Executive Engineer, ED-3rd srinagar
Office of Executive Engineer, ED-3rd srinagar
Creation of 02 no. 63 KVA feasible substations at different locations (01 no. at Kreshbal and 01 no. at Sangam) under Capex Budget 2023-24 work code-PDDSS2022100302 falling under the jurisdiction of ESD Nawakadal, ED 3rd (Partial Turnkey Basis)
2023_PDD_227518_1
ED-III /13 of 2023-24, Dated - 26-08-2023
Open Tender
Electrical Works
Turn-key
30 days
Office of Executive Engineer, ED-3rd srinagar
Refer SBD, Specification, Drawings
7 documents required · 7 mandatory
₹500
Executive Engineer, ED-3rd srinagar
₹8,870
5 Oct 2023
26 Aug 2023
29 Sept 2023
26 Aug 2023
28 Sept 2023
31 Aug 2023
31 Aug 2023 - 28 Sept 2023
Amount
Creation of 02 no. 63 KVA feasible substations at different locations (01 no. at Kreshbal and 01 no. at Sangam) under Capex Budget 2023-24 work code- PDDSS2022100302 falling under the jurisdiction of ESD Nawakadal, ED 3rd (Partial Turnkey Basis)
Installation, testing and commissioning (including loading/ unloading/ carriage from Divisional store to site) of 63 KVA, 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Al wound, and with LV Cable Box having detachable Al. Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable. ( X-mer without OCTC (Off Ckt Tap Changer)) including integration with system by way of providing Clamps/Jumpers/necessary items required for commissioning (Transformer to be provided departmentally) 1. Sangam - 01 no. 2. Kreshbal -01 no.
Installation, testing and commissioning (including loading/ unloading/ carriage from Divisional store to site) of S.T. poles 9.0 Meter long swaged Type conforming to ST 410 SP-33, IS: 2713 amended up-to date well finished and coated with black bituminous paint upto plant depth and Red-Oxide coated above ground level with earthing arrangement through bolt welded on pole of 14mm diameter, provided at height of 300mm above the planting depth which should be 1.5ms (SP 33). Top plate 3mm thick fully welded & bottom plate 35cm*35cm, 5mm thick fully welded. (To be Provided Departmentally) 1. Sangam - 05 no. 2. Kreshbal -09 no.
Installation, testing and commissioning (including loading/ unloading/ carriage from Divisional store to site) of S.T. poles 8.0 Meter long swaged Type conforming to ST 410 SP-15, IS: 2713 amended up-to date well finished and coated with black bituminous paint upto plant depth and Red-Oxide coated above ground level with earthing arrangement through bolt welded on pole of 14mm diameter, provided at height of 300mm above the planting depth which should be 1.5ms (SP 15). Top plate 3mm thick fully welded & bottom plate 35cm*35cm, 5mm thick fully welded. (To be Provided Departmentally) 1. Sangam - 02 no. 2. Kreshbal -02 no.
Installation, laying, testing and commissioning (including loading/ unloading/ carriage from Divisional store to site) of 50 mm² ACSR Conductor (Rabbit) (To be Provided Departmentally) 1. Sangam - 450 Mtr 2. Kreshbal -250 Mtr
Supply,installation, testing and commissioning of Gapless Surge Arrestor, 9 kV, 10 kA, Lighting Arrestor Set Heavy duty with Plymer Housing, Station type conforming to IEC-99-4 Capable of withstanding Maximum continuous operating voltages (M.C.O.V) 1. Sangam - 01 set 2. Kreshbal -01 set
Supply, installation, testing and commissioning of 11KV 200 Amperes, Triple pole switches Gang Operated (G.O. Set) conforming: IS-2544, IS: 5340 (Part-III) and SS: 9921 (Part-I -V) 1. Sangam - 01 set 2. Kreshbal -01 set
Supply, installation, testing and commissioning of 11 KV Horn, Gap (fuse 3-phase 200A) as per Relevant IS. 1. Sangam - 01 set 2. Kreshbal -01 set
Supply, installation, testing and commissioning of 70 mm²single core Cable,1.1kV Grade, XLPE Insulated Stranded Conductor FRLS type including lugs/Clamps 1. Sangam - 60 Mtr 2. Kreshbal -60 Mtr
Supply, installation, testing and commissioning of 11KV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm 1. Sangam - 03 no. 2. Kreshbal -03 no.
Supply, fabrication & installation of G.I Channel Iron / Angle Iron /Flat of sizes including clamps and collars 50 x 8 mm 1. Sangam - 369 Kg. 2. Kreshbal -461 Kg.
Supply and fixing of Nuts and Bolts full thread of sizes Galvanized as per IS 1. Sangam - 13 Kg. 2. Kreshbal -17 Kg.
Supply,installation, testing and commissioning of LT Fuse Set for Distribution Transformers (Customised) as per KPDCL Drawing no. CE/P&P/DRG/2023/LTFS/001 1. Sangam -01 Set 2. Kreshbal -01 set
Providng and laying of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts, including baby insulators, refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. 1. Sangam -03 No. 2. Kreshbal -03 No.
Supply, installation, testing and commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm 1. Sangam -12 No. 2. Kreshbal -24 No.
Supply and fixing of Danger Plate With Clamps as per Standards wih writing in English & Urdu. 1. Sangam -04 No. 2. Kreshbal -08 No.
Supply and fixing of Wedge Connectors/PG Clamps 1. Sangam -06 No. 2. Kreshbal -06 No.
Supply and fixing of Anti Climbing devices(GI Barbed Wire (12 SWG) at height of 3.5 meters from Ground Level) 1. Sangam -05 No. 2. Kreshbal -09 No.
Providing and painting of poles with single coat of red oxide an two coats of Aluminum Paint 1. Sangam -07 No. 2. Kreshbal -11 No.
Providing and fixing of Pole Earthing Complete by GI Pipe 40 mm 3mtr long through GI Strip 25x3 mm 1. Sangam -05 No. 2. Kreshbal -09 No.
Supply and fixing of 16 KN Polymer Shackle Insulators including GI U-Clamps for Shackle Insulators 1. Sangam -08 Set 2. Kreshbal -08 Set
supply and fixing of GI Wire 6 SWG & 8 SWG 1. Sangam -15 Kg. 2. Kreshbal -30 Kg
Providing of material and laying of Cement bottoming of poles (1:2:4 Mix as per REC Standards 0.5 M3 per Pole) 1. Sangam -05 No. 2. Kreshbal -09 No.
Providing of material and laying of Cement bottoming of poles (1:2:4 Mix as per REC Standards 0.45 M3 per Pole) 1. Sangam -02 No. 2. Kreshbal -02 No.
SOLARCITY ELECTRICALS AND SUPPLIERS
M/S AL MANSUR CONTRACTORS AND SUPPLIERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .