Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | I₹1.8 LAccepted-Finance | I | Accepted-Finance Accept | |
| 2 | II₹1.8 LRejected-Finance | II | Rejected-Finance Reject | |
| 3 | III₹1.9 LRejected-Finance | III | Rejected-Finance Reject |
Tender Value
Refer Docs
EMD Value
₹2,000
Closing Date
27 Mar 2025, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer
132 KV S/S Bharua Sumerpur
WORK
2025_UPTCL_1019182_1
TS-59/ETD(H)/2024-25
Open Tender
Electrical Works
Lump-sum
30 days
132 KV S/S Bharua Sumerpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
Executive Engineer
₹2,000
Yes
29 Mar 2025
19 Mar 2025
27 Mar 2025
19 Mar 2025
27 Mar 2025
19 Mar 2025
Amount
Details of Work
Oil Topup in conservator tank ( if required) and complete centrifusing of 160 MVA T/F-II (EMCO make) oil in main tank by mainting the outgoing flow of machine oil temperature in range of 55-58 degree celsuius and taking the BDV and PPM after each Two hours and recording in centrifusing register and signed by UPPTCL representative. Before starting the complete centrifusing machine, filter etc. will be checked by SDO/JE with photo of filters. Taking the BDV of oil periodically till the required value upto 75 KV is achieved & PPM upto 5.
To service and detect the Fault in the Internal cicuit of 110V battery Charger set-1 (Make- CHLORIDE) Installed At 220KV substation Mahoba. Under ETD Hamirpur.
Check all Types of terminal And Connections and check all types of SCRs, thyristors present in the circuit and replace any faulty accessories so that the battery charger works properly.
Check the terminals and connection of the contactor of the float circuit installed in the Battery charger set-1 and if the Float Contactor is Faulty then replace it with A new contactor of the same specification to make the circuit healthy so that the Battery charger set works on float Properly.
Check the terminals and connection of the contactor of the Boost circuit installed in the Battery charger set-1 and if the Boost Contactor is Faulty then replace it with A new contactor of the same specification to make the circuit healthy so that the Battery charger set works on Boost Properly.
Check the connections of all types of indicators, rotary switches and alarm fitted in the Battery charger set-1 and if any of themis defective then it should be replaced with a new one. Which Battery charger set should work properly.
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
M/SNITYA INTERPRISES (BID ID -5083769)
S N ENTERPRISES (BID ID -5083898)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .