Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.1 LAccepted-AOC RAM SHIV COLONY GALI NO 2 NAIKA CHATNAG ROAD JHUNSI PRAYAGRAJ UP 211019 | PRAYAGRAJ | UTTAR PRADESH | 211019 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹13.5 L+₹1.4 L (11.4%)Rejected-Finance 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹14.9 L+₹2.8 L (22.9%)Rejected-Finance 59 NEW MARKET CLOCK TOWER DEHRADUN UK PIN 248001 | DEHRADUN | UTTARAKHAND | 248001 | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹18.0 L+₹5.9 L (48.6%)Rejected-Finance CHANDIGARH | CHANDIGARH | CHANDIGARH | 160001 | L4 | Rejected-Finance Other than lowest bidder |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
12 Sept 2024, 6:00 pmClosed
GE (AF) MC CHANDIGARH
GE (AF) MC CHANDIGARH
REPAIR/MAINT TO DG SETS WITH OIL, PANELS IN CERTAIN AREA IN 3BRD AF STATION CHANDIGARH UNDER GE (AF) MC CHANDIGARH
2024_MES_665673_1
GE (AF) MC/CHD/T-13/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
CHANDIGARH
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (AF) MC CHANDIGARH
₹40,000
Yes
8 Nov 2024
12 Jul 2024
14 Sept 2024
12 Jul 2024
12 Sept 2024
26 Jul 2024
Amount
M&L for preparation of rusted surface of DG Set (outer structure) of following capacities of any size/shape/make and painting with two coats of enamel paint with existing colors complete all as specified and as directed.
DG set capacity 10KVA to 50KVA
DG set capacity 62.5KVA to 82.5KVA
DG set capacity 100KVA to 125KVA
DG set capacity 160KVA
DG set capacity 200KVA
DG set capacity 250KVA
DG set capacity 320KVA
DG set capacity 400KVA to 625KVA
M&L for opening tappet cover of engine any make of following capacities DG and carrying out work as under:- (i) Checking and adjusting of tappet clearance. (ii) Cleaning cylinder and piston head by removing carbon deposits (iii) Checking general condition of the engine (iv) Checking and adjustment of operating parameters (v) Checking and adjustment of fuel timing (vi) Checking and adjustment of fault warning system (vii) Checking and adjustment of fasteners (viii) Replacement of the damaged gasket and re-assembling of tappet cover and testing complete all as specified and directed.
DG set capacity 10KVA to 50KVA
DG set capacity 62.5KVA to 82.5KVA
DG set capacity 100KVA to 125KVA
DG set capacity 160KVA
DG set capacity 200KVA
DG set capacity 250KVA
DG set capacity 320KVA
DG set capacity 400KVA to 625KVA
M&L for servicing to DG sets 10 KVA to 50 KVA capacity by replacing following spare parts. The servicing should be carried out by representative of Original Equipment Manufacturer to the entire satisfaction of Engr-in-charge. (a) Fuel Filter (Primary & Secondary) - 01 Set (b) Oil Filter - 01 Set (c) Air filter - 01 No (d) Engine Oil and Coolant - As per capacity of DG Set. Note : Rate of the Spare parts and Engine oil and coolant deemed to be included in quoted rate.
M&L for servicing to DG sets 62.5 KVA to 82.5 KVA capacity by replacing following spare parts. The servicing should be carriedout by representative of Original Equipment Manufacturer to the entire satisfaction of Engr-in-charge. (a) Fuel Filter (Primary & Secondaroy) - 01 Set, (b) Oil Filter - 01 Set, ( c) Air filter - 01 No (d) Engine Oil and Coolant - As per capacity of DG Set. Note : Rate of the Spare parts and Engine oil and coolant deemed to be included in quoted rate.
M&L for servicing to DG sets 100 KVA to 125 KVA capacity by replacing following spare parts. The servicing should be carried out by representative of Original Equipment Manufacturer to the entire satisfaction of Engr-in-charge. (a) Fuel Filter (Primary & Secondaroy) - 01 Set, (b) Oil Filter - 01 Set, (c) Air filter - 01 No ( d) Engine Oil and Coolant - As per capcity of DG Set. Note : Rate of the Spare parts and Engine oil and coolant deemed to be included in quoted rate.
M&L for servicing to DG sets 160 KVA capacity by replacing following spare parts. The servicing should be carried out by representative of Original Equipment Manufacturer to the entire satisfaction of Engr-in-charge. (a) Fuel Filter (Primary & Secondaroy) - 01 Set, (b) Oil Filter - 01 Set, (c) Air filter - 01 No (d) Engine Oil and Coolant - As per capcity of DG Set. Note : Rate of the Spare parts and Engine oil and coolant deemed to be included in quoted rate.
M&L for servicing to DG sets 200 KVA capacity by replacing following spare parts. The servicing should be carried out by representative of Original Equipment Manufacturer to the entire satisfaction of Engr-in-charge. (a) Fuel Filter (Primary & Secondaroy) - 01 Set, (b) Oil Filter - 01 Set, (c) Air filter - 01 No (d) Engine Oil and Coolant - As per capcity of DG Set. Note : Rate of the Spare parts andEngine oil and coolant deemed to be included in quoted rate.
M&L for servicing to DG sets 250 KVA capacity by replacing following spare parts. The servicing should be carried out by representative of Original Equipment Manufacturer to the entire satisfaction of Engr-in-charge. ( a) Fuel Filter (Primary & Secondaroy) - 01 Set, ( b) Oil Filter - 01 Set, ( c) Air filter - 01 No ( d) Engine Oil and Coolant - As per capcity of DG Set. Note : Rate of the Spare parts and Engine oil and coolant deemed to be included in quoted rate.
M&L for servicing to DG sets 320 KVA to 400KVA capacity by replacing following spare parts. The servicing should be carried out by representative's of Original Equipment Manufacturer to the entire satisfaction of Engr-in-charge. ( a) Fuel Filter (Primary & Secondaroy) - 01 Set, (b) Oil Filter - 01 Set, (c) Air filter - 01 No d) Engine Oil and Coolant - As per capcity of DG Set. Note : Rate of the Spare parts and Engine oil deemed to be included in quoted rate.
M&L for servicing to DG sets 500 KVA to 625 KVA capacity by replacing following spare parts. The servicing should be carried out by representative's of Original Equipment Manufacturer to the entire satisfaction of Engr-in-charge. (a) Fuel Filter (Primary & Secondaroy) - 01 Set, (b) Oil Filter - 01 Set, (c) Air filter - 01 No (d) Engine Oil and Coolant - As per capcity of DG Set. Note : Rate of the Spare parts and Engine oil and coolant deemed to be included in quoted rate.
M&L for top up lubrication oil Viscosity No SAE 15W/40 for DG sets of capacity 10 KVA to 625 KVA at different locations for top up of the Engine tank complete all as specified and directed. MAKE : Servo /Castrol/Veedol
S&F in replacement of battery 12 volts 150 AH with 25 Nos plates complete all as directed. Make; Exide - (Little Champ) FLCO-EXLC150R , TATA GREEN - 150G51CV, LUMINOUS - IG 1500
S&F in replacement of battery 12 volts 180 AH with 25 Nos plates comple all as directed. Make; Exide - (Little Champ) FLCO-EXLC180R , TATA GREEN - 180H52CV, LUMINOUS - IL22000
S&F in replacement of Auto Voltage Regulator suitable for 50 KVA to 160 KVA , 415 V AC as per existing make and pattern complete all as specified and directed. Make: Kirloskar/Stamford/Ashok Lyland
S&F in repalacement of Auto Voltage Regulator suitable for 200 KVA to 625 KVA , 415 V AC as per existing make and pattern complete all as specified and directed. Make: Kirloskar/Stamford/Ashok Lyland
M&L in repair of self starter 12 volts duly rewinding of armature and replacement of unservicable spare parts etc DG Sets capacity from 10KVA to 100KVA DG set including testing complete all as specified and directed.
M&L in repair of self starter 24 volts duly rewinding of armature and replacement of unservicable spare parts etc DG Sets capacity from 125KVA to 625KVA DG set ncluding testing complete all as specified and directed.
M&L in repair of battery charger including rewinding of transformer and replacement of rectifier,toggle switches,voltmeter, ammeter & MCB etc of capacity 12 volts complete all as specified and directed.
M&L in repair of battery charger including rewinding of transformer and replacement of rectifier,toggle switches,voltmeter, ammeter & MCB etc of capacity 24 volts complete all as specified and directed.
S&F in repair of battery charger including copper wound transformer, rectifier, toggle switches, voltmeter, AM meter & MCB etc of capacity 12 volts complete all as specified and directed.
S&F in repair of battery charger including copper wound transformer, rectifier, toggle switches, voltmeter, Ampmeter & MCB etc of capacity 24 volts complete all as specified and directed.
S&F in replacement of battery lead copper of 50 sqmm as per sample ( Red and Black colour ) battery lead all as specified and directed.
S&F in replacement of heavy duty battery terminal positive marking /negetaive marking of brass of existing size battery terminal complete all as specified and directed.
M&L for top up coolent for DG sets complete all as specified and directed. Make: CASTROL - RADICOOL HEAVY DUTY COOLANT or Equivalent of SERVO , VEEDOL
S&F in replacement of MCCB 4 pole 160 Amps with adjustable type 36 KA breaking capacity complete all as specified and directed. Make Schneider Cat Part No LV430780 or equivalent make of Hager/ABB/Legrand/Havells
S&F in replacement of MCCB 4 pole 200 Amps with adjustable type 36 KA breaking capacity complete all as specified and directed. Make Schneider Cat Part No LV430780 or equivalent make of Hager/ABB/Legrand/Havells
S&F in replacement of MCCB 4 pole 250 Amps with adjustable type 36 KA breaking capacity MCCB all as specified and directed. Make Schneider Cat Part No LV431780 or equivalent make of Hager/ABB/Legrand/Havells
S&F in replacement of MCCB 4 pole 400 Amps with adjustable type, 36 KA breaking capacity complete all as specified and directed. Make Schneider Cat Part No LV432677 or equivalent make of Hager/ABB/Legrand/Havells
S&F in replacement of MCCB 4 pole 630 Amps with adjustable type,50 KA breaking capacity complete all as specified and directed. Make Schneider Cat Part No LV432677 or equivalent make of Hager/ABB/Legrand/Havells
S&F in replacement of off load Change over switch 4 pole of capacity 400 Amps, AC, 50 Hz, 415 volts with sheet steel enclosure out door type all as directed. Make:Cat No IHCFFE0400 of HAVELLS or equivalent C & S, Legrand
S&F in replacement of off load Change over switch 4 pole of capacity 630 Amps, AC, 50 Hz, 415 volts with sheet steel enclosure out door type all as directed. Make: Cat No IHCFFE0630 of HAVELLS or equivalent C & S,Legrand
S&F in replacement of Dynamo Assy from 10KVA to 50 KVA DG Set to its original position complete all as directed.
S&F in replacement of Dynamo Assy from 62.5 KVA to 82.5KVA DG Set to its original position complete all as directed.
S&F in replacement of Dynamo Assy from 125 KVA to 625 KVA DG Set to its original position complete all as directed.
S&F in replacement of radiator from the 62.5KVA DG Set including connected hose pipe etc and cleaning thoroughly all the tubes and fins etc and carrying out copper brazzing to stop the leakage of the cooling tubes complete all as specified and directed.
S&F in replacement of radiator from the 200/250KVA DG Set including connected hose pipe etc and cleaning thoroughly all the tubes and fins etc and carrying out copper brazzing to stop the leakage of the cooling tubes complete all as specified and directed.
S&F in replacement of radiator from the 320KVA to 625KVA DG Set including connected hose pipe etc and cleaning thoroughly all the tubes and fins etc and carrying out copper brazzing to stop the leakage of the cooling tubes complete all as specified and directed.
S&F in replacement of self starter 12 Volts complete all as directed. Make : Audolek or Equivalent
S&F in replacement of self starter 24 Volts complete all as directed. Make : Audolek or Equivalent approved by GE
S&F in repalacement of Controller suitable for 10 KVA to 63 KVA as per existing make and pattern suitable for DG of any make complete all as directed.
S&F in repalacement of Controller suitable for 125 KVA to 400 KVA as per existing make and pattern suitable for DG of any make complete all as directed.
S&F in repalacement of Controller suitable for 500 to 625 KVA as per existing make and pattern suitable for DG of any make complete all as directed. as specified and directed. Note: For item No. 40 to 42 DG make are Kirloskor, Cumins, M&M & Sudheer with different capacity and model.
S&F in repalacement of Under Voltage Relay 415V AC for control Panel as per existing make and pattern complete all as directed. Make: Teknika or equivalent as approved by GE.
S&F in repalacement of Tripping coil ACB 240 V AC complete all as directed. Make: Siemens or equivalent as approved by GE.
S&F in repalacement of Contactor 4 Pole 400 Amp 440 volt complete all as directed. Make: Schneider or equivalent as approved by GE.
S&F in repalacement of Contactor 4 Pole 250 Amp 440 volt complete all as directed. Make: Schneider or equivalent as approved by GE.
S&F in repalacement of Contactor 4 Pole 95 Amp 440 volt complete all as directed. Make: Schneider or equivalent as approved by GE.
S&F in repalacement of ACB Closing coil 200 V to 250 V complete all as directed. Make: Schneider or equivalent as approved by GE.
S&F in repalacement of under voltage release type mv coil 220 V and 415 V complete all as specified and directed. Make: L&T or equivalent as approved by GE.
S&F in repalacement of Brass oil pressure sensor complete all as directed. Make: Cummins or equivalent as approved by GE.
S&F in repalacement of Panel mounting Timer on-delay, 5Amp complete all as directed. Make: Mistura or equivalent as approved by GE.
S&F in replacement of V-Belt off sizes, Make - Fenner, complete all as per site requirement complete all as specified and directed.
M&L for dismantling of Exhaust pipe of silencer, cleaning of silencer to remove carbon deposit inside exhaust pipe and refixing including replacement of worn out rubber gasket packing and nut, bolts complete all as specified and directed.
Dismantling of defective alternator/dynamo from engine, supplying and fixing new alternator 24 Volt DC Make- TVS Lucas, including replacement of worn out nuts bolts mounting clamp etc. complete all as specified and directed.
S&F in replacement of Oil pressure gauge ISI mark complete all as specified and directed.
S&F in replacement of oil temperature gauge ISI mark complete all as specified and directed.
S&F in replacement of Fuel gauge meter ISI mark operated on 24V DC complete all as specified and directed.
S&F in replacement of high temperature diesel Hose pipe of 1000 PSI of size 12.5mm dia for connecting from diesel tank outlet to Engine complete with banjo bolt & washer complete all as specified and directed.
S&F in replacement of high temperature diesel Hose pipe of 1250 PSI of size 10.3mm dia for connecting from engine to diesel tank complete with banjo bolt & washer complete all as specified and directed.
M & L for Door joint and handle locks arrangement for any size/capacity DG set complete all as specified and directed.
Supply of new battery charger unit for DG Set of capacity upto 500 KVA suitable for 12 V 180 AH with 2m copper leads -02 Nos & brass clamps complete all as specified and directed.
M&L cleaning of diesel tank of DG set of any capacity including replacement of worn out pipe line and measuring scale and fixing in original position and make it leak proof with necessary clamps complete all as specified and directed.
M&L for repair and maintenance of FIP for DG set of 40 KVA to 62.5 KVA including replacement of plunzers , Governer kit with pin Nozzles P type , Head ball guide kit, Head sheet (Set of 12 piece) Rock rod , Roller bearing oil seal, piston and rings , Piston pin joint kit and sleeves complete as specified and directed.
M&L for repair and maintenance of FIP for DG set of 82.5 KVA to 200 KVA including replacement of plunzers , Governer kit with pin Nozzles P type , Head ball guide kit, Head sheet (Set of 12 piece) Rock rod , Roller bearing oil seal, piston and rings , Piston pin joint kit and sleeves complete as specified and directed.
M&L for repair and maintenance of FIP for DG set of 250 KVA to 625 KVA including replacement of plunzers , Governer kit with pin Nozzles P type , Head ball guide kit, Head sheet (Set of 12 piece) Rock rod , Roller bearing oil seal, piston and rings , Piston pin joint kit and sleeves complete as specified and directed.
M&L for dismantling of radiator assembly for 10KVA to 62.5KVA capacity DG Sets from engine, cleaning of the same with suitable cleaning reagent to remove rust & scaling , plugging of any water leakage by brazing and refixing including replacement of rubber hose pipe complete with Jupiter clamps complete all as specified and directed.
M&L for dismantling of radiator assembly for 82.5KVA to 200KVA capacity DG Sets from engine, cleaning of the same with suitable cleaning reagent to remove rust & scaling , plugging of any water leakage by brazing and refixing including replacement of rubber hose pipe complete with Jupiter clamps complete all as specified and directed.
M&L for dismantling of radiator assembly for 250KVA to 625KVA capacity DG Sets from engine, cleaning of the same with suitable cleaning reagent to remove rust & scaling , plugging of any water leakage by brazing and refixing including replacement of rubber hose pipe complete with Jupiter clamps complete all as specified and directed.
M&L for dismantling of Exhaust pipe of silencer, cleaning of silencer to remove carbon deposit inside barrel and refixing including replacement of worn out rubber gasket packing and nut, bolts complete all as specified and directed.
S&F in replacement of Electronic Control Panel & Governor upto 62.5KVA DG set of any make complete all as specified and as directed. Make Cummins or as approved by GE
S&F in replacement of Electronic Control Panel & Governor 100 to 250 KVA DG set of any make complete all as specified and directed. Make:- Cummins or as approved by GE
S&F in replacement of Electronic Control Panel & Governor for 315 to 625 KVA DG set of any make complete all as specified and directed. Note: For item No. 70 to 72 DG make are Kirloskor, Cumins, M&M & Sudheer with different capacity and model.
S&F in replacement of solenoid coil suitable for 12 volt DC complete with all connections complete all as specified and directed.
S&F in replacement of Turbo charger including mounting gas kit complete for 62.5KVA DG set complete all as specified and directed.
S&F in replacement of Turbo charger including mounting gas kit complete for 200KVA to 500KVA DG set complete all as specified and directed.
M&L for Repair/replacement of water pump for 125KVA to 625 KVA DG set complete all as specified and directed.
M&L for Repair/replacement of water pump for 10KVA to 82.5KVA DG set complete all as specified and directed.
Maintenance, repair, servicing of Automatic Mains Failure panel 24Volt DC and 440Volt AC supply operated system by locating faults and replacement of unserviceable parts and components, for DG set 15KVA to 100KVA, complete all as specified and directed, as per following:- (a) Repair of faulty worn out control wiring DC/AC for engine starting and off, with adequate and suitable size copper conductor wire, connected with proper copper lugs & terminals through protection pipe/casing. (b) Repair of worn out/faulty internal wiring of controls and timers, indicating/measuring instruments through various control fuses and relays with suitable and adequate size of copper conductor wire, connected with suitable copper lugs and terminals. (c) Replacement of worn out small control fuses, indicating lamps, various type of copper lugs, thimbles terminals all as deemed necessary or directed including minor spare parts and components in order to make system serviceable and perfectly in working order (d) Material and labour, painting of AMF panel metallic body surface with one coat of superior quality synthetic enamel paint of approved colour and 1st quality including replacement of worn out rubber beading. (e) Testing of system on load. Note : Supply & fix, spare parts for replacement where required, shall be measured and paid separately.
M&L for Earthing complete with GI earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.5 m deep below ground level) with top edge of plate not less than 1.5 m below normal ground level, earth pit surrounded by 15 cm thick and packed layers of charcoal, dust and common salt, including GI strip 32 x 6 as earth lead fixed by means of nuts, bolts, check nuts and washers etc and other end connected to the test point including 40 mm dia light grade GI protection pipe and watering pipe 20 mm dia medium grade with funnel and wire mess including necessary earth work, PCC earth pit chamber in PCC 1:2:4 using 20 mm graded stone aggregate with precast RCC pit cover 80 mm thick etc including dismantling of old earthing, complete all as directed and specified. Note : The earth value/result must be less than 5 ohms.
S&F in repair exhaust pipe of suitable capacity for DG set capacity 110 KVA till out side of the building max 6 Metre along with the asbestos rope and suitable flanges, support for fixing the pipe including connecting accessories all as specified and directed.
Note:- Amount of credit of Rs. 84844.00 for retrieved materials is mentioned in Schedule of Credit of tender documents in pdf form which will be deducted offline while acceptance of tender.
SANJEEV ENTERPRISES (BID ID -3084970)
M/s badrinath Traders (BID ID -3094099)
Jai Maa Electrical Works (BID ID -3086582)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .