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel shall be anti-acid & anti corrosive. Degree of protection against mechanical load shall be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy ofCPRI TEST REPORT only also share panel assembled by OEM, channel partner or sister concern assembly will not be accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket shall be internally embedded made of polyurethane. The Panels made by aprroved enclosures in MES & they shall submit a copy of TYPE TEST REPORT of a board made out of CRCA accordance with IEC 60439-1. The ASTA CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current-Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The board manufacturer shall submit the copy of type test reports for CRCA Board only. Each Board shall have individual routine test report of the manufacturer. The panel shall pass glow wire test 960 degrees Centigrade in accordance with 60695-2-11 [flame retardant and self extinguishing) comprising the following accessories:-
INCOMER: (a).Main MCCB 400 amp 4Pole Breaking Capacity 36KA Thermal and Magnetic Released with Spreader Links & Extended Rotary Handle-1 No.
(b) Digital VAF meter Voltmeter (0-500 volt) ammeter (0-500 amp) frequency -01 no 3. LED Indicator Lamp R,Y,B-3 Nos 4. Control Fuse-3 No 5. CT coils 250/5A-3 Nos
OUTGOING: (a) MCCB 160 Amp 4Pole Breaking Capacity 25 KA Thermal and Magnetic Released with Spreader Links & Rotary Handle-2 Nos. Make-Legrand/ABB/Schnleder/L&T.
(b) MCCB 100 Amp 4Pole Breaking Capacity 25 KA Thermal and Magnetic Released with Spreader Links & Rotary Handle-3 Nos.
Note: Fixing, Labour charges, including Cable Glands, Lugs, connected items such as Nuts, Bolts, Washers etc., earth work and PCC work charges are deemed to be included in quoted rates. | 1 | Each | 1,00,000 ₹1 L | 3,10,000 ₹3.1 L | 2,25,000 ₹2.3 L | 1,25,000 ₹1.3 L | 2,50,000 ₹2.5 L |
| 10.00 | Construction of transformer platform size 3mx2mx1m from ground incl XPM jalli fabricated with angle size 50x50x6mm and two coat of aluminum paint over one coat of red oxide inci steps plinth protection and all other relevant works complete all as specified and directed. | 2 | Each Job | 70,000 ₹1.4 L | 30,000 ₹60,000 | 40,000 ₹80,000 | 65,000 ₹1.3 L | 25,000 ₹50,000 |
Updated dates
Tender Value
₹39.0 L
EMD Value
₹78,100
Closing Date
14 Mar 2026, 6:00 pmClosed
Anurag Anand DCWE
HQ 135 WKS ENGRS PIN- 914135 C/O 56 APO
UNDER GE (N) AKHNOOR (Only external electric supply) AND PROVN OF BOREWELL AND CONNECTED CONNECTED ITEMS FOR AUGMENTATION OF WATER SUPPLY under GE (N) AKHNOOR (Only external electric supply)
2026_MES_751804_1
CWE/JA-42/2025-26
Open Tender
Electrical and Maintenance Works
180 days
AKHNOOR
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
GE NORTH AKHNOOR
₹78,100
Yes
11 May 2026
7 Feb 2026
16 Mar 2026
7 Feb 2026
14 Mar 2026
28 Feb 2026
Supply, laying, testing and commissioning HT XLPE cable, insulated, screended, PVC bedded, galvanised steel strip or wire armoured, electic power cable (heavy duty) with multistaranded aluminium conductor, conforming to IS : 7098 (Part II), 11000 Volts "E" grade, cross sectional area 3 core x 120 sqmm (Earthed) laid in trenches/ ducts/under plinth floors passing through pipes etc, fixed on wall complete all as specified and directed.
Supply, laying, testing and commissioning HT XLPE cable, insulated, screended, PVC bedded, galvanised steel strip or wire armoured, electic power cable (heavy duty) with multistaranded aluminium conductor, conforming to IS : 7098 (Part II), 11000 Volts "E" grade, cross sectional area 3 core x 185 sqmm (Earthed) laid in trenches/ ducts/under plinth floors passing through pipes etc, fixed on wall complete all as specified and directed.
S & F Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11.00 metres long) with necessary excavation, foundation and coping including applying two coats of of exterior weather proof paint of approved colour to pole and to MS cross arms, cable protection pipe, brackets etc with two coats of Aluminium Paint over a coat of red oxide primer including Synthetic enamel Painting in alternate lines of Yellow & Black Strips min of 6 Nos (each Strip 200 mm wide) at bottom of pole complete all as specified and directed. Note:- Earth work, Cement Concrete etc. will be measured and paid under approprite Items.
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed
M & L of lightening arresters nominal discharge current Peak 65 KA rating, suitable for operation on HT 11000 volts system, comprising of zinc oxide disks, electrodes, fibre re-in forced composite structure, non tracking weather resistant shedded heat shrinked polymeric housing for withstanding from the effects of pollution, rain, heat and with moisture seal , stainless steel bolts and nuts, stainless steel end fitting cups and fixing arrangements complete all as specified and directed.
Supply, installation, connecting electrically & commissioning switch air break, gang operated, tripple pole mounted on insulators 15 Nos and steel frame with operating mechanism in worked from ground level, drop out fuse, for current rating upto 400 amps and working voltage 11000 volts all as required at site complete all as specified and directed.
Supply anf fixing of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqm complete all as specified and directed.
Construction of transformer platform size 3mx2mx1m from ground incl XPM jalli fabricated with angle size 50x50x6mm and two coat of aluminum paint over one coat of red oxide inci steps plinth protection and all other relevant works complete all as specified and directed.
Shifting of transformer from site not more then 200 KVA from the Garrison including loading and unloading on newly constructed platform complete all as specified and directed. Note:- Any damage to the tranformer during loading and unloading shall be bear by contractor.
Excavation in trenches n. exc.1.5m wide and n. exc. 1.5m in depth for foundation of pole and laying of HT/LT cables as in soft/loose soil and getting out complete all as specified and directed.
Returning filling in including spreading, levelling, watering and wall ramming in layers not exc 25cm in soft/loose soil complete all as specified and directed
Removal of excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point
Supply and laying sub class 'B' bricks laid dry flat transversely along the length of cable with width equal to the length of bricks over sand cushioning as protection cover of cable laid complete all as specified and directed.
Material and labour for sand cushioning in trenches including spreading and consolidation in layers of 8cm thick before laying the cable & 15 cm thick after laying the cable and punned down to form a bed complete all as specified and directed.
Supply & Fixing of HT feeder pillar box autdoor type factory made weather and vermin proof made out from 3.15 mm sheet supported with legs all across the panel made of angle iron 50x50x5mm of size 1.2 m x 1.0 m x 1.0 m with 3 Nos required length aluminium bus bar of size 40x10mm or 400 Ampe for 11 KV post insulator 6 Nos duly drilled hole for HT Cable connection including front and rear side openable with locking arrangment suitable for 11 KV HT and provision for incoming and out going HT cable connection including painting with two coats of smoke gray synthetic enamels paint over a coat of red oxide primer complete and providing security fence XPM jally type of 2 mtr height from ground level square type all rounded 2.5 mtr length with 9 nos angle iron of 25x25x5mm of height 2.25mtr (2 mtr above ground 0.25 mtr under ground) including necessary location gate of same XPM jally all as specified and directed. Note:- Feeder piller box shall be mounted on brick platform built in PCC not less then 60 cm above ground level with suitable PCC foundation rendering 15 mm in CM (1.6), applying two coats and cement base paints and XPM jally supported on 9 nos angle iron with concrete base.
M&L of PCC 1:48 type D2 using 40 mm graded crushed stone aggregate in foundation of electric poles including necessary from work and exposed surfaces finished fair without using extra cement complete all as specified and directed
M&L of PCC 1:3:6 type D2 using 40 mm graded crushed stone aggregate in foundation of electric poles including necessary from work and exposed surfaces finished fair without using extra cement complete all as specified and directed
Supply and installation of voltage stabilizer for auto matic operation, three phase naturally Oil cooled indoor type and designed input variation between 300 Volts to 480 volts with out put voltage stabilized at 415 Volts with accuraccy + 2.5 % and speed of correction 8 Volts per Second and of capacity 100 KVA, including first fill of transformer Oil having dielectric strength of 60 Kv with 3 mm gap, construction of suitable PCC foundation including making of connections and testing complete all as specified and directed.
Supply, laying & testing of HT Cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables(heavy duty) with stranded aluminium conductor, 11000 volts, grade cross setional area 95 sq mm, 3 core complete all as specified and directed.
Supply, laying & testing of LT Cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables(heavy duty) with stranded aluminium conductor, 1100 volts, grade cross setional area 95 sq mm, 3.5 core complete all as specified and directed.
Material and labour for Air break gang operated switch with 12 Nos insulators outdoor type, triple pole, mechanically operated, suitable for vertical installation, single break, provided with locking arrangement, consisting of MS Channel, HT post type insulator copper alloy, high pressure, assembly drop out fuses, operating rod 25mm dia GI pipe, medium grade for operating from 1.2 m above GL complete including drop out fuses conforming to IS rated voltage 11 KV and for current rating 200 Amp complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 sqmm complete all as specified and directed.
M&L for LED flood light of capacity 250 watt IP 66 Lumainire with aluminium die cast housing toughened glass and unique lens system for enhancement illumination complete with all accessories complete all as specified and directed. Make Wipro cat part No LF3 -342-060-57XX or equivalent in specification of make phillips, Oshram,wipro
Supply ,installation ,testing and commissioning og indoor type microprocessor based power factor correction system APFC panel MD-XL(mixed die-electric cpacitor of 30 KVAR and incoming MCCB with suitable steps having auto switching system for each stage in the form of electromagnetic switching system for energising each capacitor stage should have the current carrying capacity not less than 1.5 times the charging current of the respective stage shall carry a back up protection in the form of tripple pole MCB of rating not less than 2 times charging current. The outer shell of APFC shall be made up of 2mm thick CRCA sheet steel and MS angle section 50x50x6mm frame factory fabricated with front and back openable single door system lockable openable by keys from both sides having 19mm dia fancy locks detachable plate having provision for entry of armoured cable of adequate size with glands.The outer shell be powder coated with siemen grey shade complete all as specified and directed
Supply ,installation ,testing and commissioning of LT Panel Board, indoor type of suitable size as per relevent IS, mounted on angle iron legs of size 40x40x6mm embedded in PCC 1:2:4 block type B-2 (using 40 mm graded aggregates) at pump house, floor mounting, dust and vermin proof, factory made, fabricated out of 2 mm thick CRCA sheet suitable for 3 Phase, 415 Volt, 50HZ AC Supply, busbar chamber with aluminum busbar of suitable amp rating for 3 Phase and 4 wire system duly insulated with heat shrinkable sleeve as per colour, supported on epoxy insulator 01 set, common earth bus of 25mm x 4mm at bottom inside panel board with two earth terminal out side panel board, cable alley cable gland with independent plate at bottom and complete panel board painted with powder coating in grey colour all as specified & directed, The panel should be IS/IEC 61439-I&II- TTA. The Panel builder should submit Test Certificate along with GA drawing before executing the job. (Note: Panel shall be a front/rear opening with cable entry from the bottom) comprising the following accessories:- (a) MCCB 160 Amps,thermal adjustable and magentic setting having rupturing capacity 36 KA (Ics= 100% Icu) , TP, 415 volts, 50 Hz, along with Extended Ratory handle ,Spreader terminal and phase barrier - 01 No. (b) Supply, installation, testing and commissioning of Soft Starter 60 H.P. (c) Supply, installation, testing and commissioning contactors, relays, CT timers, for suitable rating having with ON, OFF , Trip Indicating Light, Push Buttons, Digital MFM along with contactor & semiconductor fuses with , Control Fuse etc fitted in Panel board for showing V, I, Hz, Pf
Installation only Transformer capacity 160 KVA on constructed platform incl transportation of same from MES Complex , connection of cables of HT and LT side of transformer complete all as specified and directed. Note Transformer shall supplied by MES and any damage during loading and unloading shall bear by the contractor without any extra cost.
M&L for steel tubular swaged pole type 410 SP-31 (9 metre long) with 300 mmx 300mmx6mm mild steel base plate continuously welded to pole, finial taper, nut, bolts and screws all as specified including factory painted with two coats of black bituminous paint internally through out and externally for embedded portion and applying one coat of red oxide primer for the remaining portion and two coats of aluminium paint beyond 1.5m from ground level/coping and making 30cm black and white strips with two coats of super enameled paint up to 1.5m from ground level/coping, complete all as specified and directed.
All as per serial item No 12 above but depth exceeding 1.5 m and not exceeding 3 mtrs.
Fabrication of CGI sheet open shed of size 12'x9' for accomodating LT panels, voltage stabilizers , Including angle iron truss ,PCC INCLUDING MS Pipe 100 mm dia for post flooring and brick work upto 5 feet height from ground and above 4 feet welded jali 4 mm dia to be used total height of the shed is 9 feet from ground flooring complete all as specified.
Supply, laying & testing of LT Cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables(heavy duty) with stranded aluminium conductor, 1100 volts, grade cross setional area 10 sq mm, 2 core complete all as specified and directed.
Supply, laying & testing of LT copper flexible Cable armoured 2.5 Sqmm 2 Core complete all as specified and directed.
Note:- Deduction for Schedule of credit (Sch 'A' Part-II) to be made of ₹ 00.00 from the total quoted amount of BOQ while accepting the bid. Details of schedule of credit is given in tender documents.
Please Enable Macros to View BoQ information
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.34 MB
BOQ_842055.xls
BOQ • 1.82 MB
TENDER42.pdf
Tender Documents • 1.12 MB
Download all tender documents and submit your bid