| Sl No | Description | Qty | Unit | P. K. POWER SOLUTIONS L2 | SIDDHI ENTERPRISES L3 | KRISHNA ENGINEERS L1 |
|---|---|---|---|---|---|---|
| 1.00 | Testing of 5/8/10 MVA Power Transformer installed at various 33/11 KV Sub-Staion under EUDD-Kanpur Road, including following test- a. Insulation. b. Open circuit Test & Short circuit test. c. Magnetization current Test. d. Magnetic balance Test. e. Buchholz, (OTI/WTI) Circuit Test. f. Neutral to earth & Body to earth resistance. g. Relay Testing by Secondary Injection IDMT & DMT curve verification with TMS & delay time. The test should be carried out by bringing kit and all requires instrument on site by the contractor, making all necessary connection for above tests and insuring healthiness of transformer, complete testing shall be done once half yearly or as and when requires in emergency. | 26 | Job | 10,200 ₹2.7 L | 12,000 ₹3.1 L | 9,900 ₹2.6 L |
| 2.00 | Testing of 33 KV Feeder panel breakers including testing of CTR both the primary injection. Testing of relay by secondary injection IDMT & DMT curve verification with TMS and delay time. Works includes cleaning and adjustment of relay contracts & springs checking of closing and tripping of breakers on remote/manual and protection trip command through CT (By means of primary injection) Testing of 11 KV incoming/ outgoing panels including testing of CTR by primary injection, testing of relay works includes cleaning of relay contacts and adjustment of springs. Checking operations and tripping of VCB on remote/manual and protection trip. | 26 | Job | 3,500 ₹91,000 | 3,600 ₹93,600 | 3,300 ₹85,800 |
| 3.00 | Testing of 11 KV incoming/outgoing breaker/pannels including testing of CT ratio by primary injection set along with Fuse Checking at every Feeder and meter Checking. Testing of relays and its setting as per requirement. The work includes cleaning of relay. Checking and operation of VCB by remote/local and manual/ protection command generated through primary injection set with operation of relays For tightening of all contacts testing of relay & control, wiring, equipment All T&P's as required for above work should be provided by the contractor. | 126 | Job | 3,100 ₹3.9 L | 3,300 ₹4.2 L | 2,950 ₹3.7 L |
| 4.00GST Extra as per Rules | ||||||
Tender Value
₹7.4 L
EMD Value
₹7,370
Closing Date
18 Aug 2025, 5:00 pmClosed
SE-EUDC-VRINDAVAN, LUCKNOW.
33/11 KV SECTOR-5D, VRINDAVAN COLONY, LUCKNOW.
Testing of 33/11 KV breakers and power transformers and other related works under the area of EUDD-Kanpur Road, Amausi Zone, Lucknow against O and M head 2025-26 of EUTD-Vrindavan, Amausi Zone, Lucknow.
2025_MVVNL_1063080_1
15/EUDC-VRINDAVAN/LESA/2025-26
Open Tender
Electrical Works
365 days
KANPUR ROAD
AS PER TENDER DOCUMENTS
2 documents required · 2 mandatory
₹1,180
A/C NO. 1277784945 IFSC CBIN0280140
₹7,370
8 Oct 2025
5 Aug 2025
19 Aug 2025
5 Aug 2025
18 Aug 2025
5 Aug 2025
Amount
Testing of 5/8/10 MVA Power Transformer installed at various 33/11 KV Sub-Staion under EUDD-Kanpur Road, including following test- a. Insulation. b. Open circuit Test & Short circuit test. c. Magnetization current Test. d. Magnetic balance Test. e. Buchholz, (OTI/WTI) Circuit Test. f. Neutral to earth & Body to earth resistance. g. Relay Testing by Secondary Injection IDMT & DMT curve verification with TMS & delay time. The test should be carried out by bringing kit and all requires instrument on site by the contractor, making all necessary connection for above tests and insuring healthiness of transformer, complete testing shall be done once half yearly or as and when requires in emergency.
Testing of 33 KV Feeder panel breakers including testing of CTR both the primary injection. Testing of relay by secondary injection IDMT & DMT curve verification with TMS and delay time. Works includes cleaning and adjustment of relay contracts & springs checking of closing and tripping of breakers on remote/manual and protection trip command through CT (By means of primary injection) Testing of 11 KV incoming/ outgoing panels including testing of CTR by primary injection, testing of relay works includes cleaning of relay contacts and adjustment of springs. Checking operations and tripping of VCB on remote/manual and protection trip.
Testing of 11 KV incoming/outgoing breaker/pannels including testing of CT ratio by primary injection set along with Fuse Checking at every Feeder and meter Checking. Testing of relays and its setting as per requirement. The work includes cleaning of relay. Checking and operation of VCB by remote/local and manual/ protection command generated through primary injection set with operation of relays For tightening of all contacts testing of relay & control, wiring, equipment All T&P's as required for above work should be provided by the contractor.
GST Extra as per Rules
P. K. POWER SOLUTIONS (BID ID -5449670)
SIDDHI ENTERPRISES (BID ID -5450129)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid