EXECUTIVE ENGINEER
IRRIGATION DIVISION NO.4, GADWAL
REFURBISHMENT OF 500 KVA TRANSFORMER FOR NEW DEWATERING PUMP HOUSE ALAMPUR TOWN, JOGULAMBA GADWAL DISTRICT
683590
T.No.07/2025-26, Date:-26.02.2026
OPEN
Electrical Works
JOGULAMBA GADWAL, TELANGANA
5 documents required · 5 mandatory
₹105
₹3,000
31 Mar 2026
28 Feb 2026
2 Mar 2026
Removing the existing transformer from the plinth / Pole and refixing the same transformer of 500 KVA capacity
Loading and Unloadng of transformer of 500KVA from Alampur Transformer yard ( site ) to Workshop or vice verse
Routine maintenance of 500 KVA transformer in operation covering insulation resistance oil, break down strength. Reconditioning / replacement of silicazel, cleaning of transformer and topping upto oil level if required (extra cost will be paid for oil).
Replacing old and unserviceable gasket of top cover plate of transformer having 500 KVA capacity
Replacing old and unserviceable gasket of bushing for the 500KVA Transformer capacity(L.T.)
Replacing LT bushing metal parts for 500 KVA distribution Transformer by new one.
Drying the repaired transformer (500KVA) with appropriate heat / air
Supply of New Transformer oil tested as per IS-335 - 1972
Replacing old and unserviceable gasket of bushing for the 500KVA Transformer capacity H.T.
Replacing HT bushing for 500 KVA distribution Transformer by new one.
Painting with 2 coats Zinchromate red oxide duly scraping existing paint followed by 2 coats of hammerton grey paint etc., (500 KVA)
Replacing HT bushing metal parts for 500 KVA distribution Transformer by new one.
Replacing LT bushing for 500 KVA distribution Transformer by new one.
Filteration of transformer oil as per ISS specifications filters to die electric strength above 40 KV (at workshop)
Coarse aggregate 40-20 mm(excluding Seigniorage charges)
11KV 400 Amps (Conventional) DB AB Switch with Post type insulators
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
500 KVA Transformer.xls
TENDER_DOCUMENT • 0.17 MB
boq.xls
TENDER_DOCUMENT • 0.03 MB
Document.docx
TENDER_DOCUMENT • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .