GM TERMINAL
ATHIPATTU VILLAGE ENNORE
SUPPLY, INSTALLATION, ERECTION, TESTING AND COMMISSIONING OF ELECTRICAL WORKS FOR AMBIENT AIR HEATER PROJECT AT INDIANOIL PETRONAS PVT LTD
2026_IPPL_275083_1
IPPL/ENN/PT-04/2026-27
Open Tender
Electrical Works
Works
150 days
ENNORE CHENNAI
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹4.0 L
ONLINE
17 Jun 2026
17 Apr 2026
4 May 2026
18 Apr 2026
2 May 2026
28 Apr 2026
24 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1POWER DISTRIBUTION PANELS | |||||
| 1.01 | Supply, installation, testing, commissioning of double-front MCC Panel with dual incomer each 415 V,TPN 65 KA for 1sec,all ACB shall be drawout type with incomer rating of 1600A ACB , Outgoing motors feeders with VFD & DOL Starters with operating mechanism, all accessories, auxiliaries etc. complete in all respects with protection,metering,indications, local, remote start stop and provision for PLC connection, lettering painting works as specified in technical specification, data sheet & SLD | 1 | NO | - | - |
| 1.02 | Supply, installation, testing, commissioning of 1 No. of 1600 ACB 415 V,TPN 65 KA for 1sec,ACB without panel enclosure along with CT,meters,fuses, wiring , relays with all accessories, auxiliaries etc. complete in all respects as specified in technical specification. ACB shall be retrofit in the existing 800A ACB feeder with all necessary protection,indication,metering etc. | 2 | NO | - | - |
| 1.03 | Dismantling of existing 800A ACB feeder, along with fuses, wiring , relays,metering etc and modification suitable for 1600A ACB breaker installation as per Item 1.2. | 2 | NO | - | - |
| 1.04 | Supply, installation, testing, commissioning of 1 No of 1000 ACB 415 V,TPN 65 KA for 1sec,ACB without panel enclosure along with CT,meters,fuses, wiring , relays with all accessories, auxiliaries etc. complete in all respects as specified in technical specification. ACB shall be retrofit in the existing 800A ACB feeder with all necessary protection,indication,metering etc. | 1 | NO | - | - |
| 1.05 | Dismantling of existing 800A ACB feeder, along with fuses, wiring , relays,metering etc and modification suitable for 1000A ACB breaker installation as per Item 1.4 | 1 | NO | - | - |
| 2AUTOMATIC POWER FACTOR CORRECTION PANEL (APFC PANEL) | |||||
| 2.01 | Supply, Installation, testing & commissioning of CRCA sheet steel enclosed, floor mounted, free standing indoor APFC Panel 415 V,TPN 65kA for 1.0sec, with detuned filter of 500kVAR with automatic correction of Power Factor with 7% Detuned Reactor. ACBs shall be darwout type with single front type indoor with operating mechanism, all accessories, auxiliaries and all other necessary components for smooth operation including transportation from store/yard to site at the place of installation, unpacking, assembly, including mounting and wiring of loose parts supplied by equipment vendor, including installation on foundations or steel structures, aligning, leveling, grouting, testing and calibration of relays and meters etc., including all labour and materials, etc complete in all respects as specified in technical specification, data sheet & SLD of APFC of this tender, and directions of Engineer-in-Charge
(Location: Substation) | 1 | NO | - | - |
| 3CABLE JUNCTION BOX | |||||
| 3.01 | Supply, Installation, testing & commissioning of 415V, 4P,1600A rated indoor Industrial type Cable junction box with copper busbars with indicators.
Incomer cables shall be 6R, 3.5C x 300 sqmm & Outgoing Cable shall be 6R,3.5C x 300 sqmm, XLPE AL Cables.( Without breakers) | 2 | NO | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.07 MB
HSETCPT04.pdf
Tender Documents • 0.21 MB
VOL1PT04.pdf
Tender Documents • 3.26 MB
BOQ_321294.xls
BOQ • 1.21 MB
VolumeIIPT48.pdf
PDF • 16.07 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .