Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹46.8 LAccepted-AOC 4 94D RAJA COTTAGE 1ST FLOOR KANYAKULAM PARVATHIPURAM NAGERCOIL KANNIYAKUMARI TAMILNADU 629 003 | KANNIYAKUMARI | TAMIL NADU | 629003 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹51.6 L+₹3.6 L (7.54%)Rejected-Finance 66 C O J R NAICKER ASWATHNAGAR SANJAYNAGAR P O BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L2 | Rejected-Finance Rejected. Quoted rates are higher than L1 | |
| 3 | L3₹52.3 L+₹4.3 L (9.03%)Rejected-Finance | L3 | Rejected-Finance Rejected. Quoted rates are higher than L1 | |
| 4 | L4₹54.5 L+₹6.5 L (13.5%)Rejected-Finance | L4 | Rejected-Finance Rejected. Quoted rates are higher than L1 | |
| 5 | L6₹56.2 L+₹8.2 L (17.0%)Rejected-Finance NO 83 THAMMAIAH GARDEN ABBIGERE CHIKKABANAVARA PO BANGALORE 560 090 | BENGALURU URBAN | KARNATAKA | 560090 | L6 | Rejected-Finance Rejected. Quoted rates are higher than L1 |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
26 Nov 2024, 6:00 pmClosed
Garrison Engineer M AF Jalahalli
Garrison Engineer M AF Jalahalli Bangalore 560013
REPAIR MAINT OF WATER SUPPLY DISTRIBUTION SYSTEM GATE VALVE LEAKAGE REPAIR PUMP MOTOR CHLORINATION PLANT AND OTHER MISC WORKS AT AFTC 2 DC AREA AND CQAE WE UNDER GE M AF JALAHALLI
2024_MES_681699_1
8911/E8
Open Tender
Electrical and Maintenance Works
Item Rate
181 days
Garrison Engineer M AF Jalahalli
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Garrison Engineer M AF Jalahalli
₹1 L
10 Dec 2024
29 Oct 2024
28 Nov 2024
29 Oct 2024
26 Nov 2024
12 Nov 2024
29 Oct 2024 - 5 Nov 2024
Amount
Demolition of Brickwork or precast concrete block walling including wall quoins, arches, pillars, etc, but excluding ashlar facings, dressed stone work and concrete articles built in cement mortar complete all as specified or directed.
M&L for Pre-cast cement concrete PCC (1:3:6) type C-1 using 20mm graded crushed stone aggregate for block masonry with solid blocks, exc. 10 cm in width and setting in cement mortor 1 : 4, complete, in walls all as specified and directed by Engr-in-Charge.
Taking down and relaying of existing DI water pipe lines of size 200 mm bore but of any type includings all fittings after removal of scalling, cleaning and flushing etc complete all as specified and directed. Note: Excavation & earthwork shall be measured & paid seperately
Taking down and relaying of existing DI water pipe lines of size 150 mm bore but of any type includings all fittings after removal of scalling, cleaning and flushing etc complete all as specified and directed. Note: Excavation & earthwork shall be measured & paid seperately.
Taking down and relaying of existing DI water pipe lines of size 100/80 mm bore but of any type includings all fittings after removal of scalling, cleaning and flushing etc complete all as specified and directed. Note: Excavation & earthwork shall be measured & paid seperately.
M&L as in replacement for Ductile Iron Pipe (DI Pipes), (K-7) ISI marked, 200 mm dia laid in trenches including jointing material such as EPDM Rubber Gasket and suitable type of grase etc complete all as specified and directed. Note :- DI fitting/special will be measured and paid separately. Note: Excavation & earthwork shall be measured & paid seperately
Supply and fixing in replacement Sluice valve of size 200 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed.
Material and Labour for dismantling the brass splindle from 200 mm dia bore sluice valves in various locations and reconditioning the sluice valve by replacing SS/bronze spindle, spindle nuts with brass ring, gland nuts complete all as specified and as directed.
Material and Labour for gland packing in leaking Sluice Valves of 200 mm dia size Complete including replacing/tightening the existing bolts and nuts etc. complete all as directed .
Material & Labour as in repair for Construction of Valve pit having inner dimensions 1000mm x 1000 mm x 1000 mm with foundation PCC 1:4:8 type D2 using 40mm graded stone aggregate, brick work with sub class B old size build in Cement mortar 1:6, PCC 1:2:4 type B1 using 20mm stone aggregate for Coping, 15 mm thick rendering plaster in CM 1:4 inluding MS cover with locking arrangement all as specified and as directed. Note :- Chamber Covers will be measured and paid separately under relevant item of this schedule.
Supply and fixing in replacement Non return valve (NRV) of size 200 mm ISI marked, gum metal body suitable for 200 mm dia pipe line complete all specified and directed
S&F in replacement foot valve cast iron of size 200 mm bore including rubber insertion, packing material, nuts, bolts, and washer with suitable new one all as specified and directed.
Supply and fix replacement of U/S leather packing suitable for foot valve 150 to 200 mm dia, suction pipe flanged connected to pumpsets including replacement of nuts and bolts etc all as specified and directed
M&L as in replacement for Ductile Iron Pipe (DI Pipes), (K-7) ISI marked, 150 mm dia laid in trenches including jointing material such as EPDM Rubber Gasket and suitable type of grase etc complete all as specified and directed. Note :- DI fitting/special will be measured and paid separately. Note: Excavation & earthwork shall be measured & paid seperately
Material and Labour for dismantling the brass splindle from 150 mm dia bore sluice valves in various locations and reconditioning the sluice valve by replacing SS/bronze spindle, spindle nuts with brass ring, gland nuts complete all as specified and as directed.
Supply and fixing in replacement Sluice valve of size 150 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed
Material and Labour for gland packing in leaking Sluice Valves of 150 mm dia size Complete including replacing/tightening the existing bolts and nuts etc. complete all as directed .
Supply and fixing in replacement Non return valve (NRV) of size 150 mm ISI marked, gum metal body suitable for 150 mm dia pipe line complete all specified and directed
S&F in replacement foot valve cast iron of size 150 mm bore including rubber insertion, packing material, nuts, bolts, and washer with suitable new one all as specified and directed.
Clearing the bushes trunk girth not exceeding 10 .00 cm and area around valve chambers upto 1.0 mtrs and depositing at a distance nexceeding 50 mtrs from starting point etc complete all as specified and directed
M&L as in replacement for Ductile Iron Pipe (DI Pipes), (K-7) ISI marked, 100 mm dia laid in trenches including jointing material such as EPDM Rubber Gasket and suitable type of grase etc complete all as specified and directed. Note :- DI fitting/special will be measured and paid separately. Note: Excavation & earthwork shall be measured & paid seperately
Supply and fixing in replacement Sluice valve of size 100 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed
Material and Labour for dismantling the brass splindle from 100 mm dia bore sluice valves in various locations and reconditioning the sluice valve by replacing SS/bronze spindle, spindle nuts with brass ring, gland nuts complete all as specified and as directed.
Material and Labour for gland packing in leaking Sluice Valves of 100 mm dia size Complete including replacing/tightening the existing bolts and nuts etc. complete all as directed .
Supply and fixing in replacement Non return valve (NRV) of size 100 mm ISI marked, gum metal body suitable for 100 mm dia pipe line complete all specified and directed
Material & Labour as in repair for Construction of Valve pit having inner dimensions 900 mm x 900 mm x 900 mm with foundation PCC 1:4:8 type D2 using 40mm graded stone aggregate, brick work with sub class B old size build in Cement mortar 1:6, PCC 1:2:4 type B1 using 20mm stone aggregate for Coping, 15 mm thick rendering plaster in CM 1:4 inluding MS cover with locking arrangement all as specified and as directed. Note :- Chamber Covers will be measured and paid separately under relevant item of this schedule.
S&F in replacement foot valve cast iron of size 100 mm bore including rubber insertion, packing material, nuts, bolts, and washer with suitable new one all as specified and directed.
M&L as in replacement for Ductile Iron Pipe (DI Pipes), (K-7) ISI marked, 80 mm dia laid in trenches including jointing material such as EPDM Rubber Gasket and suitable type of grase etc complete all as specified and directed. Note :- DI fitting/special will be measured and paid separately. Note: Excavation & earthwork shall be measured & paid seperately
Supply and fixing in replacement Sluice valve of size 80mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed.
Material and Labour for dismantling the brass splindle from 80 mm dia bore sluice valves in various locations and reconditioning the sluice valve by replacing SS/bronze, spindle nuts with brass ring, gland nuts complete all as specified and as directed.
Material and Labour for gland packing in leaking Sluice Valves of 80 mm dia size Complete including replacing/tightening the existing bolts and nuts etc. complete all as directed .
Supply and fixing in replacement Non return valve (NRV) of size 80 mm ISI marked, gum metal body suitable for 80 mm dia pipe line complete all specified and directed
Material & Labour as in repair for Construction of Valve pit having inner dimensions 600 mm x 600 mm x 600 mm with foundation PCC 1:4:8 type D2 using 40mm graded stone aggregate, brick work with sub class B old size build in Cement mortar 1:6, PCC 1:2:4 type B1 using 20mm stone aggregate for Coping, 15 mm thick rendering plaster in CM 1:4 inluding MS cover with locking arrangement all as specified and as directed. Note :- Chamber Covers will be measured and paid separately under relevant item of this schedule.
Supply and fixing in replacement Non return valve (NRV) of size 65 mm ISI marked, gum metal body suitable for 65 mm dia pipe line complete all specified and directed
S&F in replacement foot valve cast iron of size 80 mm bore including rubber insertion, packing material, nuts, bolts, and washer with suitable new one all as specified and directed.
Supply and fix replacement of leather packing suitable for foot valve 80 to 100 mm dia, suction pipe flanged connected to pumpsets including replacement of nuts and bolts etc all as specified and directed
M & L for DI specials and fittings as per IS for spigot and socketed pipes or flanged pipe for water mains branches lines such as bends (any type radius and angle ) tapers any type (straight, bend,increasing,decresing,or double socket etc) tee preces,single branch,Y juntion, double branch, cross, including connecting pieces one end flanged and other socket or spigot and bell mouth pices suitable for rubber joint,tyton joint up to 150 mm bore and conforming to IS-9523: 2000 complete all as specified and directed
S & F as in replacement ON load change over switch 4 pole 250 Amps in sheet metal enclosure complete all as specified and as directed by Engineer-in-Charge. make :- Havells /L&T/Indo Asian
M&L Taking down defective centrifugal pump set 100 HP capacity by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at same location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :- (a) The spares shall be measured and paid seperately in the relevent items given below. (b) Cost of labour for replacement of spares and transportation are deemed to be included in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case services affected due to delay in repair of pump set, a penalty of Rs 1000 per day will be levied from the contractor. (e) Please note that this penalty is exclusively other than the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract. (f) The decision of the Accepting Officer in this regard shall be final and binding.
Supply only coupling Rubber Bush suitable for 100 HP capacity motor pump as per manufacturer's design complete all as specified and as directed.
Supply only shaft sleeves suitable for 100 HP capacity motor pump as per manufacturer's design complete all as specified and as directed.
Supply only water seal suitable for 100 HP capacity motor pump as per manufacturer's design complete all as specified and as directed.
Supply only Ball bearing suitable for 100 HP capacity motor pump as per manufacturer's design complete all as specified and as directed. Make : Tata/SKF/NBC
Supply only split casing gaskets suitable for 100 HP capacity motor pump as per manufacturer's design complete all as specified and as directed.
Supply only Air cock grease nipple suitable for 100 HP capacity motor pump as per manufacturer's design complete all as specified and as directed.
Supply only coupling bolt with nuts suitable for 100 HP capacity motor pump as per manufacturer's design complete all as specified and as directed.
Supply only bronze impeller suitable for 100 HP capacity motor pump as per manufacturer's design complete all as specified and as directed.
Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 100 HP capacity motor pump as per manufacturer's design complete all as specified and as directed.
M&L for rewinding of squirrel cage induction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load all as directed and specified for the 100HP motor capacity.
M&L for suitable size of gland packing for 100 HP pump set as per manufacturer's design complete all as specified and as directed.
Supply & fix in replacement of 3 Pole power contactor AC 415 V 160 Amps , AC3 ( inductive load ) type with Aux contact 2 NO + 2 NC 50 Hz Model No. as per existing frame suitable for 100 HP Pump sets complete all as specified and as directed. Make : L & T / Indo Asian /Schneider
M & L for servicing of starter by checking and servicing the contactor coil , over load relay coil and any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drilling testing the panel complete all as specified and directed for the 100 HP capacity pump sets Notes :- (i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be include in quoted rate.
Supply & fix in replacement adjustable CT/Direct operated thermal over load relay 105 to 156 A for 100 HP motor 3 phase 415v , 3 pole , with single phase protection including CTs complete all as specified and as directed. Make : L & T / Indo Asian /Schneider
Supply and fix as in repair 4 Pole MCCB ,415 volts,fixed type ,400 Amp, 50 Hz, with rupturing capacity 36 KA in the existing pump starter panel including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. Make: Indo Asian/L&T/ Legrand
M&L Taking down defective centrifugal pump set 40 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. (Supply of spare parts shall be measured and paid for separately under respective items here-in-after). Note :- (a) The spares shall be measured and paid seperately in the relevent items given below. (b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case of services affected due to delay in repair of pump set, a penalty of Rs 1000 per day will be levied from the contractor. (e) Please note that this penalty is exclusively other than the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract. (f) The decision of the Accepting Officer in this regard shall be final and binding.
Supply only coupling Rubber Bush suitable for 40 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only water seal suitable for 40HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only Ball bearing suitable for 40 HP motor pump as per manufacturer's design complete all as specified and as directed. Make : Tata/SKF/NBC
Supply only coupling bolt with nuts suitable for 40 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only shaft sleeves suitable for 40 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only split casing gaskets suitable for 40 HP motor pump as per manufacturer's design complete all as specified and as directed.
Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 40HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only Air cock grease nipple suitable for 40 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only bronze impeller suitable for 40HP motor pump as per manufacturer's design complete all as specified and as directed.
M&L for rewinding of squirrel cage induction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load all as directed and specified for the 40 HP motor capacity.
M&L for suitable size of gland packing for 40 HP pump set as per manufacturer's design complete all as specified and as directed.
M & L for servicing of starter by checking and servicing the contactor coil , over load relay coil and any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drilling testing the panel complete all as specified and directed for the 40 HP capacity pump sets complete all as directed. Notes :- (i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate.
Supply & fix in replacement adjustable CT/Direct operated thermal over load relay suitable for 40 HP motor 3 phase 415v , 3 pole , with single phase protection including CTs complete all as specified and as directed. Make : L & T / Indo Asian /Schneider
Supply and fix as in repair 4 Pole MCCB ,415 volts,fixed type ,160 Amp, 50 Hz, with rupturing capacity 25 KA in the existing pump starter panel including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. Make: Indo Asian/L&T/ Legrand
Taking down defective centrifugal pump set 20 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :- (a) The spares shall be measured and paid seperately in the relevent items given below. (b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contractor. (e) Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract. (f) The decision of the Accepting Officer in this regard shall be final and binding.
Supply only Ball bearing suitable for 20 HP motor pump as per manufacturer's design complete all as specified and as directed. Make : Tata/SKF/NBC
Supply only split casing gaskets suitable for 20 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only coupling bolt with nuts suitable for 20 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only Air cock grease nipple suitable for 20 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only coupling Rubber Bush suitable for 20 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only shaft sleeves suitable for 20 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only water seal suitable for 20 HP motor pump as per manufacturer's design complete all as specified and as directed.
Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 20 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only bronze impeller suitable for 20 HP motor pump as per manufacturer's design complete all as specified and as directed.
M&L for rewinding of induction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load all as directed and specified for the 20 HP motor capacity.
M&L for suitable size of gland packing for 20 HP pump set as per manufacturer's design complete all as specified and as directed.
Supply & fix in replacement of 3 Pole power contactor AC 415 V AC3 ( inductive load ) type 40 Amps with add on Aux contact 2 NO + 2 NC 50 Hz Model No as per existing frame suitable for 20 HP Pump set complete all as specified and as directed. Make : L & T / Indo Asian /Schneider
M & L for servicing of starter by checking and servicing the contactor coil , over load relay coil and any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drilling testing the panel complete all as specified and directed by Engineer in charge for the 20 HP capacity pump sets complete all as directed. Notes :- (i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate.
Supply & fix in replacement adjustable CT/Direct operated thermal over load relay 30 to 43 A for 20HP motor 3 phase 415v , 3 pole , with single phase protection including CTs complete all as specified and as directed. Make : L & T / Indo Asian /Schneider
Supply and fix as in repair 4 Pole MCCB ,415 volts,fixed type ,125 Amp, 50 Hz, with rupturing capacity 25 KA in the existing pump starter panel including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. Make: Indo Asian/L&T/ Legrand
Taking down defective centrifugal/Monoblock pump set 10 HP to 15 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :- (a) The spares shall be measured and paid seperately in the relevent items given below. (b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contractor. (e) Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract. (f) The decision of the Accepting Officer in this regard shall be final and binding.
Supply only split casing gaskets suitable for 10 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only Ball bearing suitable for 10 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed. Make : Tata/SKF/NBC
Supply only coupling bolt with nuts suitable for 10 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only Air cock grease nipple suitable for 10 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only coupling Rubber Bush suitable for 10 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only shaft sleeves suitable for 10 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only water seal suitable for 10 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only bronze impeller suitable for 10 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed.
Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 10 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed.
M&L for rewinding of induction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load all as directed and specified for the 10 HP to 15 HP motor capacity.
M&L for suitable size of gland packing for 10 HP to 15 HP pump set as per manufacturer's design complete all as specified and as directed.
Supply & fix in replacement of 3 Pole power contractor AC 415 V AC3 ( inductive load ) type 25 Amps with add on Aux contact 2 NO + 2 NC 50 Hz Model No as per existing frame suitable for 15/10 HP Pump sets complete all as specified and as directed. Make : L & T / Indo Asian /Schneider
M & L for servicing of starter by checking and servicing the contactor coil , over load relay coil and any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drilling testing the panel complete all as specified and directed for the 10 HP to 15 HP capacity pump sets complete all as directed. Notes :- (i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate.
Supply & fix in replacement adjustable CT/Direct operated thermal over load relay 15 to 21 A for 10/15 HP motor 3 phase 415v , 3 pole , with single phase protection including CTs complete all as specified and as directed. Make : L & T / Indo Asian /Schneider
Supply and Fixing as in replacement MCCB, 4 poles 415 Volts, 100 Amps, 16 KA, 50 Hz, AC, adjustable thermal and magnetic type in the existing pump starter panel including connecting up incoming/out going cable with suitable lugs and testing complete all as specified and as directed. Make : Legrand/Indo Asian/L&T
Taking down defective centrifugal /Monoblock pump set 5 HP to 7.5 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :- (a) The spares shall be measured and paid seperately in the relevent items given below. (b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contractor. (e) Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract. (f) The decision of the Accepting Officer in this regard shall be final and binding.
Supply only coupling bolt with nuts suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only split casing gaskets suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only Ball bearing suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed. Make : Tata/SKF/NBC
Supply only Air cock grease nipple suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only coupling Rubber Bush suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only shaft sleeves suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only water seal suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only bronze impeller suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
M&L for rewinding of electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load all as directed and specified for the 5 HP to 7.5 HP motor capacity.
M&L for suitable size of gland packing for 5 HP to 7.5 HP pump set as per manufacturer's design complete all as specified and as directed.
M & L for servicing of starter by checking and servicing the contactor coil , over load relay coil and any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drilling testing the panel complete all as specified and directed for the 5 HP to 7.5 HP capacity pump sets complete all as directed. Notes :- (i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate.
Supply and fix as in repair TPN MCB ,415 volts,fixed type ,63 Amp, 50 Hz, with rupturing capacity 10 KA in the existing pump starter panel including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. Make: Indo Asian/L&T/ Legrand
Taking down defective centrifugal /Monoblock pump set upto 4 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :- (a) The spares shall be measured and paid seperately in the relevent items given below. (b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contractor. (e) Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract. (f) The decision of the Accepting Officer in this regard shall be final and binding.
Supply only Ball bearing suitable for upto 4 HP motor pump as per manufacturer's design complete all as specified and as directed. Make : Tata/SKF/NBC
Supply only split casing gaskets suitable for upto 4 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only coupling bolt with nuts suitable for upto 4 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only Air cock grease nipple suitable for upto 4 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only coupling Rubber Bush suitable for upto 4 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only shaft sleeves suitable for upto 4 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only water seal suitable for upto 4 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only bronze impeller suitable for upto 4 HP motor pump as per manufacturer's design complete all as specified and as directed.
Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for upto 4 HP motor pump as per manufacturer's design complete all as specified and as directed.
M&L for rewinding of electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation /base, cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation/ base of sunction sweeper by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load all as directed and specified for the up to 4 HP motor capacity.
M & L for servicing of starter by checking and servicing the contactor coil , over load relay coil and any other parts and replacement the burnt out wiring including any modification to pump starter panel by welding,cutting , grinding ,drilling testing the panel complete all as specified and directed for the upto 5 HP capacity pump sets complete all as directed. Notes :- (i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be included in quoted rate.
S & F in repair Over load Relay (as per sample) for up to 5 HP starter (Dol/Star delta) complete all as directed .
Supply & fix in replacement Single phase preventer for motor in the existing panel board with new one at water supply installations complete all as specified and as directed.
Supply and fix as in repair TPN MCB ,415 volts,fixed type ,40 Amp, 50 Hz, with rupturing capacity 10 KA in the existing pump starter panel including connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed. Make: Indo Asian/L&T/ Legrand
Supply & fix in replacement Star Delta timer 0-30/60 sec complete all as specified and as directed.
Supply , fabricating ,installation,commissioning and testing of LT Motor Panel box double door weather proof ,dust vermine proof (CPRI approved) LT Motor Panel made out of 3.15 mm thick CRCA sheet front and back door openable type and suitable for operation on 415 Volts ,50 Hz ,AC supply confirming to IP-54 and fixed on angle iron frame /channel of suitable size complete ,aluminium bus bar ,cable gland brass chromium plated of different size suitable for incoming and out going cable. Panel Painted with powder coated paint including necessary PCC (1:3:6) type C-1 using 20mm graded crushed stone aggregate for foundation of suitable size infront of the panel including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed and comprising of the following:-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 600 Amp, 36 KA - 01 No (Incomer). (b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 400 Amp, 36 KA - 01 No. (c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 250 Amp, 25 KA - 03 Nos. (d) MCCB with thermal magnetic release 3 Pole, 415 V of capacity 200 Amp, 50 KA - 02 Nos. (e) Soft Stater of capacity of 100 HP pump including suitable adjustable OLR relay , along with single phase preventer and connected accessories - 02 Nos (f) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. (g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. Note :- (i) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (ii) Make of Switch gear : Indoasian/L&T/ Legrand (iii) The contractor shall submit the drawing for approval of GE before executing the work.
Cleaning of service tanks of the capacity as mentioned below on roof top of bldgs upto three storey after disconnection from inlet and outlet pipe, removing of float valve of service tank and keep aside safely for reuse drain out water through drain plug, cleaning thoroughly to remove all scales and dirt by brushing internal surface, cleaning properly inside with soda wash, flushing out with fresh water, re-positioning of tank at same place, re-connecting inlet and outlet pipes, closing of drain plug, re-installation of float valve duly cleaned, writing/ labelling the record of cleaning carried out with white bold letter such as "TANK CLEANED ON"--------- (month and year), including removing creepers, vegitation and roots of plants, trees branches on or surrounding of service tank complete all as directed. Note:-(i) Unit rate quoted is deemed to be included for testing of water supply in tank both inlet and outlet flow during next supply hours early in the morning or late in evening. (ii) Contractor shall maintain a pucca bound register for cleaning carried out with date and obtain users signature and remarks if any and this register to be submitted alongwith RAR. (iii) Contractor is liable to rectify any damages to the external finishes of the bldg occured during the cleaning process, i.e. scrubbing and touch up with external paints as existing specifications. Unit rate quoted is deemed to be included the cost of the same. (iv) All sort of petty T&P items such as ladder, safety equipment, nuts, bolts, washers etc. required to accomplish the job shall be provided by the contractor with out any extra cost to dept.
(a) For RCC /PVC tank exceeding 200 litters and not exceeding 500 ltrs
(b) For RCC /PVC tank exceeding 501 litters and not exceeding 1000 ltrs
(c) For RCC /PVC tank exceeding 1001 litters and not exceeding 2000 ltrs
Supply and fix Nipple suitable for HDPE water tank.(Minimum weight 20 mm- 45gm) complete all as specified and as directed.
Supply and fix Nipple suitable for HDPE water tank (Minimum weight 25mm- 65g complete all as specified and as directed.
Supply and fixing in repair 25 mm dia Unplasticised PVC (UPVC) Pipes of pressure 10kgf/cm2 including fittings like socket / union / Tee / Reducer / Nipple etc complete fixed to wall/ceilings/ in floors etc, complete all as specified and directed.
Supply and fixing in repair 20 mm dia Unplasticised PVC (UPVC) Pipes of pressure rating 10kgf/cm2 including fittings like socket / union / Tee / Reducer / Nipple etc complete fixed to wall/ceilings/ in floors etc, complete all as specified and directed.
Supply and fixing in repair UPVC Gate Valve of size 25 mm dia , ISI marked complete all as specified and as directed.
Supply and fixing in repair UPVC Gate Valve of size 20 mm dia, ISI marked complete all as specified and as directed.
Supply and fix of PVC water tank 500 ltrs capacity Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) (Three layer) hoisted and fixed in position all as specified in SSR Part-I ,complete all as directed incl disconnecting existing tank of any description and any capacity .
Supply and fix in repairs lids suitable for up to 1000Ltrs cap of tanks for polyethylene water storage tanks, threaded or hinged type as per existing incl PTMT nuts/binding wire complete all as specified and directed.
Supply and fix in replacement PVC Ball valve ISI marked high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe and fixed of size 25 mm complete all as specified and directed
M&L for dewatering & Cleaning of RCC Over Head Tanks of the following capacities by involving of the followings 09 (NINE) stage of cleaning process complete all as specified and directed (i) De-watering by high pressure submersible pump complete (ii) Removal of sludge from RCC Over Head Tanks (iii) Cleaning of walls, floors, ceiling etc by high pressure jet pump 80-180 bar pressure l complete (iv) Removing dirt and sludge by vacuum pump (v) Anti- Bacterial Treatment to inside of tank which effective against all pathogens all complete. (vi) Sterilization of the tank atomosphere by UV radiation inside of the tank. (vii) Applying one coat of white wash to internal surfaces. (viii) Replace nylon net for vent pipes & man hole covers (ix) Writing letter in bold with white paint on black colour back ground such as sump number, capacity, cleaned on Date & Due on Date etc
Note for item No 147 :- The Bidder shall take into consideration for following points while quoting his rate for this item and the unit rate is deemed to be included for :- (i) The contractor shall provide dewatering pump of suitable capacity and mobile generator for operation of dewatering by high pressure submersible pump (or) Diesel driven high pressure pump and the rate quoted is inclusive of rent/hiring charge complete. (ii) Cutting and filling shall be cleared of shrubs, vegetation, grass bush, weed, trees and sapling not exceeding 30 cm in girth, measured at a height of two metre above ground level. Useful material shall be stacked. (iii) Material removed from the tank shall be disposed off at out side MD land. (iv) Tank shall be made available for cleaning for a period of 8 hours only and contractor has to arrange sufficient labour/ T&P to complete the job within the given period only. or otherwise penalty shall be imposed @ Rs 500/- per day. (v) All safety with gadgets like safety Belts, special safety ladder, Helmets, Heavy Duty Gum Boots, Gloves, Safety Goggles, Masks, Aprons, etc. for complete security the safe operations. Storage and Cleaning equipment’s like Scrubbers/Wipers, Storage drums, Sludge Collectors and Cisterns, etc. must be integral part of system.
(a) water tank of capacity 228000 Ltr of approx 32 Mtr Height
Supply and fixing in repair 20 mm dia Chlorinated PVC (CPVC) Pipes of pressure rating 10kgf/cm2 including fittings like socket / union / Tee / Reducer / Nipple etc complete fixed to wall/ceilings/ in floors etc, complete all as specified and directed.
Supply and fixing in repair Chlorinated PVC (CPVC) Gate Valve of size 20 mm dia, ISI marked complete all as specified and as directed.
Supply and fix of PVC water tank 1000 ltrs capacity Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part-I ,complete all as directed incl disconnecting existing tank of any description and any capacity.
Supply and fix in repairs lids suitable for 1001 to 2000 Ltrs cap of tanks for polyethylene water storage tanks, threaded or hinged type as per existing incl PTMT nuts/binding wire complete all as specified and directed.
Supply and fix in replacement PVC Ball valve ISI marked high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe and fixed of size 20 mm complete all as specified and directed
M&L for dewatering & Cleaning of RCC UG sumps of the following capacities by involving of the followings 09 (Nine) stage of cleaning process complete all as specified and directed (i) De-watering by high pressure submersible pump complete (ii) Removal of sludge from sump (iii) Cleaning of walls, floors, ceiling etc by high pressure jet pump 80-180 bar pressure complete (iv) Removing dirt and sludge by vaccum pump. (v) Anti- Bacterial Treatment to inside of tank which is effective against all pathogens complete. (vi) Sterilization of the tank atomosphere by UV radiation inside of the tank. (vii) Applying one coat of white wash internal surfaces. (viii) Replace nylon net for vent pipes & man hole cover (ix) Writing letter in bold with white paint on black colour back ground such as sump number, capacity, cleaned on Date & Due on Date etc
Note for item No 155 :- The Bidder shall take into consideration for following points while quoting his rate for this item and the unit rate is deemed to be included for :- (i) The contractor shall be provide dewatering pump of suitable capacity and mobile generator for operation of dewatering by high pressure submersible pump (or) Diesel driven high pressure pump and the rate quoted is inclusive of rent/hiring charge complete. (ii) Cutting and filling shall be cleared of shrubs, vegetation, grass bush, weed, trees and sapling not exceeding 30 cm in girth, measured at a height of two metre above ground level. Useful material shall be stacked. (iii) Material removed from the tank shall be disposed off at out side MD land. (iv) Tank shall be made available for cleaning for a period of 8 hours only and contractor has to arrange sufficient labour/ T&P to complete the job within the given period only. or otherwise penality shall be imposed @ Rs 500/- per day. (v) All safety with gadgets like safety Belts, special safety ladder, Helmets, Heavy Duty Gum Boots, Gloves, Safety Goggles, Masks, Aprons, etc. for complete security the safe operations. Storage and Cleaning equipment’s like Scrubbers/Wipers, Storage drums, Sludge Collectors and Cisterns, etc. must be integral part of system.
(a) Underground sump of 15000 gallon capacity.
(b) Underground sump of 10000 gallon capacity.
(c) SWT sump of 15000 gallon capacity.
(d) SWT sump of 10000 gallon capacity.
Material and Labour for Plain Cement Concrete (1:2:4), type B1 (using 20 mm graded crushed stone aggregate) as in Coping, bands benching etc including finishing the concrete surfaces even and smooth without using extra cement including necessary form work Complete all as specified and directed.
Supply and fixing Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, hinges and handles etc. , conforming to Fe.290.Gde-E-165 (Steel for fabrication of valve pit chamber, raising main support and motor foundation supports etc complete all as specified and directed).
Material and labour for fabricate supply and fix valve chamber covers made out of suitable size MS angle/MS plate/flat/rod, hinges, locking arrangement including painting with two coats of synthetic enamel paint over one coat of red oxide primer including removimg existing unserviceable rusted cover all as directed.
Material and labour for Painting with two coats of synthetic enamel paint over coat of zink chrome on surfaces of any description, over 10cm in width or girth,not otherwise described complete all as specified and directed.
Material and labour for anti vibration rubber mount of size 8” X 8” of Qty – (06 to 08) Nos for 100 HP pump motors including taking down of old one complete all as specified and directed. Note: Lifting arrangement of pump and modification in PCC foundation and alignment of the delivery and suction pipe will be deemed to inclusive in unit quoted rate.
Taking down and relaying of existing serviceable GI tubing / connection in new or old positions including cleaning, cutting, threding all as directed, along with new GI fittings where ever replaced and required at site of site of size 100 to 150 mm borecomplete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
Taking down and relaying of existing serviceable GI tubing / connection in new or old positions including cleaning, cutting, threding all as directed, along with new GI fittings where ever replaced and required at site of site of size 50 to 80 mm borecomplete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
Supply & Fix as in replacement of GI tubing medium grade of size 150 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
Supply & Fix as in replacement of GI tubing medium grade of size 100 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
Supply & Fix as in replacement of GI tubing medium grade of size 80 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
Supply & Fix as in replacement of GI tubing medium grade of size 50 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
S&F in replacement Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 50mm complete all as specified and directed.
Supply & Fix as in replacement of GI tubing medium grade of size 40 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
S&F in repair Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 40 mm complete all as specified and directed
Supply & Fix as in replacement of GI tubing medium grade of size 25 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
S&F in repair Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 25 mm complete all as specified and directed.
Supply & Fix as in replacement of GI tubing medium grade of size 20 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
S&F in repair Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 20 mm complete all as specified and directed.
Supply & Fix as in replacement of GI tubing medium grade of size 15 mm bore with all fittings on wall/ trenches complete including cutting and thereading all as required at site complete all as specified directed. Note: Excavation & earthwork shall be measured & paid seperately
S&F in repair Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed of size 15 mm complete all as specified and directed.
Over hauling and repair to Chemical Dosing Pump Granual based chloronome plants at different pump house by cleaning the FRP 150 Ltrs Tank, and cleaning of filters and NRV , checking and cleaning the delivery pipe line for chocking , cleaning of chlorination plant and maintainig properly including checking the level of oil in the gauge and topping up as and when required, checking the glands and maintain the plant in all respect and replacement of minor spare for smooth functioning of Chlorination Plant all as directed. Note:- The unit rate quoted shall be deemed to include for the cost of replacement of minor spares such as 'O' rings , nut/screws,washers,bolt, cleaning waste , tools for routine day to day maintenance and necessary servicing to keep the plants in running condition on all days including Sundays and holidays, Replacement of other major spares shall be measured and paid for separately.
Supply only PVC diaphram valve 25 mm dia heavy duty
Supply only Teflon gland square type 3 mm for smooth functioning of Chlorination plant
Supply only Chloroscope chlorine kit upto 2ppm
Supply only Rubber ring for mixing chamber
Supply only Agitator mixing assembly with motor
Supply only PVC NRV set with glass ball for suction and delivery adopter 20 mm dia
Supply only Chlorine dosing piston pump unit complete
Supply Only Chlorine test kit with coloured sample Complete with all testing fitments and OT - solution in Rexene finished box Complete all as specified and as directed
Taking down defective open well submersible pump set 5 HP to 7.5 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed. Note :- (a) The spares shall be measured and paid seperately in the relevent items given below. (b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contractor. (e) Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract. (f) The decision of the Accepting Officer in this regard shall be final and binding.
Supply only shaft sleeves suitable for 5 HP to 7.5 HPmotor pump as per manufacturer's design complete all as specified and as directed.
Supply only Ball bearing suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed. Make : Tata/SKF/NBC
Supply only water seal suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only split casing gaskets suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
Supply only bronze impeller suitable for 5 HP to 7.5 HP motor pump as per manufacturer's design complete all as specified and as directed.
M&L for rewinding of open well submersble electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load all as directed and specified for the 5 HP to 7.5 HP motor capacity.
M & L for laying/fixing on floor centrifugally cast MS pipe medium grade of size 200 mm dia mm bore conforming to IS 1239 with necessary supports and including consumables and painting with one coat of red oxide primer and two coat of synthetic enamel paint including making good the disturbed surfaces of wall/ ceiling etc complete all as directed.
M&L for MS bends,tapers,tee pieces,cross,collars,caps and plugs any type,raducer and angle for pipes up to 200 mm bore confroming to IS-1239 complete all as specified and directed.
Material and labour for removing the submersible pump set of capacity up to 15 HP including pipes and submersible cables complete from the exisiting bore well of depth up to 200 mtr by any suitable method i.e either manual or vehicle mounted motorized system and disconnecting the pump motor to locate the faults in presence of Engr-in-Charge, transporting to Wksp for carry out repairs, reassembling, lowering to bore well after repairs, testing and commissioning complete all as specified and directed
M&L taking out, dismantling pump and motor of submersible pump set of capacity upto 15 HP to carry out repairs and replacements , duly rewinding and replacing worn out parts, applying one coat of spray painting with synthetic enamel paint of existing colour and testing and inserting in borewell after repair complete all as specified and directed. Note :- (a) The spares shall be measured and paid seperately in the relevent items given below as supply only. (b) Cost of labour for replacement of spares and transportation are deemed to be included in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contractor. (e) Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract. (f) The decision of the Accepting Officer in this regard shall be final and binding.
Supply only GM Bush suitable for 15 HP submersible pump set as per manufacturer's design complete all as specified and as directed.
Supply only oil seal thrust bearing suitable for 15 HP submersible pump set as per manufacturer's design complete all as specified and as directed.
Supply only sleeve MS key for impeller suitable for 15 HP submersible pump set as per manufacturer's design complete all as specified and as directed.
Supply only SS coupling bearing suitable for 15 HP submersible pump set as per manufacturer's design complete all as specified and as directed.
Supply only Sand Guard suitable for 15 HP submersible pump set as per manufacturer's design complete all as specified and as directed.
Material and Labour for Cutting DI pipes in position for insertion of new tees and socket of size 150 mm dia Complete all as specified and as directed.
Supply and fixing in replacement butterfly valve of size 80 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, PN-1.6 having Stainless Steel spindle and check nut including operating wheel fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed
Supply and fixing of fully automatic Soft Stater of capacity of 100 HP pump including adjustable OLR relay , along with single phase preventer and display including all connected accessories including taking down of old one complete all as specified and directed. Make : L&T/ ABB/ BCH
Material and labour for Making arrangement to flush out the existing pipe line of any type 110 to 150mm bore and upto 100m length, applying 4.5 N/sqmm pressure kg/sq cm pressure to remove scalings/ sludges/ other blocking materials to make smooth flow of water including testing all as specified and directed.
Material and labour for Making arrangement to flush out the existing pipe line of any type 160 to 200 mm bore and upto 100m length, applying 4.5 N/sqmm pressure kg/sq cm pressure to remove scalings/ sludges/ other blocking materials to make smooth flow of water including testing all as specified and directed.
Note for item 210 to 212 :- (i) The Contractor is deemed to arrange necessary tools and equipments, removing or alteration of fittings from existing pipe lines, arragement of plugging devices, etc to build up specified pressure required to wash out the pipes. This will be inclusive in quoted rate. (ii) Excavation and earth work required will be measured and paid seperately. (iii) The flushing out will be carried out with fresh filled water of well only duly chlorinated with specified sodium hypochlorite solution to disinfect the pipe lines from all pathogens and Coliform organisms.This will be inclusive in quoted rate.
Excavation in trenches for laying under ground cable, errection of poles and stays etc in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep and getting out complete all as specified and directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed.
Removing surplus excavated material to a distance not exceeding 50 meter and depositing where directed at a level not exc 1.50 m above the starting point complete all as specified and directed.
Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983, complete all as specified and directed. Note :- (i) Excavated approved soil shall be ribbed by using sieve to separate composite particles etc. as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness shall be considered for payment.
M & L for Bricks covering with width equal to length of brick as mechanical protection to cable with well burnt sub class ‘B’ bricks laid dry flat complete all as specified and directed.
Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earth work, excavation exc 600mm depth but not exc 1mtr depth, 800 mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. Note :- The tenderer shall take into consideration for following points while quoting rate for this item and the unit rate is deemed to be inclusive for :- (i) Earth work and excavation in any type of soil (ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick complete all as specified and as directed. (iii) Removing excavated material to out side MD. (iv) Laying of any type/any bore of pipe in trenches including taking down. Supply of pipe shall be measured and paid separately (v) 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate as in road to make good existing disturbed surfaces.
Supply and fix for GI pipe light grade 100 mm dia for cable protection on road crossings /plinth protection fixed to the pole, wall etc along with suitable fittings for cable protection complete all as specified and directed. .
Material and labour in repair for 3 ½ core 240 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole etc complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items.
Supply, installation,commissioning and testing of factory assembled ,floor mounted ,free standing type tested LT Feeder pillar panels,with canopy ,as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycrabonate,should be weather, vermin proof, anti -acid,anti-corrossive,UV resistance in accordance with IEC 61439-1,fire retardant and self extingushing in accordance with IEC 60695-2-11 ,UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties ,RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tight to base with thermoplastic screw having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosuser should be minimum 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No. of polycarbonate IP 65 9 W LED transperent bulk head luminaire 6500K,PF > 0.95 under canopy for easy maintenance . Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 300 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded stone aggreate for bedding upto a height of 45 CM above ground level ,including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
(a) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 200 Amps ,36 KA - 02 Nos (Incomer). (b) On Load Change over front operated of capacity 250 Amps,4 Pole ,415 V -01 No. (c) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 160 Amps ,25 KA - 02 Nos. (d) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 63 Amps ,10 KA - 02 Nos. (e) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 40 Amps ,10 KA - 01 No. (f ) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. (g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (h) Space for spare feeder -01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S. (iv) MCCB should be ICu =100% ICs. (v) Make of LT Panel/FPB shall be as per mentioned in list of makes (PS).
Supply, installation, testing & commissioning of maintenance free chemical earthing system comprising of 17mm dia copper bonded rod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducing liquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 Amp by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation including taking down existing one, complete all as specified and directed. Make : Model HTSP 317 of safeTrode or equivalent in OBO Betterman/ FURSE/ERICO.
The quoted rate shall also deemed to be included the following :- (i) Prior to installation of maintenance free chemical earthing, soil resistivity test to be carried out at the location where earthing work to be done in presence of Engr-in- Charge/JE (E/M),user and the report has to submit to Garrison Engineer with recommendation of manufacturer, if required additional interconnection of earthing (not more than 04 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testing and submission of report with recommendation deemed to be included in the quoted rate.
(ii) The description/ size/ qty of items mentioned in above are for indicating only however qty/ size may vary at site condition to maintain the earth resistance 1 ohm. The contractor shall quote rate by considering all factors.
(iii) Rate of earth energizer compound of 25 Kg of 02 bags and earth resistance reducing liquid 10 litre per cane for each pit deemed to be included in the quoted rate.
(iv) Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor before commencement of work.
(v) Earth enhancing material should not leach into the adjacent soil or underground water channels and its PH value should be in neutral range complete all as specified and as directed. It should solidify when mixed with water and set like concrete.
(vi) Copper strip of size 20 x 3 mm shall be fixed on proper post insulator at the instrument end ( copper strip upto 7.5 RM shall be considered in unit quoted rate and extra will be measured and paid separately).
(vii) Testing of earth shall be carried out in presence of departmental and user representative and report shall be submitted to Garrison Engineer duly signed by all concerned.
(viii) Earth resistance tester will be provided by the contractor. Tester should be calibrated from authorised company/ lab.
(ix) Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintained duly signed by all concerned. After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained.
(x) The contractor shall give a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion.
(xi) No further maintenance or periodic watering or recharge shall be required in earthing during its guarantee period of over 03 years in all type of soil including soft/ disintegrated or hard rock.
(xii) During the guarantee period, if earth resistance is not maintained less than 1 ohm the contractor has to redo or rectify at no extra cost to Govt till desired result is maintained.
(xiii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing for each earthing shall be retained from payment due to the contractor from final bill for the guarantee period.
(xiv) The electrode shall carry manufacturer's name .
(xv) The connection clamp shall be permanentlly welded to the copper bounded rod to avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination.
(xvi) The acceptable earth resistance at earth busbar/ test point shall not be more than 0.1 ohm.
(xvii) Earth work such as auguring and making good the surrounding area shall carried out in any type of soil.
(xviii) The contractor shall submit CPRI India certified document for copper bounded rod to ensure genuineness of material.
(xix) Sign board of mild steel sheet 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxide Zinc chrome primer showing result of earthing shall be fixed near the earth pit after completion as directed by engr -in- charge.
S&F in repair copper strip 20 x 3mm thick as earthing lead fixed to wall/roofs etc including taking down existing one, complete all as specified and directed. Note : - All Joints should be joined by Exothermic Welding or Brazing.
Earth pit cover made of heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 7.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm for each electrode pit, complete including taking down, complete all as specified and directed. Make : Model SEPC 250 of SAFE TRODE/ Electrogrip Model/ EGTEK3LC of ISG Global or equivalent in OBO Betterman/ ERICO. Note :- The contractor shall submit load bearing capacity certificate from the manufacturer.
Material and labour as in repair for Earth pit indicator for existing earthing pit made out of 16 mm dia and 60 cm long MS Square bar embedded in PCC (1:3:6) type C-1 using 20 mm graded stone aggregate in PCC block of size 30 X30 X30 cm including CI/MS plate of size 250X300X 3 mm thick fixed on side of earth pit cover complete including painting and writing over the plate ie. Type , Result, Date of measurement and pit number with Black back ground with white letters and complete all as specified and as directed.
Supply, installation,commissioning and testing of factory assembled ,floor mounted ,free standing type tested LT Feeder pillar panels,with canopy ,as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycrabonate,should be weather, vermin proof, anti -acid,anti-corrossive,UV resistance in accordance with IEC 61439-1,fire retardant and self extingushing in accordance with IEC 60695-2-11 ,UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties ,RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tight to base with thermoplastic screw having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosuser should be minimum 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No. of polycarbonate IP 65 9 W LED transperent bulk head luminaire 6500K,PF > 0.95 under canopy for easy maintenance . Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 300 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded stone aggreate for bedding upto a height of 45 CM above ground level ,including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200 Amp, 36 KA - 01 No (Incomer). (b) On Load Change over front operated of capacity 250 Amp, 4 Pole, 415 V - 01 No. (c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 160 Amp, 25 KA - 02 Nos. (d) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp, 10 KA - 01 No. (e) MCB TPN, 415 V of capacity 40 Amps, 10 KA - 02 Nos. (f) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. (g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set (h) Space for spare feeder - 01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S. (iv) MCCB should be ICu =100% ICs. (v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). Note :- An amount of Rs 123862.00 on account of credit schedule for schedule 'A' part II shall be deducted from the total amount of BOQ to arrive at the contract sum.
OM ENTERPRISES (BID ID -3169745)
RAMESH BABU CO (BID ID -3169519)
JM Engineering (BID ID -3173772)
M/S SRI BALAJI ENTERPRISES (BID ID -3169033)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .