| Sl No | Description | Qty | Unit | K S M BASHIR MOHAMMAD AND SONS L5 | GHV (India) PVT. Ltd. L1 | LISHA ENGINEERS PRIVATE LIMITED L4 | VASCON ENGINEERS LTD L3 | Quality Buildcon Private Limited L2 |
|---|---|---|---|---|---|---|---|---|
| 1.00Civil and E&M Works | ||||||||
| 1.01 | SCHEDULE- A: DSR WORKS 2021 | 1 | Nos | 0 ₹101.4 Cr | 0.17 ₹84.7 Cr | 0.12 ₹89.5 Cr | 0.1 ₹91.7 Cr | 0.12 ₹89.2 Cr |
| 1.02 | SCHEDULE- B:NDSR ITEMS | 1 | Nos | 0.35 ₹2.2 Cr | 0.05 ₹3.2 Cr | 0.03 ₹3.3 Cr | 0.18 ₹2.8 Cr | 0.12 ₹3.0 Cr |
| 1.03 | Schedule - C: PEB WORKS | 1 | Nos | 0.35 ₹51.7 L | 0 ₹79.6 L | 0.17 ₹65.8 L | 0.04 ₹76.4 L | 0.12 ₹70.0 L |
| 1.04 | Schedule - D : NDSR PLUMBING ITEMS | 1 | Nos | 0.35 ₹4.3 Cr | 0.12 ₹5.8 Cr | 0.07 ₹7.1 Cr | 0.22 ₹5.2 Cr | 0.12 ₹5.8 Cr |
| 1.05 | Schedule - E (E & M Items) : Electrical & Mechanical Works | 1 | Nos | 0.35 ₹9.8 Cr | 0.12 ₹13.2 Cr | 0 ₹15.0 Cr | 0.22 ₹11.7 Cr | 0.12 ₹13.2 Cr |
Updated dates
Tender Value
₹150.2 Cr
EMD Value
₹3 Cr
Closing Date
12 Mar 2026, 3:00 pmClosed
Managing Director
Uttar Pradesh Metro Rail Corporation, Administrative Building, Near Dr. Bhimrao Ambedkar Samajik Parivartan Sthal, Vipin Khand, Gomti Nagar, Lucknow 226010
Construction of Depot cum Workshop at Vasantkunj on Hardoi Road for East-West Metro Corridor of Lucknow Metro Rail Project.
2026_UPMRC_265441_1
LKCC(02)-01
Open Tender
Civil Works
540 days
Lucknow
As per Tender
6 documents required · 6 mandatory
₹23,600
Yes
UPMRCL (Lucknow Project)
₹3 Cr
Yes
Online
15 May 2026
4 Feb 2026
13 Mar 2026
4 Feb 2026
12 Mar 2026
7 Mar 2026
4 Feb 2026 - 13 Feb 2026
13 Feb 2026
Civil and E&M Works
SCHEDULE- A: DSR WORKS 2021
SCHEDULE- B:NDSR ITEMS
Schedule - C: PEB WORKS
Schedule - D : NDSR PLUMBING ITEMS
Schedule - E (E & M Items) : Electrical & Mechanical Works
Note: 1. In case of any discrepancy/dispute in respect of DSR items, the item description, unit and rates of standard DSR shall be applicable.
Lucknow East West Corridor
Summary for all Schedules
Sub Head No.
i. ELECTRICAL SYSTEM
ii. FIRE ALARM & FIRE FIGHTING
iii. VAC
iv. COMPRESSED AIR SYSTEM
v. PLUMBING WORKS
vi. Any other DSR
Total
SCHEDULE - A (DSR ITEMS)
Sub Head
EARTH WORK
CONCRETE WORK
BRICK WORK
Cladding Work
WOOD WORK
STEEL WORK
FLOORING WORK
ROOFING WORK
FINISHING WORK
Dismantling and Demolishing
ROAD WORK
SANITARY FIXTURES
WATER SUPPLY
SEWERAGE AND DRAINAGE
ALUMINIUM WORK
WATER PROOFING WORK
RAIN WATER HARVESTING & TUBEWELLS
Structural Glazing Aluminium Composite Panel
Total of New Technologies and Materials
Piling works
Horticulture works under Horticulture DSR 2020
MISCELLANEOUS DSR WORKS
TOTAL OF SCHEDULE - A (Inc GST)
TOTAL OF SCHEDULE - A (Exc GST)
(Exc GST)
Schedule A (DSR ITEMS)
Excavating trenches by mechinical / manual means of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, for all depth, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :
Total of Earth Work
Providing and laying in position ready mixed or site batched design mix cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/ Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.
Total of Concrete Work
Total of Brick Work
Total of Cladding Work
Total of Wood and PVC Work
Total of STEEL WORK
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sq.m including pointing the joints with white cement and matching pigments etc., complete
Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately).
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.
Total of Flooring Work
Total of Roofing Work
Pointing on brick work with cement mortar (1:3) :
Applying priming coat:
6 mm cement plaster of mix :
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Total of Finishing Work
Demolishing mud phaska in terracing and disposal of material within 50 metres lead.
Total of Dismantling and Demolishing Work
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-incharge.
Construction of dry lean cement concrete sub base over a prepared subgrade with coarse and fine aggregate conforming to IS:383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per specifications, cement content not to be less than 150 Kg/cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, for all leads & lifts, laid with a mechanical paver, compacting with 8-10 tonne vibratory roller, finishing and curing etc. complete as per direction of Engineer-in- charge.
Total of Road Work
Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.
Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge.
Total of Sanitary Installations
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.
Total of Water Supply
Extra depth for circular type manhole 1.52 m internal dia (at bottom) beyond 2.30 m :
Total of Drainage Work
Total of Aluminium Work
Total of Water Proofing Work
Total of Rain Water Harvesting & Tubewells
Total of Structural Glazing Aluminium Composite Panel
Total of New Technologies and Materials
Total of Piling works
Total (A)
Schedule B (NDSR ITEMS)
WOOD WORK
Total of Wood Work
CONCRETE WORK
Total of Concrete Work
STEEL WORK
Technical Specification should be as follow: Rolling Curtain: Constructed from single skinned galvalume, bright steel laths and is retained by interlocking with each other. Surface: Galvalume with nature finish, Partial Bright Steel with one coat of grey epoxy primer by spray Material Thickness: 1.2mm for clear width > 3.5m & 0.9mm for clear width <= 3.5m as per IS 6248 laths, 8.0mm Curtain Weight: 15.5 kg/m2 approx Structure Shape: Curved, Honeycomb Support Brackets: Mild Steel with one coat of grey epoxy primer by spray Shaft: Shaft is manufactured from mild steel tube of suitable outside diameter and wall thickness to suit the shutter application and is unsprung Finish: One coat of grey epoxy primer by spray Side Guides: 2.0mm thick heavy duty TG Galvanised Steel Finish: One coat of grey epoxy primer by spray Wind lock-Storm anchors: Included
Hood & Motor Cover: 0.9mm thick Pressed galvalume steel hood box complete with reinforced bracket as required to suit the shutter width. Finish: Natural Finish Bottom Profile: Bend-resistant Galvanised steel profile for additional strength. Finish: One coat of grey epoxy primer by spray Locking arrangement: Shoot Bolt Arrangement Seals: Optional on side guides & bottom Surface with protective paint: Optional CE Certified CRS Compact Gear P.R.C. Make Indirect Drive Operator Drive Unit: Indirect drive operator. System power supply wired with industrial plug Safety mechanism: Patented safety mechanism for chain failure with inbuilt limit switches Control Switch: Three station push button with deadman control Emergency manual operation: Emergency operation by means of chain Optional Accessory: Additional three station push button Cost is inclusive of all materials and labour complete (curtain, grill, hood, motor, motor cover, anchors, gears, push button, deadman control and any other if required).
Total of Steel Work
STONE WORK
Total of Stone Work
FIRE DOORS
Total of Fire Doors
MISCELLANEOUS WORK
Making of cutout (cor cutting) in pre constructed RCC/CC work of all grades for services required.
Note:-Payment stages (i)70% on installation (ii)30% on removal/shift.
b. Erection, Dismantling and shifting (from station to station) of Rig Machine
a. 200 MM dia MS ERW Housing pipe having wall thickness 6 MM
b. 150 MM dia MS ERW Blind pipe having wall thickness 5 MM
c. 150 MM dia MS ERW Slotted pipe
a. Transportation of Air Compressor
b. Erection of Air Compressor
c. Running of Air Compressor
Total of Miscellaneous Work
Total Schedule B
Civil, Plumbing, Electrical, VAC, Fire fighting & Fire detection systems for Metro Depot of Corridor 2 at Kanpur
SCHEDULE - B (NON - DSR ITEMS)
Sub Head
WOOD WORK
CONCRETE WORK
STEEL WORK
STONE WORK
FIRE DOORS
MISCELLANEOUS WORK
TOTAL OF SCHEDULE - B (NON - DSR ITEMS)
SCHEDULE - C (NON - DSR PLUMBING ITEMS)
Sub Head
SANITARY FIXTURES
SOIL, WASTE AND RAIN WATER PIPES
WATER SUPPLY
SEWERAGE AND DRAINAGE
PUMPS AND CONTROL PANELS
EFFLUENT TREATMENT PLANT
SEWERAGE TREATMENT PLANT
TOTAL OF SCHEDULE - C (NON - DSR PLUMBING ITEMS)
Signature of Authorized Signatory
On behalf of Tenderer
SCHEDULE - C1
Providing and fixing hand shower (Health Faucet) with 8 mm dia 1 metre long flexible tube and wall hook (Cat. ALD‐573 Jaguar) with rawl plugs and screws etc complete as per directions of Engineer‐in‐charge (P‐11843)
Extra for providing 15 mm water saver CP brass pillar cock in place of ordinary CP brass pillar cock against tender item elsewhere.
Total of Sanitary Fixtures
SOIL, WASTE AND RAIN WATER PIPES
Providing and fixing SS grating with frame including fixing to the floor with cement mortar.
100 mm dia (P- 11798)
Providing and fixing P.V.C. WC connector (straight or bend type) with rubber lip ring including 110 mm dia PVC pipe of required length and proper connection to C.I. pipe complete as required. (P-11843)
Providing and fixing on wall face M.S. Pipe rain water pipes conforming to IS:1239/3589 including jointing with seal ring. Leaving 10mm gap for thermal expansion
200 mm dia (P-11843)
Providing and fixing in position 100x50 mm GI reducing elbow including fix to floor with cement mortar. (P-11844)
Total of Soil, Waste and Rain Water Pipes
WATER SUPPLY
Providing, fixing, jointing and testing in position the following heavy class G.I. pipes conforming to IS:1239 cut to required lengths including all necessary fittings and specials such as bends, tees, union, reducers, flanges & plugs etc. Threading, jointing and making proper connections. 100mm thick fine sand around the pipes. Including excavation in all kind of soil (excluding hard rock), for pipe running at minimum 1.0 m to 1.2 m depth, dewatering, refilling, watering, ramming & removing the surplus excavated material and making good the same complete as required.
100 mm dia (P-11844)
Providing protection to embedded G.I. pipes and fittings by applying pyp kote primer (@ 100 gm/sqm) thereafter wrapping 4mm thick pyp kote (AW 4mm) protection coating by thermo fusion process. Overlap shall be maintained at 15mm. The application process shall be strictly according to manufacturer's specification.
25 mm dia (P-11845)
32 mm dia (P-11845)
40 mm dia (P-11845)
50 mm dia (P-11845)
80 mm dia (P-11845)
100 mm dia (P-11846)
Providing and fixing M.S. puddle flanges fabricated out of 6 mm thick M.S. plate of size 300 x 300mm plus dia of pipe of 750mm long pipe pieces fixed to RCC wall of water tanks. Including painting with two coats of primer complete as required. The entire fitting shall be hot dipped galvanised.
50 mm dia (P-11846)
65 mm dia (P-11846)
80 mm dia. (P-11846)
100 mm dia (P-11846)
150 mm dia (P-11847)
200 mm dia (P-11847)
Total of Water Supply
SEWERAGE AND DRAINAGE
Providing and laying non-pressure NP3 class R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
300 mm dia (P-11847)
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size), inside plastering 12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement complete as per standard design:
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 (P-1843) Inside size 120x90 cm and 90 cm deep with SRFC performated heavy duty HD-20
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 (P-1844) Inside size 120x90 cm and 90 cm deep with SRFC performated cover extra heavy duty EHD-35
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing and fixing uPVC agricultural pipes conforming to IS:4985 Class IV (10 kg/sqcm) including all fittings, e.g. couplings, tees, bends. reducers and screwed adoptors, solvent welded joint as per manufacturers' iecommendations. [for Effluent Line in Work Shop]
160mm OD (P-11848)
Excavating trenches of required width for pipes, cables, etc including excavation for sockets. and dressing of sides. ramming of bottoms, depth upto 1.5 m including getting out the excavated soil, and then reterring the soil as required, in layers not exceeciiria 20 an in depth, including consolidating each eposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :
Pipes, cables etc. exceeding 600 mm dia.
Total of Sewerage and Drainage
PUMPS AND CONTROL PANELS
Providing and fixing heavy duty PVC insulated copper armoured cables 1.1KVA grade including necessary support clamps at ceiling level and connection lugs complete in all respects.
Power cable 3 core 4 mm (P-11849)
Power cable 3 core 6 mm2 (P-11849)
Providing and fixing of cast iron double flanged butterfly valves (PN-25) complete with 2 nos. matching flanges,bolts, nuts, 3.0 mm thick compressed asbestos gasket.
50 mm dia
65 mm dia
80 mm dia p-11850
100 mm dia P-11850
150 mm dia P-2180
Providing and fixing of cast iron double flanged dual plate type check valves (PN-25) including 2 no.s. matching flanges, nuts. bolts. 3 0 mm thick compressed gasket complete.
65 mm dia
80 mm dia (P-2180)
100 mm dia
Providing & fixing of resilient rubber neoprene lined style arch vibration eliminators suitable for raw-water upto pressure 20 kg/cm2..
65 mm dia
80 mm dia (P-2180)
100 mm dia (P-2180)
Providing and fixing of CI Y type suction strainer with gunmetal or brass internal parts installed outside water tanks.
100 mm dia
150 mm dia
Total of Pumps and Control Panels
EFFLUENT TREATMENT PLANT
Designing, providing, installation, testing and commissioning of Metro Boggey Wash effluent treatment plant (ETP) including all electrical & mechanical equipments, piping, valve sleeves, control panels based on any technology like MBBR / FAB, recirculation pumps, wiring panel etc. complete in all respects, including all equipments and consumable materials of ETP but excluding all civil work of R.C.C. tanks for the following incoming and outgoing parameters. The rate shall be inclusive of operation and maintenance for twelve months including man power and consumable items complete. The design basis considered to size the treatment plant is as follows including as required in the specification etc.
Inlet Parameters
Flow : Effluent =75m3/ day for 20 hours operation
COD : 400-600 mg/l
BOD : 200-250 mg/l
TSS : 200-300 mg/l
Oil & Grease : 30-50 mg/l
Outlet Parameters
COD : < 50 mg/l
BOD : < 10mg/l
TSS : <20 mg/l
Oil & Grease : <10 mg/l
The proposal should include the following units in general. However the alternate proposals will also be considered, if found technically suitable.
A) Below Ground Civil Tanks for the ETP plant.
Bar Screen Chamber, oil and grease tank. (R.C.C.)
Equalization tank.(R.C.C.)
Sludge Drying beds of adequate capacity ,for sun drying of ETP plant sludge (Brick Work + R.C.C. + Sand & Pebbles media for the sludge drying beds).
All R.C.C. Civil Foundations works for the Electro-mechanical equipment.
B) Above Ground ETP plant :
Bar Screens (2 nos.) , MSEP , to be fixed in Bar Screen Chamber.
Coagulation, Flocculation & Primary Tube Settling Tank (In M.S. Epoxy construction) & PVC media. -1 no.
Chemical doing pumps , dosing tanks (LDPE/ FRP) & agitators as required for Chemicals Dosing. (for Coagulator & Flocculator)- 1 set
FAB/ MBBR Bio –Reactor tank (In M.S. Epoxy construction) complete with internal strainers + fittings & PP media for the bio-reactor -1 no.
Chemical doing pumps , dosing tanks (LDPE/ FRP) & agitators as required for Chemicals Dosing. (for Secondary Tube Settler)- 1 set
Effluent Feed Pumps (Submersible) – CI construction , 2 nos. (1 working + 1 standby)
Air Blowers, Twin Lobe Type. 2 nos. (1 working + 1 standby)
Air Grids in the Equalisation tank & MBBR tank (in UPVC) with air diffusers as required-1 lot.
Chlorine Contact Tank (In M.S. Epoxy construction) -1 no.
Chlorine Dosing pump & Dosing pump -1set.
Filter Feed Tank (In M.S. Epoxy construction) -1 no.
Filter Feed Pumps (Horizontal Centrifugal -monoblock) – CI construction , 2 nos. (1 working + 1 standby)
Dual Media Filter –MSEP Vessel -1 no.
Activated Carbon Filter –MSEP Vessel -1 no.
Treated Water Storage tank (in HDPE) -15 KL capacity -1 no.
By Pass Arrangement before treated water Sump and from other units as required.
Effluent Treated Water Recirculation pump -2 nos. (1 working + 1 stand-by) of 200 LPM at 30 Mtr.)
ETP interconnecting valves and piping : MS- c-class piping for Air & UPVC – Sch 40 for Effluent & water lines connections. -1 lot
Instrumentation for Tanks water level controlling , pumps dry level protections , pressure Gauges , 2 nos. electro-magnetic flow meters, 1 no. energy meter & 1 no. Air Rota-meter – 1 lot.
Electrical Distribution panel for all ETP plant drives, interconnecting cables (Armoured, Al /Cu conductors) + GI cable trays & GI earthing as required - 1 lot.
1 year ETP -Operation and Maintenance is included.
Total of Effluent Treatment Plant
SEWERAGE TREATMENT PLANT
Designing, providing, installation, testing and commissioning of Sewage treatment plant (STP) including all electrical & mechanical equipments, piping, valve sleeves, control panels based on any technology like MBBR / FAB / Biocask , recirculation pump, wiring panel etc. complete in all respects, including all equipments and consumable materials of STP but excluding all civil work of R.C.C. tanks for the following incoming and outgoing parameters. The rate shall be inclusive of operation and maintenance for twelve months including man power but excluding the consumable items complete. The design basis considered to size the treatment plant is as follows including as required in the specification etc.
Inlet Parameters
Flow : 10 m³/ day for 20 hours operation
COD : 400-600 mg/l
BOD : 200-400 mg/l
TSS : 200-300 mg/l
Oil & Grease : 30-50 mg/l
Outlet Parameters
COD : < 50 mg/l
BOD : < 10mg/l
TSS : <30 mg/L
Oil & Grease : <10 mg/l
The proposal should include the following units in general. However the alternate proposals will also be considered, if found technically suitable.
A) Below Ground Civil Tanks for the STP plant.
Bar Screen Chamber, oil and grease tank. (R.C.C.)
Equalization tank.(R.C.C.)
Sludge Drying beds of adequate capacity ,for sun drying of STP plant sludge (Brick Work + R.C.C. + Sand & Pebbles media for the sludge drying beds). Sludge Drying beds of adequate capacity , for sun drying of STP plant sludge (Brick Work + R.C.C. + Sand & Pebbles media for the sludge drying beds).
All R.C.C. Civil Foundations works for the Electro-mechanical equipment.
B) Above Ground STP plant
Bar Screens (2 nos.) , MSEP , to be fixed in Bar Screen Chamber.
FAB/ MBBR /Biocask Bio –Reactor tank (In M.S. Epoxy construction) complete with internal strainers + fittings & PP media for the bio-reactor -1 no.
Tube Settler tank (In M.S.Epoxy construction) with PVC-media for tube settler-1no.
Chemical doing pumps , dosing tanks (LDPE/ FRP) & agitators as required for Chemicals Dosing. (for Secondary Tube Settler)- 1 set
Sewage Feed Pumps (Submersible)-CI construction, 2 nos. (1 working + 1 standby)
Air Blowers, Twin Lobe Type. 2 nos. (1 working + 1 standby)
Air Grids in the Equalisation tank & MBBR tank (in UPVC / SS) with air diffusers as required-1 lot.
Chlorine Contact Tank (In M.S. Epoxy construction) -1 no.
Chlorine Dosing pump & Dosing pump -1set.
Filter Feed Tank (In M.S. Epoxy construction) -1 no.
Filter Feed Pumps (Horizontal Centrifugal -monoblock) – CI construction , 2 nos. (1 working + 1 standby)
Dual Media Filter –MSEP Vessel -1 no.
Activated Carbon Filter –MSEP Vessel -1 no.
Treated Water Storage tank (in HDPE) -2 KL capacity -1 no.
By Pass Arrangement before treated water Sump and from other units as required.
Sewage Treated Water Recirculation pump -2 nos. (1 working + 1 stand-by) of 50 LPM at 30 Mtr.)
STP interconnecting piping : MS- c-class piping for Air & UPVC – Sch 40 for Effluent & water lines connections. -1 lot
Instrumentation for Tanks water level controlling , pumps dry level protections , pressure Gauges , 2 nos. electro-magnetic flow meters, 1 no. energy meter & 1 no. Air Rota-meter – 1 lot.
Electrical Distribution panel for all STP plant drives, interconnecting cables (Armoured, Al /Cu conductors) +GI cable trays & GI earthing as required - 1 lot.
1 year STP -Operation and Maintenance is included.
Total of Sewage treatment Plant
TOTAL
Civil, Plumbing, Electrical, VAC, Fire fighting & Fire detection systems for Metro Depot of Corridor 2 at Kanpur
SCHEDULE - D (NON - DSR PEB ITEMS)
Sub Head
NON - DSR PEB ITEMS
TOTAL OF SCHEDULE - D (NON - DSR PEB ITEMS)
Schedule D (NDSR PEB ITEMS)
Total
Civil, Plumbing, Electrical, VAC, Fire fighting & Fire detection systems for Metro Depot of Corridor 2 at Lucknow
SCHEDULE - E (E&M ITEMS)
Sub Head
PART-I
TOTAL
Difference Amount
PART-II
TOTAL OF MISC FIRE SUPRESSION ITEMS (AEROSOL BASED)
TOTAL
PART-III
TOTAL
PART-IV
TOTAL
PART-V
TOTAL
PART-VI
GRAND TOTAL
SCHEDULE E - E&M
SCHEDULE - E (E&M ITEMS)
BOQ Item No.
ELECTRICAL SYSTEM
The BOQ specified below include the latest relevent standards, specifications, drawing details and the contractor is required to go through them as referred in tender document while quoting the rates. All the samples/ material intended to be used in the works shall be subject to approval before use as the Employer's representative may opt.
Sub-letting of work by the contractor shall only be permitted in accordance with Special Conditions of Contract.
The items indicating one/Zero quantity can also be operated and variation clause shall be applicable as stipulated in GCC / SCC.
Contractor's shall quote reasonably rates against each item of BOQ (both in word and figure)
Price shall include supply installation, testing & comissioning at site of all equipments, ancilary materials as specified and all such items what so ever required to full fill the intent and purpose laid down in specification.
Switch Boards/panels
MAIN LT PANEL
1 no. 3200A, 415V, 50kA, 4P draw-out Electrically operated ACB complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 3200 A suitable to with stand symmetrical fault level of 65 kA at 415 V. The neutral busbar is to be of same size as phases.
Two incomers & one Bus Coupler shall be interlocked electrically & mechanically so that only two out of three shall be switched on at a time.
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 3200 A suitable to with stand symmetrical fault level of 65 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required.
MAIN EMERGENCY PANEL
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 1000 A suitable to with stand symmetrical fault level of 50 kA at 415 V. The neutral busbar is to be of same size as phases.
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 1000 A suitable to with stand symmetrical fault level of 50 kA at 415 V. The neutral busbar is to be of same size as phases.
Two Normal incomers & DG incomer shall be interlocked electrically & mechanically so that only one out of three shall be switched on at a time.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
NORMAL PANELS
WORKSHOP OFFICE MDB-N1
1 no. 630A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 630 A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
WORKSHOP BAY MDB-N2
1 no. 630A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 630 A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
INSPECTION BAY MDB-N3
1 no. 250A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 250 A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
STABLING SHED MDB-N4
1 no. 160A, 415V, Ics=35 kA, TP MCCB’s with fixed neutral and with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
SUB-STATION MDB-N5
1 no. 160A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
PIT WHEEL LATHE MDB-N6
1 no. 160A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
WATER PUMP PANEL MDB
1 no. 125A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 125A suitable to with stand symmetrical fault level of 35kA at 415 V. The neutral busbar is to be of same size as phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
EMERGENCY PANELS
WORKSHOP OFFICE MDB - E1
1 no. 630A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 630A suitable to with stand symmetrical fault level of 35 kA at 415 V.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
WORSHOP BAY MDB - E2
1 no. 160A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 100% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
INSPECTION BAY MDB-E3
1 no. 160A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 160A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 100% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
STABLING SHED MDB-E4
1 no. 125A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 125A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 100% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
SUB STATION MDB - E5
1 no. 125A, 415V, Ics=35kA, TPN MCCB with variable overcurrent and short circuit releases & each complete with
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 125A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 100% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
FIRE PUMP PANEL MDB
Supply, Installation, Testing & Commissioning of 2 position ATS 0f 250 amp rating with single solenoid operator, having 4P with overlapping neutral and In-phase monitor. The ATS should be UL-1008 listed or confirming to AC-33A duty as per IEC 60947 -6- etc as per drawing & specification
ON,OFF, TRIP (Each for both supply)
out going terminals for cable collection to be provided
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 250A suitable to with stand symmetrical fault level of 35 kA at 415 V. The neutral busbar is to be 100% of phases.
The switchboard shall be complete with all inter connections,risers,internal wiring,labels etc complete as required
100 amps TPN COPPER bus bars with heat shrinkable insulation sleeve (2 Sets)
The switchboard shall be complete with all inter connections, risers, internal wiring, labels etc. complete as required.
CAPACITOR PANEL
Direct cable from Main LT Panel with the following accessories
Outgoing feeders consisting of following accessories.
All MCCB’s shall be of 25 KA breaking capacity.
The switchboard shall be complete with all inter connections, risers, internal wiring, labels etc. complete as required
Addition/Deletion Items
Adjustment rates for addition/deletion of compartmentalised switchgear in above panels/board of following rating including the supply, fabrication, extension, modification of the enclosure or in a separate enclosure, earthing ,basbar, other sub-systems, accessories etc complete as required and as per specifications and as specified in of item 1.0 above
630 A, 4P , 415 volts, MCCB having Electronic Trip Unit with adjustable protection against Overload and adjustable protection against Short Circuit and adjustable protection against Earth fault (Integral), with LED indication lamp for ON, OFF & TRIP.
630 A, TP 415 volts, MCCB having Electronic Trip Unit with adjustable protection against Overload and adjustable protection against Short Circuit and adjustable protection against Earth fault (Integral), with LED indication lamp for ON, OFF & TRIP.
400 A, 4P 415 volts, MCCB having Electronic Trip Unit with adjustable protection against Overload and adjustable protection against Short Circuit and adjustable protection against Earth fault (Integral), with LED indication lamp for ON, OFF & TRIP.
400 A, 3P 415 volts, MCCB having Electronic Trip Unit with adjustable protection against Overload and adjustable protection against Short Circuit and adjustable protection against Earth fault (Integral), with LED indication lamp for ON, OFF & TRIP.
250A, 4P 415V, Ics=35 kA, 4P, MCCB with variable over current, short circuit, Earth fault protection and 1- set of three phase indicating lamps (red, yellow, blue)
250 A TP,415V, Ics=35kA, TP, MCCB with variable over current, short circuit, Earth fault protection with heavy duty solid neutral link and neutral CT and 1-set of three phase indicating lamps
160 A, 4P 415V, Ics=35 kA ,4P, MCCB with variable over current, short circuit, Earth fault protection and 1- set of three phase indicating lamps
160 A, TP 415V, Ics=35 kA ,TP, MCCB with variable over current, short circuit, Earth fault protection with heavy duty solid neutral link with neutral CT and 1-set of three phase indicating lamps
100/63 A, 415V, Ics=25 kA ,TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps
Less than 63A to 40A, 415V, Ics=25 kA ,TP, MCCB with variable over current and short circuit releases with heavy duty solid neutral link and 1-set of three phase indicating lamps
Adjustment rates for addition/deletion of supply & fixing of following including making of suitable holes/space in the panel/DBs and making good all external finishes, terminations etc. complete as required.
Supply & fixing of 200 Amp on load, four pole ATS as per relavent IEC standards with HRC fuses and indications as required, suitable for 415 V, 3 phase, 4 wire, supply with suitable MS enclosure.
Supply & fixing of 125 Amp on load, four pole Automatic Transfer Switch (ATS) as per relavent IEC standards with HRC fuses and indications as required, suitable for 415 V, 3 phase, 4 wire, supply with suitable MS enclosure.
75/60 HP, Star Delta starter comprising 3 Nos. TP contactor AC-3 duty Auto/Manual switch, Start Stop push button, bimetallic over current relays single phasing preventer and timer & with potential free contacts for remote monitoring and control.
50/45 HP, Star Delta starter comprising 3 Nos. TP contactor AC-3 duty Auto/Manual switch, Start Stop push button, bimetallic over current relays single phasing preventer and timer & with potential free contacts for remote monitoring and control.
10/7.5 HP, Star Delta starter comprising 3 Nos. TP contactor AC-3 duty Auto/Manual switch, Start Stop push button, bimetallic over current relays single phasing preventer and timer & with potential free contacts for remote monitoring and control.
Upto 5.5HP, DOL starter comprising 3 Nos. TP contactor AC-3 duty Auto/Manual switch, Start Stop push button, bimetallic over current relays single phasing preventer and timer & with potential free contacts for remote monitoring and control.
Electrical Operating mechanism (Motorised mechanism) for all types of above MCCBs
5-32A FP MCB 10 kA
40-63A FP MCB 10 kA
5-32A TP MCB 10 kA
40-63A TP MCB 10 kA
5-32A DP MCB 10 kA
40-63A DP MCB 10 kA
5-32A SP MCB 10 kA
40-63A SP MCB 10 kA
16-32Amp DP RCCB, 30 mA
Miscellaneous Switchgear
Other accessories
Supply and fixing of the following safety equipments in Aux. Sub.Station/MDB room as per detailed descriptions given below and as per relevant IE rules & code of standard practice
TOTAL E.01 - MV SWITCHGEAR
Supply, installation, testing & commissioning of front operated front access cubical type indoor duty dead front wall / recess/ surface mounting, totally enclosed dust and vermin proof (minimum protection IP 54) panels with foamed-in neoprene gasketted hinged doors, fabricated from 2 mm thick CRCA sheet with powder coated finish suitable for 415 V, 3-phase, 4 wire, 50 Hz system including suitably rated insulated copper busbars, interconnections, neutral bar assembly, phase segregating barriers, LED indicating lamps for incoming feeders,15% spare space for future expansion, knockouts and gland plates for entry of cables and conduits, all internal wiring using high temperature FR wires, independant terminals for each phase, earthing terminals and including the cost of providing Master key lock on the door and pad locking facility on door as well as at incomer, bonding to earth etc. complete as per specification, drawings as required and as under:
Lighting distribution boards (LDB) Type-1
1 no. 32 amp DP 10 kA MCB with thermal magnetic protective releases incoming with 2 pole 40 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 6 nos 6/10/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-2
1 no. 63 amp DP 10 kA MCB with thermal magnetic protective releases incoming with 2 pole 63 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 12 nos 6/10/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-3
1-32 amp 4P 10 kA MCB with thermal magnetic protective releases incoming with 4 pole 40 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 3 single phase banks each comprising of 1-32 amp DP 30 mA ELCBR/RCCB incoming and 4 nos 6/10/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-4
1-40 amp 4P 10 kA MCB with thermal magnetic protective releases incoming with 4 pole 40 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 3 single phase banks each comprising of 1-40 amp DP 30 mA ELCB/RCCB incoming and 6 nos 6/10/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-5
1-40 amp 4P 10 kA MCB with thermal magnetic protective releases incoming with 4 pole 40 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 3 single phase banks each comprising of 1-40 amp DP 30 mA ELCB/RCCB incoming and 8 nos 6/10/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-6
1-63 amp 4P 10 kA MCB with thermal magnetic protective releases incoming with 4 pole 63 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 3 single phase banks each comprising of 1-63 amp DP 30 mA ELCB/RCCB incoming and 12 nos 6/10/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
Power distribution boards (PDB) Type-1
1-100 amp TPN 15 kA MCCB with thermal magnetic protective releases incoming with 4 pole 63 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 8 nos 40 amps TP 10 kA MCB and 7 nos 32 amps DP 10 kA MCB with thermal magnetic protective releases out goings.
Power distribution boards (PDB) Type-2
1-125 amp TPN 25 kA MCCB with thermal magnetic protective releases incoming with 4 pole 125 amp HDHC tinned copper bus bar with coloured heat shrinkable PVC sleeves and 8 nos 63 amps TP 10 kA MCB with thermal magnetic protective releases out goings.
Lighting distribution boards (LDB) Type-8
6 WAY TPN with Timer on 2-phases
1-40 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1-40 amp 30 mA DP ELCB incoming and 6 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-40 amp 30 mA DP ELCB incoming with 32 amp ON position latched contactor and 24 hours programe timer for operation of incoming and 6 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
TOTAL E.02 - DISTRIBUTION BOARDS
The Cable and Cable Containment System specified herein, must confirm to technical Specifications, in addtion to the description given in respective items of BOQ, whether explicitly specified or not. In case of contradiction between specifications and description in BOQ, the most stringent of the condition will apply.
It may be noted that Contractor will be required to carry out cable sizing based on actual cable lengths, as per Working Drawings developed by him and after incorporating any changes in load requirements from the tendering stage. Optimisation must be carried out during cable sizing to reduce the cable requirement and size. Further, Contractor must obtain Engineer's approval on the Cable SIzing Calculation.
Cable Laying in cable trays, walls etc
Supply, laying, testing and commissioning of 1100 V grade, armoured, FRLSH, XLPE, aluminium(AL) / Copper (CU) conductor cables on existing trays/walls/columns/ indoor including the cost of supports with suitable clamps, saddles, hooks, bolts etc. & in ground/trenches including the cost of proper dressing of cables, markers providing identification tags, sand filling etc. (cost of excavation, sand & bricks, included here) earthing of glands armouring etc. complete as per specifications as required and as below.
Cable jointing and termination of cable as per item 1.1 -including cost of supplying and fixing, crimping lugs, double compression brass glands, insulation tape etc. complete as per specifications and as required.
Supply, laying testing and commissioning of 1.5 sqmm 1100 V grade, armoured, FRLS PVC insulated, FRLS PVC sheathed copper conductor cables on existing trays/walls/columns/ indoor/ trenches including the cost of supports with suitable clamps, saddles, hooks, bolts etc. and including the cost of proper dressing of cables and including the cost of providing identification tags etc. complete as per specifications, as required and as below.
Note : Termination of all control cables to be provided under the above item and as per schematic diagram including the cost of supplying and fixing crimping lugs, compression type brass glands, heavy duty ferrules, insulation tape etc. complete as per specifications and as required
Supply and laying of 4 pair Cat-5e cable complete as required in heavy guage GI conduit.
Cable Trays & Raceways
Supply, fabrication & installation of perforated hot dipped galvanised double bended cable trays of GI sheets continuously connected including horizontal and vertical bends, reducers, tees, and other accessories complete as per specifications, as required and as below.
Cable Trays
Supply, installation and testing of sheet steel raceways in floor, fabricated from 2.0 mm thick GI with minimum coating thickness 260 gm / sq. meter on both sides with removable cover plate complete with counter sunk cadmium plated brass screws, bends, tee-junctions, cross junction etc. rendered electrially continous as approved and of following sizes
Supply & installation of prefabricated, GI, ladder type cable tray conforming to Technical Specifications, continously connected including horizontal & vertical bends reducers, tees, coupling plate, nut bolts washers& all material required for installation i.e Tie Rods, GI angles, Channels, earth link etc conforming to Technical Specifications, complete as required. The side runners shall be 100 x 20 x 2.5 mm and centre rungs shall be of size 30 x 15 x 2.5 mm with centre to centre distance of 250 mm, as required. (With double reverse flange)
Supply, fabrication & installation of Hot dipped galvanised Iron(HDGI) cable tray covers (Non-perforated) 50mm deep made out of 1.6 mm thick steel sheet suitable for oerforated and ladder trays including all HDGI accessories like clamp, bolt nut etc. complete as per specifications, as required and as below
Note : Hot Dipped Galvanised Iron (HDGI) suspenders and necessary anchor fasteners or any other fabricated item of any size as approved is included in this item and shall not be paid separately.
Supplying & fixing of rectangular, G.I. Cable trunking of Following sizes including pull boxes as required at site, 2 mm thick, as specified in Technical specifications, with removable cover throughout its length with center-screw latch fixing, or quick-fixing device to the Engineers approval, earthing arrangement including provision of earthing strips at joints etc. complete as required.
Providing 2 hour fire rating with PROMASEAL Bulkhead Sealer system as per IS1530:Part 4 and BS: 476 Part 20 to seal the opening required to passage of cable, cable trays, ducts, MS pipes etc. through walls/slabs – Comprising of one layers of 100mm thick, 120kg density rock wool panels tightly sealed and coated with 1 mm of PROMASEAL Bulkhead Sealer. The layers of coating is also extended to 50mm into the adjoining wall/slabs and 100mm on cables to achieve 2 hour fire rating as per BS: 476 part-20: 1987. All the Joints are filled with Promaseal An Acrylic Sealant.
Bus Trunking
Supply, installation & testing of 25 A, Copper, Lighting Bus Trunking System in easy detachable and conveninet assembly suitable for 415 +-10% Volts, 3 Phase+ + Neutral, 8 Wire, 50 Hz A C System with Cu Bus Conductors of minimum 2.5 sq mm section and stainless steel / hot galvanised steel enclosure, with tap off provision every 0.5 mtr. The Lighting Bus Trunking shall be confirming to latest IEC Standards. It shall be with IP-55 Protection, halogen free and Fault Level Withstand Capacity of 2.5 kA min for 0.1 Sec (Icw) and 9.6 kA (Ipk). The Bus Trunking shall be complete with accessies like supporting clamps for Installation at Site, Fixing Clamps for lumanaries etc.
TOTAL E.03 - MV CABLING
Whether explicitly stated in the schedules below or not, the following must be complied with:
Supplying all materials, storing, handling, fixing, laying wiring and testing for light, fan, exhaust fan and 6A Socket points etc starting from the point control box to the point by using 2.5 sq.mm 1100 volts grade FRLHS stranded copper conductor in concealed GI Stove enamelled 16 gauge conduit including 2mm thick GI boxes, fan regulator boxes, together with wiring accessories such as 6A moulded flush mounted modular switches, sockets in boxes of suitable sizes including circuit wiring with 2 x 2.5 sq.mm 1100 volts grade FRLHS PVC insulated stranded copper conductor along with one run of 2.5 sq.mm PVC insulated (green colour) stranded earth wire complete with earthing of fixtures, sockets and boxes. PVC bushes for conduits ends, chrome-plated brass screws, identification ferrules at either ends complete in all respects as per standard specifications.
Note: Lights, fans and 6 amps socket outlets may be wired on a common circuit, and circuit shall not have more than ten points of light, fans and 6 amps sockets or a load of 800 watts whichever is less.
Switch Controlled Primary Light Points
Point wiring for switch controlled primary light points with 3 x 2.5 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/ hangers etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing modular grid plate mounted flush mounted 240 volt 6 amp control switch of approved quality & colour housed in zinc chromate passivated GI boxes with moulded cover plate and including cost of circuit wiring (from DB to first switch in the sub circuit) complete as per specifications and as required.
DB/MCB Controlled Primary Light Points
Point wiring for DB/MCB controlled primary light points with 3 x 2.5 sq mm (P+N+E) FRLSH PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/ hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting complete as per specifications Including cost of circuit wiring (From DB to first light point) complete as per specifications & as required (cost of MCB not included)
Point wiring for Four/three 400W highbay/250W high/medium bay light fixtures, DB controlled primary light points with 3 x 4.0 sq mm (P+N+E) FRLSH PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 32mm dia GI recessed and/or surface conduiting system including cost of providing saddles/ hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting complete as per specifications Including cost of circuit wiring (From DB to first light point) complete as per specifications & as required (cost of MCB not included)
Secondary Light Points
Point wiring for Secondary light points with 3 x 2.5 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting complete as per specifications and as required.
Secondary light points for Four/three 400W highbay/250W high/medium bay light fixtures with 3 x 4.0 sq mm (P+N+E) FRLAH PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 32mm dia MS recessed and/or surface conduiting system including cost of providing saddles/hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting complete as per specifications and as required.
Ceiling Fan Points
Point wiring for ceiling fan points with 3 x 2.5 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing modular grid plate mounted flush mounted 240 volt 6 amp control switch and 240 volt 300 watt 5 Step electronic speed regulator of approved quality & colour housed in zinc chromate passivated GI boxes with moulded cover plate and with inter connections complete as per specifications and as required.
Exhaust Fan Points
Point wiring for exhaust fan points with 3 x 2.5 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hanger etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing modular grid plate mounted flush mounted 240 volt 6 amp control switch and including cost of supplying and fixing 240 volt 6 amp socket outlet near exhaust fan of approved quality & colour housed in zinc chromate passivated GI boxes with moulded cover plate and with inter connections complete as per specifications and as required.
Air Circulator Fan
Point wiring for 16 amp socket outlets with 3 x 4 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hangers etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing of 1 No. 16A 3 pin socket outlet in 2mm thick GI enclosure controlled by one 16A SP MCB complete as required. (Outlet shall be installed at 1800mm AFFL & Controlling MCB shall be installed at 1000mm) (Cost of circuit wiring included in above item)
Wiring for Socket Outlets
Point wiring for 6 amp socket outlets with 3 x 2.5 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc as required and including the cost of cutting/making good chases in brick work and including the cost of supplying and fixing modular grid plate mounted 240 volt 6 amp 5 pin combined shuttered socket outlets alongwith 240 volt 6 amp control switch of approved quality and colour housed in zinc chromate passivated GI boxes with moulded cover plate and interconnections and including the cost of loop earthing with 2.5 sq mm FR PVC insulated 660/1100 volt grade stranded copper conductor wires complete as per specifications and as required.
Point wiring for 16 amp socket outlets (1 outlet wired on 1 circuit) with 3 x 4 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including cost of providing saddles/hangers etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and including the cost of supplying and fixing modular grid plate mounted 240 volt 16 amp 3 pin combined shuttered socket outlets alongwith 240 volt 16 amp control switch of approved quality and colour housed in zinc chromate passivated GI boxes with moulded cover plate with interconnections complete as per specifications and as required.(Cost of circuit wiring included in above item)
Point wiring of 16 amp socket outlets (2 outlets wired in 1 circuit) with 3 x 4 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/making good chases in brick work and including the cost of supplying and fixing modular grid plate mounted 240 volt 16 amp 6 pin combined shuttered socket outlets alongwith 240 volt 16 amp control switch of approved quality and colour housed in zinc chromate passivated GI boxes with interconnections complete as per specifications and as required. (two switched socket outlets shall be connected to one circuit. Both the outlets shall be measured and counted as 1 units) Cost of circuit wiring included in above item.
Point wiring for 20 amp single phase socket outlets with 3 x 4 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing 20 amp 10 kA "C" DP MCB and including 240 volt 3 pin 20 amp industrial metal clad socket outlet with interconnections in 16 SWG powder coated GI box and including the cost of 3 pin 240 volts plug top complete as per specifications and as required.
Point wiring for 32 amp single phase socket outlets with 3 x 6 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (84 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia G.I. recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing 32 amp 10 kA "C" DP MCB and including 240 volt 3 pin 32 amp industrial metal clad socket outlet with interconnections in 16 SWG powder coated MS box and including the cost of 3 pin 240 volts plug top complete as per specifications and as required.(Cost of circuit wiring included in above item)
Point wiring for 3 phase 32 amp socket outlets with 6 x 6.0 sq mm stranded copper conductor FRLHS PVC insulated 1100 volt grade wires (3P+N+2E) 660/1100 volt grade flexible stranded (84 strands of 0.3 mm dia) copper conductor wires in IS embossed 50 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing industrial type 32 amp 10 kA "C" 4P MCB and 415 volt 32 amp industrial metal clad socket outlet in 16 SWG powder coated GI box with interconnections and including the cost of 415 volts 32 amp 4P plug top complete as per specifications and as required..
Point wiring for 3 phase 63 amp socket outlets with 6 x 10.0 sq mm stranded copper conductor FRLHSPVC insulated 1100 volt grade wires (3P+N+2E) 660/1100 volt grade flexible stranded (84 strands of 0.3 mm dia) copper conductor wires in IS embossed 50 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/ making good chases in brick work and including the cost of supplying and fixing industrial type 63 amp 10 kA "C" 4P MCB and 415 volt 63 amp industrial metal clad socket outlet in 16 SWG powder coated GI box with interconnections and including the cost of 415 volts 63 amp 4P plug top complete as per specifications and as required..
Point wiring for weather proof 16 amp outlets with 3 x 4 sq mm (P+N+E) FRLHS PVC insulated 660/1100 volt grade flexible stranded (56 strands of 0.3 mm dia) copper conductor wires in IS embossed 25 mm dia GI recessed and/or surface conduiting system including the cost of providing saddles/hangers etc. as required and including the cost of cutting/making good chases in brick work and including the cost of providing and fixing 2 pole 16 amp switch with 16 amp 240 volts socket outlet and plug top mounted and including a IP 56 rated surface/recessed box with the total unit having IP 56 ingress protection complete as required. (Cost of circuit wiring included in above item)
Supply installation testing and commissioning of Occupancy sensor based movement detector with a build-in switch suitable for recessed/surface mounting at a height of 3m with detection pattern of 6m X 8m. The sensor should have an operating voltage range of 240VAC +/10%; 50/60Hz and should be able to take upto 6A of electrical load and should be able to provide the switch off delay from 1 minute to 30 minutes range. The sensor should be in compliance with EN/IEC 60669-2-1, IEC (EN) 60669-2-1, IEC (EN) 61547, IEC (EN) 55015 and IEC (EN) 55022, class B.
TOTAL E.04 CONDUIT WIRING
Supply, installation, testing & commissioning of light fittings including all accessories e.g. Driver, Reflector, surface/recess mounting arrangement etc. including necessary supports, accessories and hardware as per specifications & as required at site and as below:
The lighting system must confirm to the perticular specfication in addition to the description given in BOQ, in case of contradiction BOQ shall prevail.
Supply, installation, testing and commissioning of LED 2X2 recess mounted fixture - 40 Watt that delivers 3500 nominal lumens at a system efficacy of >90lumen/watt for a design ambient temperature of 45 deg C (Similar to Philips Catalogue no. RC380 LED35 6500 PSU – OD WH or equivalent). The luminaire shall have a CRCA powder coated body and a high efficiency diffuser. The light output shall have a CRI>80 and the luminaire shall be made available with a CCT 6500K or as required. The electronic driver shall operate a power factor>0.9 and a THD<10%. (BOH with False Ceiling Area)
Supply, installation, testing and commissioning of LED recessed mounted 1x4 luminaire with a system lumen output of 3200 lumens and a minimum system efficacy of 115 lm/W. The Luminaire shall be IP20 rated and shall have a life of 40k hours at L70 .Luminaire should have CRCA housing with Opal PMMA diffuser. Similar to Philips catalogue no. RC380B LED32S-4000 L120W30 PSU OD.(For office area)
Supply, Installation, Testing & commissioning of Down Lighter as per the approved make of list. The luminaire should be suitable for recessed/ suspended. The luminaire should have die cast aluminium heat sink CRCA with high efficiency polycarbonate diffuser. The fixture comes with an integrated constant current. The luminaire shall have total lumen output package of minimum 1800 lumens with system efficacy of >120lumen/ watt, CCT 4000-6500K. It should have min IP-20 protection (Public/ toilets/ BOH).
Supply, installation, testing and commissioning of LED recessed mounted downlighter luminaire with a system lumen output of 1800 lumens and a minimum system efficacy of 85 lm/W. The Luminaire shall have a life of 30k hours at L70.Luminaire should have polycarbonate cover with diffused optics. Similar to Havells catalogue no. ENDURANEODLR21WLED857MOD.(For Corridor area)
Supply, installation, testing and commissioning of LED surface mounted downlighter luminaire with a system lumen output of 1200 lumens and a minimum system efficacy of 100 lm/W. The Luminaire shall be IP20 rated and shall have a life of 30k hours at L70.Luminaire should have polycarbonate cover with diffused optics. Similar to Philips catalogue no. SM260C LED12S- 4000 PSU WH.(For Toilets)
Supply, installation, testing and commissioning of LED surface mounted downlighter luminaire with a system lumen output of 2000 lumens and a minimum system efficacy of 110 lm/W. The Luminaire shall be IP20 rated and shall have a life of 30k hours at L70.Luminaire should have polycarbonate cover with diffused optics. Similar to Philips catalogue no. SM261C LED20S- 4000 PSU WH.(For corridors/passeges,entrace lobby)
Supply, installation, testing and commissioning of LED Linear recessed fixture, with a system lumen output of 3000 lumens at a system efficacy of 120 lumen/watt. The luminaire shall have powder coated CRCA housing and light output is by means of fully difuused luminaire having SDCM<5. Luminaire should have THD<10% with PF>0.95. Similar to Havells catalogue no VENUSNEOHE4X1PLR28WLED857MOD or equivalant.
Supply, Installation, Testing & commissioning of LED batten luminaire as per the approved make of list. The luminaire should be suitable for wall/ surface/ suspended The luminaire should have extruded aluminium housing with polycarbonate diffuser cover. The luminaire shall have total lumen output package of minimum 2000 lumens with system efficacy of >120lumen/ watt, CCT 4000-6500K. It should have min IP-54 (BOH ROOM/ STAIRS)
Supply, installation, testing and commissioning of surface mounted LED Batten, with a minimum system lumen output of 2000 lumens and a minimum system efficacy of 105 lumen/watt. The luminaire shall have a CRI of greater than 80 with rated system lifetime of 40,000 hours at L70 and IP protection as IP20. The luminaire is made of CRCA housing and shall have diffused optics.Similar to Philips catalogue no.BN308C LED20 NW or equivalant. (for non false ceiling equipment room)
Supply, installation, testing and commissioning of Batten with 18W LED Tube (MASTER TLED) with a nominal system lumen output of 2100 lumens.The luminaire should have a color temperature of 6500K and CRI>80. The luminaire shall meet IP65 rating with THD < 10% and PF > 0.95. ((Similar to Philips catalogue No.TCW 450P 2 X TLED 18 W+18W MASTER TLED or equivalent as approved make). (For workshop & inspection bay platform area))
Supply, installation, testing and commissioning of surface mounted LED batten with a system lumen output of 4000 lumens and system efficacy of 100 lumens/Watt . The luminaire shall be IP65 rated (Similar to Philips catalogue No.WT201C LED40S-4000 PSU L120 or equivalent as approved make) (For workshop & inspection Bay area)
Supply, Installation, Testing & commissioning of LED Bulkhead as per the approved make of list. The luminaire should be suitable for installations in Shafts/ ducts etc. The luminaire should have pressure die cast housing with high efficiency diffuser. The luminaire shall have total lumen output package of minimum 750 lumens with system efficacy of >110 lumen/ watt, CCT 4000-6500K, TDH<10%. It should have min IP-66 and IK-09 protection(Shaft/ Ducts etc.).
Supply, Installation, Testing & commissioning of highbay. Fitting should have a aluminium pressure die cast housing with tempered glass for high transmittence. Luminaire should have system wattage of 80W with system efficacy of 130 lumens/W. The luminaire should have SDCM<5 with high voltage cut off and autostart facility at 320V. It is designed to meet IP66 and IK08 specifications ensuring L70 for 50000 burning hours with a THD<10% and PF of >0.95 with input voltage of 140-270V. Similar to PHILIPS BY225P LED100S CW WB PSU FG GR V1. (for Street lighting)
Revolving Search Light
Supply, Installation, testing, Commissioning of Flexible LED Strip with Suitable electronics Driver, with a system wattage of 5W per mtr. The Luminaire shall be minimum IP-65rated and have a CRI of 80. This shall be powered bt a separate , replaceable, constant voltage electronic driver, output short circuit protection and other safety test. The housing of luminaire is made of flexible PCB , dual layers, similar to tri-colour, Tiranga LED strip light for decorative pole Lighting or equivalent.
Supply, installation, testing and commissioning of LED In Ground Uplighter with a system lumen output of 1000 lumens and a system efficacy of 90 lumen/watt. The luminaire shall be IP67 & IK10 rated and shall have a CRI of 70. The housing of luminaire is made of high pressure die cast aluminium with front cover made of toughened glass diffuser.Similar to catalogue no.BA WO 12W WW or equivalent as approved make.(For Facade Lighting)
Supply, installation, testing and commissioning of wall surface mounted (only at Jali locations) LED Linear light with a system lumen output of 1900 lumens and a system efficacy of >80 lumen/watt. The luminaire shall be IP65 & IK08 rated and shall have a CRI of 70. The housing of luminaire is made of high pressure die cast aluminium with front cover made of toughened glass diffuser.Similar to catalogue no.BA WW IN1 AS 24W WW or equivalent as approved make.(For Facade Lighting)
HIGH/MEDIUM / LOW BAY FIXTURES
Supply, Installation, Testing & commissioning of LED luminaire similar to form factor of Philips Maxoled range or equivalent as per approved make. Fixture should have a IP65 rated high pressure die cast aluminum housing using dedicated lens based optics providing beam angles of 2X30 or 2X10 degrees (based on the application height). The luminaire shall be capable of delivering a minimum nominal system lumen output of 24000 at a minimum nominal system efficacy of 110 lumen/Watt and a Color rendering index (CRI) > 80. The fixture shall be designed to ensure L70 @ 50,000 burning hours or higher. The driver shall have a power factor of at least 0.95 and a THD<10% at full load.The luminaire shall comply with requirements of CE ,CISPR 15Ed72 , IEC 61347-2-13, IEC 61547, IEC 62384. (Similar to Philips catalogue No. BY416P LED240S CW SK60 FG GR NI S5 or equivalent as approved) (For Workshop Lathe & Inspection bay )
Supply, Installation, Testing & commissioning of LED luminaire similar to form factor of Philips Durabay range or equivalent as per approved make. Fixture should have a IP65 rated high pressure die cast aluminum housing using dedicated lens based optics providing beam angles of 2X30 or 2X55 degrees (based on the application height). The luminaire shall be capable of delivering a minimum nominal system lumen output of 16000 at a minimum nominal system efficacy of 130 lumen/Watt and a Color rendering index (CRI) > 80. The fixture shall be designed to ensure L70 @ 50,000 burning hours or higher. The driver shall have a power factor of at least 0.95 and a THD<10% at full load.The luminaire shall comply with requirements of CE ,CISPR 15Ed72 , IEC 61347-2-13, IEC 61547, IEC 62384. (Similar to Philips catalogue No. BY325P LED160S CW PSU GR FG XTFCL V1 or equivalent as approved) (For Workshop Lathe & Inspection bay ) (Light fixture code-M)
Supply, Installation, Testing & commissioning of 80 W LED High Bay luminaire similar to Philips cat no. BY 325P LED 100S CW FG WB or equivalent as approved makes) Fixtures should have IP-65 rating
Supply, Installation, Testing & commissioning of 70 W LED Low Bay luminaire similar to Philips cat no. BY 150P LED 76S CW PSU HE SY120 FG GR or equivalent as approved makes) Fixtures should have IP-65 rating
Supply, installation, testing & commissioning of the following fans including fixing arrangement and with all accessories like down rods, 5 step electronic fan regulators, cover plates, cups as required for the following complete with necessary GI pipe required for hanging of the fans etc.
Ceilng fan 1400 mm sweep with Electronic regulator complete with all accessories required.
600mm sweep Air Circulator Fans minimum of 1400 rpm, Air delivery minimum of 400 mtr cube/minute , 230 to 240 volts, 1 phase, 50 Hz complete with stand, ground, regulator, pedestal as required. Note: Air delivery shall be measured at 3.6 mtrs from fan.
Supply, installation, testing and commissioning of exhaust fan with fan guards on both sides, double ball bearings, class-E insulation, capacitor (pf 0.90 or better) complete with all other accessories as per IS 2312 and as required, of following sizes:
size 450/300mm dia, 1400 rpm
HVLS Fans
Supply, installation testing and commissioning of "High Volume Low Speed Fans Dia: 16ft, Voltage 420V, Phase: 3 phase" with all other necessary accessories including down rod of suitable length & strength as per specification.
Brush Less Direct Current (BLDC) Fan with Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
TOTAL E.05 - INDOOR LIGHTING AND FANS
Supply, installation, testing and commissioning of the following lighting fixtures including fixing arrangement and with all accessories and lamps as required for
Supply, installation, testing and commissioning of surface mounted LED flood light with a system lumen output of 21500 lumens. The luminaire shall have a aluminium pressure die-cast housing and a minimum system efficacy of 102 lumen/watt. The luminaire shall have a CRI greater than 70 with rated system lifetime of 50,000 hours at L70. (Similar to catalogue No.BVP410 LED 215 CW HE NB FG S4 XTFCL or equivalent as per approved make) (For external area)
Supply, Installation, Testing & commissioning of Flood Light luminaire as per the approved make of list. The luminaire should have Pressure die cast housing with dedicated optics giving optimal light uniform distribution configuration. The luminaire shall have total lumen output package of minimum 14000 lumens with system efficacy of >120lumen/ watt, CT 4000K-5700K. It should have min IP-65 and IK-07 min protection(External).
Supply, installation, testing and commissioning of LED Supply of Surface Mounted 50 Watt Smart Bright LED Flood light similar to Phillips cat. no B0722RS1XL and operating voltage range from 110 VAC to 270VAC, Fixture to be made of extruded aluminium housing, with Tempered glass cover, IP65( Waterproof) and including mounting of sutable MS frame with all accessories or site requirement (For External Art Work)
Supply, installation, testing and commissioning of LED Supply of Surface Mounted 70 W smart bright LED Flood light simillar to PHILIPS B071VG2PQW or similar make and operating voltage range from 110 VAC to 270VAC,Fixture to be made of extruded aluminium housing, with Tempered glass cover, IP65( Waterproof), and including mounting of sutable MS frame with all accessories or site requirement (For External Art Work)
Supply, Installation, Testing and Commissioning of LED Post Top cum Street Light having Top Red Illuminated for Aesthetic & Night Lilly Appearance with a system lumen output of 3500 lumens and a minimum system efficacy of 100 lm/W, Along with 2.35M Standard Pole, The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. System wattage 35W, The luminaire should have a color temperature of 5700K and CRI > 70.IK-08 The luminaire shall meet IP66 with THD < 10% and PF > 0.9. Operating Voltage 140-270VAC,The luminaire shall have closed diffused optics with polycarbonate diffuser board. The total power consumption should not exceed 27W (including driver). Similar to Make BGP400 LED35 L CW MR FG S1 or equivalent as per approved make. (For entrance area)
Supply, Installation, Testing and Commissioning of LED Bollard Light having relaxed warm white well-lit, with reduced glare having opal PC diffuser.Symmetrical light distribution.Low maintenance cost. PDC Heat sink on Top for better thermal management and Extruded aluminium body in grey powder coated. Constant current electronic driver provided with high voltage, open & short circuit protection IP65 & IK07. Similar to Make BGBOL 1000 9W LED WH - 1M FLUTE BOLLARD or equivalent as per approved make. (For entrance area)
Supply, installation, testing and commissions of External lights as per specifications and drawings complete with the following
Lighting Poles
High Mast complete as required above
PIPES
Supply and installation of following heavy/medium grade GI pipes for cables crossing the rail tracks with all bendings complete as required
Supply, fixing and laying of HDPE pipes complete with joints including necessary excavation & back filling complete as required
Supply, fixing 150 mm RCC Hume pipes(Class NP-4) in road crossing and below paved areas complete as required including road cutting and making good the damages etc.
TOTAL E.06 - EXTERNAL LIGHTING
EARTHMAT
PLATE EARTHING
Providing and making plate earthing station including the cost of 600 mm x 600 mm x 6.3 mm G. I. plate electrode, 15 mm dia G.I.watering pipe, CI funnel with wiremesh charcoal/coke , salt, all earth work, masonry enclosure with frame,hinged cover plate having locking arrangement,Disconnecting links, complete as per IS 3043:1987 for earthing.
Providing and making plate earthing station with 600mm x 600 mm x 3.15 mm Cu plate electrode, 15 mm dia G.I.watering pipe, CI funnel with wiremesh charcoal/coke, salt, all earth work, masonry enclosure with frame,hinged cover plate having locking arrangement,Disconnecting links, complete as required as per IS3043-1987 for earthing.
EARTHING STRIPS & CABLES
Supply, Laying, Testing and commissioning of copper/GI Strips/wire for interconnecting the earthing stations ,panels,DBs etc. of the following sizes in built up trenches /surface/wall/ground complete with holes & fixing,jointing / terminating accessories as per specifications & drawing as required. (Quantity shall be paid as per the actual measurement as executed, however direct measurement shall not excced the quantity indicated in drawing approved .
Note-1: In case of non availability of any of the sizes mentioned above, next higher size available in market shall be provided at the same rate.
Note-2: No additional payment will be made for providing Main Earth Terminals (made out of GI/Cu strips from within the above sizes). The METs will required to be fixed on walls as required and will be required to be provided with 12/16/20mm holes for connections of individual equipments including of other contractors'.
Supply, Laying, Testing and commissioning of unarmoured, stranded copper conductor, FRLS grade green coloured cables of following sizes for earthing, including termination of the same by copper lugs at both ends. Note : Item have been considered for S&T clean earth requirement.
TOTAL E.07 - PROTECTIVE EARTHING
Providing and fixing Lightning Conductor Finials made of 25 mm dia 300 mm long GI tube having a single prong at the top with 85 mm dia 6 mm thick GI base plate, fixing accessories and clamping with down conductor as per specifications & drawing complete as required.
Supplying and laying of the GI horizontal & Vertical conductor of following sizes on surface/wall / parapet/ shaft complete with joints, bimetallic connectors, testing links & other fixing accessories and clamping/ connection with earth terminations as per specifications & drawing as required
25 x 3 mm thick GI tape
32 x 6 mm thick GI tape
25 x 6 mm thick GI tape
Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125 mm long with 4 Nos. GI bolts, nuts, check nuts and spring washers complete as required.
Providing and laying of 40 mm dia minimum 3.5 meter long medium class GI pipe. CI funnel with 20 gauge GI wire mesh, masonry chamber 400 x 400 mm with concrete base. GI cover with frame, painted with bitumastic paint and packing with mixtures of charcoal and common salt around plate electrode including digging of pit and suck gilling. GI pipe electrode to be cut tapered at the bottom and provided with holes of 12 mm dia drilled no less than 75 mm from each other upto 2 meter length from bottom
Supply, installation, testing & commissioning of air craft warning lights complete with non flickering type lights similar to GEC model ZH 752 or WIPRO model no. WAN 20001 or equivalent including lamps, mounting bracket, earthing, painting complete with accessories to automatically switch off lights. (Note:Point wiring shall be done under other Item)
TOATL E.08 LIGHTNING PROTECTION
Supply installation, laying, testing & commissioning of the following rating(Amps) totally enclosed, dust and vermin proof Low impedance compact sandwich bus duct inline with Technical specification.
Ingress protection IP 55
Indoor mounts
EC Grade Aluminium bus bar
Operation at 415 Volt 3 phase 50 Hz system
Insulation voltage 1000 volts
Fault withstand 50 kA symmetrical for 1 second
The bus duct shall be complete with all required accessories like clamps, end covers, thrust pads, flexible connections etc. as required and including wall/ceiling mounting brackets/suspenders and including the cost of expansion joints complete as per specifications, as required and as below and suitable for operation at 415 volt 3 phase 50 Hz system.
Supply installation, testing & commissioning of copper flexible end termination/ flange joints as per sketch enclosed and suitable for bus duct connections from Top/ Bottom of switchgear panels/ equipments and of the following current ratings compatible with the bus ducts as per Item 1 above complete as required.
TOTAL E.09 - COMPACT SANDWICH TYPE BUS DUCT
Design, Manufacture & Supply , installation Testing and commissioning( including Integrated Testing with all system) of Silent DG set (Radiator cooled - cooling system designed for 50°C ambient of following aggregate capacity / rating. Comprising of Diesel Engines coupled to alternator both mounted on common base frame suitable for 3- phase, 415 volts 50 Hz 1500 RPM, Standby power rated output with other standard accessories i.e. Fule tank (990 Litres) with necessary medium class M.S. fule piping (25 mm size) with necessary fittings from DG set to Fule Tank, automotive batteries with leads as per manufacturer recomendations. DG sets along with AMF Panels shall be sutible for auto starting & auto synchronising with auto load sharing and remort monitoring & control arrangement compatible with the existing electrical system as per particular specifications complete as required.
Suitable number of silencers per DG set along with the insulation / aluminium cladding for sound attenuations as per specifications.
Supply of suitable rubber mat in front and back of DG control panel ( AMF panel) isolation panel as per latest standards (is:15652:2006) ammended upto date.
Detailed Maintenance & Operation manuals to be supplied after 3 months of Date of vendor approval of DG sets complete as per specifications.
Power Cableing / Control wiring, its termination inside the DG set from atternator to the DG isolation panel if any will be on part of the DG set contractor ( no separate measurements will be made).
Power Cables from the DG isolation Panel to the DG power Panel ( in scope of E&M contractor) shall be supplied and laid by E&M contractor. Necessary interfacing for the same with E&M contractor shall be done by DG set contractor for evacuation of 100 % of output power . Nothing extra shall be payable for the same. However, control cabling from DG set and its load management cum synchronising Panel with DG Power panel shall be in the scope of DG set contractor.
Deleted
Exhaust System
Supply, installation of following sizes of MS Piping for Exhaust system as per IS: 3589 and 1239 (part-I) including providing suitable bends, reducers etc.
Supply, installation, testing and commissioning of 75 mm thick Rockwool LRB mattress insulation (of 150 Kg/M³ density) over the exhaust pipes of following diameter including cladding with aluminium sheet of 24 SWG and covering from outside complete as required suitable for DG exhaust pipe temp upto 450°C etc.
Supply & fixing of miscellaneous structural support for horizontal / vertical exhaust pipe including fabrication, hardwares and painting as per requirement
Portable Oil Filling pump Electrical Type necessary to deliver the oil upto height of 10 mtrs.
Providing & fixing of pre fabricated 22SWG GI sheet ducting (120 gsm galvanisation) for hot air discharge / supply air intake complete including support , bends, flange etc. as required.
TOTAL E.12 - DG SET
Design, manufacture, supply, installation, testing and commissioning of Electric Overhead Travelling Cranes with Gantry rail and Downshop leads to be installed in the Workshop bay, Inspection bay and other maintenance buildings like Emergency Train Unit (ETU) building. The location of cranes in the various buildings is shown in drawings complete as per below (There shall be one Downshop lead of adequate capacity for 2 cranes)
TOTAL E.11 EOT CRANES
TOTAL ELECTRICAL (E.01 TO E.11)
Supply, installation, testing and commissioning of 8 Loop rest features shall be as per specfication.
Supply, installation, testing and commissioning of Repeater panel with Mimic Panel including the cost of mounting accessories complete as per specifications and as required
Supply, installation, testing and commissioning of the following signal initiating devices complete with galvanised steel back box, base detector, etc. complete as specified, required and as approved.
Heat -cum-smoke detectors(combined type full sensor detectors) with blinking LED and base.
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required.
Break Glass Unit / Manual Call Box
Response Indicator
Hooter cum speaker with 4watt speaker and Line Matching Transformer of minimum 100 dB at 10 M distance.
Supply, installation, testing and commissioning of strobes for visual indication as required and as approved.
Supply, installation, testing and commissioning of Monitor Modules including the cost of mounting accessories complete as per specifications and as required.
Supply, installation, testing and commissioning of Fault Isolator Modules including the cost of mounting accessories complete as per specifications and complete as required.
Supply, installation, testing and commissioning of Control Modules , Relay Module including the cost of mounting accessories complete as per specifications and as required.
Supply, installation, testing and commissioning of wall or ceiling mounted 240 Volt AC illuminated double sided pictorial exit signs provided with appropriate direction arrow painted in green on white with an 11W CFL Lamp including the cost of in-built rechargeable batteries with charger suitable for 90 minute operation and including the cost of accessories for surface/ recessed or ceiling suspended mounting complete as required.
Supply laying and testing of armoured Fire Alarm read cable having standard (class 2), Non compacted circular plain FS 1100V ,Heat barrier glass MFc a tape lapped over conductor.,Extructed XLAPE insulated.Overall shealded with alluminium tape along with ATC orian Wire.cables confirming to specification IS 10096part 1, circuit intigrity test shall be as per IEC : 60331
Supplying, Laying, Termination, Testing &Commisioning of Fire Survival Cables (confirming to BS: 7846 and Section E02, 35 of M & W specifications for perfomance requirements of Fire Survival Cables) armoured, 1 pair 2.5 sq.mm, screened / shielded, Copper conductor (one pair shielded and one pair unshielded) cable or Mineral Insulated cable complying the CWZ category.
Supplying, Laying, Termination, Testing &Commisioning of Fire Survival Cables (confirming to BS: 7846 and Section E02, 35 of M & W specifications for perfomance requirements of Fire Survival Cables) armoured, 1 twisted pair 1.5 sq.mm, screened / shielded copper conductor cable or Mineral Insulated cable complying the CWZ category for looping of detection units etc.
Supplying, installing, testing and commissioning of following sizes 16 guage GI conduits recessed/surface as required including clamps, hardwares etc required for conduiting arrangement complete as per specifications. (Quoted price shall include GI flexible conduits to connect from ceiling to false ceiling)
Supply, laying, testing and commissioning of 4 pair 2.5 sqmm screened copper armoured cable in existing cable trays complete as required.
Supplying , laying , testing and commissioning of 6 core 2.5 sqmm copper armoured cable for outdoor use complete with providing sand cushioning and brick protection etc.
Supplying, laying, testing and commissioning of 50 core 1.5 sqmm copper conductor armoured cable for outdoor use complete with providing sand cushioning and brick protection etc.
Supply installation testing and commissioning of two way Talk Back handsets to initiate audio interface complete as required.
Supply installation testing and commissioning of addressable analogue Talk Back jacks with face plates for Fireman's Handsets to initiate audio conversation with Main Fire Alarm Panel including the cost of mounting accessories complete as per specifications and as required.
PUBLIC ADDRESSING SYSTEM - FOR FIRE
Supplying, installing, testing and commissioning of Public Address System complete as required and with the following:
TOTAL SUM OF F.01
Supplying, laying, jointing, testing and comissioning the following sizes of MS class `C' (heavy class) pipes conforming to IS:1239 with accessories like fittings including tees, elbows, reducers, flanges, rubber gaskets, GI nuts, bolts and washers and providing protection to embedded MS pipes and fittings by applying pyp kote primer (@ 100 gm/sqm) thereafter wrapping 4 mm thick pyp kote (AW 4 mm) protection coating by thermo fusion process. Overlap shall be maintained at 15 mm. The application process shall be strictly according to manufacturer’s specification, inclusing necessary excavation and refilling as required. (For under ground works)
80 mm dia
100 mm dia
150 mm dia
Supply, fabrication & laying Class C heavy grade IS marked mild steel piping conforming to IS 1239 and IS 3589 complete with M.S. fittings, pipe supports, clamps, painting of two coats of red enamel etc. and as defined in technical specficiation.
25 mm dia
32 mm dia
40 mm dia
50 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
Providing & fixing stainless steel fire hydrant single 63 mm landing valve inlet, SS, spindle controlled 63 mm dia female instantaneous outlet type. SS coupling, blank cap, chain, twist release type lug & all accessories Conforming to IS standards & Technical specification. Including flanged tapping from wet rise complete as required.
Providing & fixing controlled RRL fire hose pipe (as per IS:636) of 63 mm dia and 15 meter length. Hose shall be complete with ISI marked S.S male & female coupling (IS:903) bound & as per technical specification.
Providing and Fixing stainless steel 63 mm dia instantaneous pattern branch short pipe, 20 mm dia nozzle conforming to IS 903, suitable for inter connection to hose pipe coupling complete as required.
Providing and fixing dial type pressure gauge with isolation cock and pipe.
Dial diameter 100 mm caliberation 0-15 kg or as required.
Providing and fixing standard SS-316 Draw Out connection conforming to relevant standards for installation at Main Fire Water Tank. 100 mm dia. Stainless Steel (SS-316) fire brigade draw out collecting head with 63 mm diameter instantaneous male draw out arranged at a suitable point at street level. This draw out shall be connected to galvanized iron pipe of 100 mm diameter with foot valve arrangement in the tank for Fire Brigade.
Supply, installation, testing and commissioning fire brigade connection with 4 way 63mm valves inlets, stand post and 150 mm MS pipe for mounting the stand post etc. as specified all complete as approved on tank. Note: The drawings of the proposed arrangement shall be provided by the contractor for approval of employer's representative.
Supply, installation, testing and commissioning Siamese connection with 4-way 63-mm outlets with non-return valve and butterfly valve etc. complete as required at road level cabinets. Note: The drawings of the proposed arrangement shall be provided by the contractor for approval of employer's representative.
Providing & fixing Stainless steel cabinet (to enclose FB connection,draw off connection & for external hydrants) fabricated from 16 g sheet with full front glass door and locking arrangement duly painted with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade and suitably mounted on a raised masonry platform as required (Approx 0.75m x 0.6m x 0.25m)
Providing & fixing single acting Air release valve with brass gate valve, flanges/ union, suitable for wet riser system with all necessary connections.
Providing and fixing Gate Valves of the following sizes (conforming to BS: 5154 and Section E 30 of the M & W Specifications) having Bronze body conforming to BS 1400 with screwed ends suitable for pressure rating of 16 bars.
25mm dia
32mm dia
40 mm dia
Providing and fixing pre fabricated 4 mm thick glass door (with SS frame) of size 2.1 m x 0.9 m with center opening for fire hose cabinet suitabely marked on the outside with the letters "FIRE HOSE" including locking arrangement suitable to accommodate 1 no Hydrant landing valves, 1no fire hose reel, 2 nos.15m long 63mm dia hose pipe,1 no branch pipe, 1no. fire man's axe and 2 nos fire extiguishers. All SS work to be in Red P.O. colour over appropriate primer.
Supplying and fixing of stainless steel hose cabinet of size 900 mm x 600 mm x 400 mm made of 2 mm thick with 6mm thick glazed glass doors including necessary locking arrangement suitable to accommodate external hydrants, 2 nos 63mm dia synthetic hose pipe 15 m long, 1 no branch S.S. pipe with 4 nos MS angle ( 40 x 40 x 8 ) supports grouted in floor
Providing & fixing CI butterfly valve of pressure of pressure rating of PN 1.6 . Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required.
Providing & fixing dual plate CI wafer type Double Plate check valve tested to a pressure of 16 Kg/sqcm. Including rubber gasket, flanges, union, nuts, bolts, washers & painting complete as required.
65 mm dia
80 mm dia
150 mm dia
Designing, providing and fixing Orifice plate made out of stainless steel plate (thickness as per specification) for 80/100/150 mm dia. pipe to reduce pressure upto 3.5 Kg/sqcm complete in all respects.
Providing and fixing standard firemans axe with heavy rubber handle.
Providing & fixing brass quartzoid sprinklers (UL approved) of 15 mm dia size, suitable for sustaining the pressure on the seat & water hammer effect. The type & temperature rating shall be as follows :
Providing, fixing, testing and commissioning of UL listed Pendant / Upright type Sprinkler Head rated at 68 degree centigrade
Providing and fixing inspector's test assembly complete with test value, sight glass sectional drain valve union with corrosion resistant orifice all complete
Providing and fixing installation valve with turbine type automatic alarm to be connected with control valve drain and test valve as per manufacturer's design.
150 mm dia.
Providing and fixing UL listed Flow Switch of 80 / 100 / 150 mm dia on Header complete with flexible full bore paddle, U clamp and NO / NC contact terminals
Supply, installation, testing and commissioning of electrically driven multistage, single outlet high pressure centrifugal type fire hydrant /sprinkler pump, suitable for automatic operation consisting of the following:
Common base plate for (a) and (b) from M.S. Channel for required size.
Common base plate for (a) and (b) from M.S. Channel for required size.
Vertical centrifugal pump, suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C supply. The installation shall be complete with Flexible coupling and coupling guard, complete as required.
The pump casing shall be CI, shaft shall be SS & impeller/ shaft sleeve/casing wearing ring shall be bronze. The pump shall be provided with mechanical seal The system shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side.
Squirrel cage induction motor TEFC type for operation on 415 V, 3 phase 50 Hz AC supply for the above pump with a synchronous speed of 2900 RPM as required.
Common base plate for (a) and (b) from M.S. channel as required size.
For pump defined above & of duty as follows :
Flow : 180 LPM
Head : 70/88/90 MTRS
Providing, fixing, testing and commissioning of precharged air vessel (size 450 mm dia & 2000 mm height) for pressurization of hydrant / sprinkler system complete with adequate pressure switches (as per design/requirement) with valves to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, 100 mm dia inlet with isolating valve duly painted from inside and outside complete as required.
Deleted
Providing and fixing Cast Iron Double Flanged `Y' Type Stainers of the following sizes with nuts, bolts, gaskets etc.
200 mm dia
80 mm dia
Supply and installation of stainless steel expansion bellow
200mm dia
150mm dia
80mm dia
65mm dia
Providing and fixing carbon-di-oxide type fire extinguishers consisting of welded M.S. cylinderical body, squeeze lever discharge valve fitted with pressure indicating guage internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge.
Capacity 4.5 Kg.
Providing and fixing mechanical foam type fire extingushers consisting of welded M.S. trolley mounted cylindrical body, squeeze lever discharge valve fitted with pressure discharge hose, discharge nozzle, trolley etc., ISI marked as per IS:13386 finished externally with red enamel paint.
Capacity 50 lit (D.G.Room)
Providing and fixing carbon-di-oxide fire extingushers trolley mounted with all accessories internal discharge tube,high pressure discharge hose,discharge nozzle, ISI marked as per IS:2878 finished externally with red enamel paint.
Capacity 22.5 kg.
Providing and fixing ABC Powder type fire extinguishers consisting of welded M.S. cylinderical body, squeeze lever discharge valve fitted with pressure indicating guage internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge.
Capacity 6.0/5.0 Kg.
Providing and fixing fire extinguisher water type of capacity 9 litre with internal plastic lining and IS marked as per IS 940 with gun metal cap, CO2 cartridge and initial refill.
The rate shall include supply and fixing set of 4 fire buckets capacity 9liters fabricated from 24 gauge MS sheet brackets and stand for 4 buckets complete in all respects including filling of sand. These 4 buckets alongwith all accessories and stand etc shall constitute one set
TOTAL SUM OF F.02
Supply, fixing, testing and commissioning of Automatic linear pneumatic Tube Detection based Clean agent System for Electrical Panels (Fire Detection Tube Panel Protection System), consisting of the following components.
10 LB CAPACITY Clean agent system complete with all necessary gas ,fitting ,support ,and accessories,connected with valve.
5 LB CAPACITY Clean agent system complete with all necessary gas ,fitting ,support ,and accessories,connected with valve.
End of line adaptor
Pressure Switch
Flexible Polymer Detection Tube with all necessary fittings & supports.
Master Control Unit for connecting each system with electronic hooters and productivity input to Scada /Fire Alarm system including all necessaries +electrical wiring to make each entire system functional
Note: The items indicated above are notable items. The vendor to include all allied and implid items in required quantity at no extra cost.
TOTAL SUM OF F.03
From 20 grams upto 100 grams
Above 100 grams upto 500 grams
Above 500 grams upto 1200 grams
Above 1200 grams
Supply, installation, testing and commissioning of Thermal actuation bulb suitable for mounting at item 3.1 above and actuation temerature of above 90 deg C
Note: Only 240 V AC UPS power supply shall be provided to the release control panel, all other accessories are inclusive in the above item
TOTAL OF MISC FIRE SUPRESSION ITEMS (AEROSOL BASED)
TOTAL SUM OF F.01+F.02+F.03
VENTILATION & AIR CONDITIONING ( VAC) WORKS
Supply, Installation, testing and commissioning of Air Cooled Variable Refrigerant Volume/Variable Refrigerant Flow System suitable for R410A and 415 ± 10% , 50 Hz, AC supply. The unit shall consist of indoor units and external condensing units and other accessories as listed below complete in all respects. The unit shall be fully charged with gas and oil.
Outdoor Unit: Supply, installation, testing and commissioning of Modular type outdoor condensing units equipped with highly efficient scroll/hermetic type DC twin rotary compressors with invertor technology, special acryl precoated heat exchanger,low noise condenser fan with motor, auto check function for errors in display panel, auto address setting, as per specifications and capacities as mentioned below.
The units shall be complete with necessary mounting frames
Capacity shall be as under :
Chilled water 'In' : 15 °C
Chilled water 'Out' : 8 °C
Chiller FF (MKS) : 0.000089 m² oC/W
Minimum COP (At AHRI/Eurovent conditions) 3.0
Supply, installation, tesing and commissioning of ceiling mounted FCU type (Low/Medium/High Static) Metallic body indoor units each complete with coil, pre-filter, etc. including necessary steel supporting structure for wall mounting The units casing shall be of steel construction and 220 volt, 1 phase, 50 Hz, AC supply. (CFM shall be as per the approved design) including valve package and thermostat
The capacities shall be as follows:
Supply, installation, testing and commissioning of Centralized Remote controller with scheduler for operation of indoor units.
Supply, installation, testing and commissioning of Imported fittings Y-joints, distributor and headers for all Indoor units as per layout drawings.
Scheduled Timer: Supply, installation, testing and commissioning of Scheduled Timer.
VRF 4 WAY CASSETTE UNITS : Supply, installation, testing and commissioning of 4 -Way Cassette Type units each complete with coil, pre-filter,pump, corded remote controller etc. The units casing shall be of steel construction and 220 volt, 1 phase, 50 Hz, AC supply all as per specifications. CFM shall be
The capacities shall be as follows:
VRF Hi-WALL UNITS : Supply, Installation, Testing and Commisioning of indoor units complete with centrifugal blower, cooling coil (min 3/4 rows for ductable splits), air filter of efficiency 80% down to 20 microns-washable filter, & insulated drain pan all as per specifications. Each unit shall be supplied with Fire retardent Flexible connection at supply. The unit shall be supplied with min 2.0 Rmt FRLS Power cable & 3 Pin Top 6 Amp rating. Each Indoor units should have Cordless Remote Controller as a standard accessory.
The capacities shall be as follows:
Notes:
Refrigerant Piping: Supply,installation,testing and commissioning of Interconnecting refrigerant pipe work with (19mm/13mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping should be laid on Galvanised/Powder Coated tray supported by Galvanised M S Hangers & Clamps.
41.3 mm O.D. (Outer dia) (insulation : 19 mm)
34.9 mm O.D. (Outer dia) (insulation : 19 mm)
28.6 mm O.D. (Outer dia) (insulation : 19 mm)
25.4 mm O.D. (Outer dia) (insulation : 19 mm)
22.2 mm O.D. (Outer dia) (insulation : 19 mm)
19.1 mm O.D. (Outer dia) (insulation : 13 mm)
15.9 mm O.D. (Outer dia) (insulation : 13 mm)
12.7 mm O.D. (Outer dia) (insulation : 13 mm)
9.5 mm O.D. (Outer dia) (insulation : 13 mm)
6.4 mm O.D. (Outer dia) (insulation : 13 mm)
Providing & fixing control cum transmission FR wire / FRLSH Control Cabling of 2 core x 1.5 sqmm copper in GI conduits between indoor and out door unit & indoor unit & its remote controller.
Split Unit: Supplying, installation, commissioning and testing of Metallic body Air Cooled Split type wall mounted 5 Star Energy rating Air conditioners with evaporating unit comprising of cooling coil, blower with motor and condensing unit comprising hermetically sealed rotory compressor, condenser coil, propeller fan. Unit shall be with metallic body & complete with controls, interconnecting copper refrigerant piping with insulation, electrical cabling etc. (15m length included) between evaporative and condensing unit, refrigerant gas and oil. The unit shall be suitable for operating on 220 ± 6% volt 1, phase 50 cycle AC supply. The units shall be suitable for corded remote operation. The refrigerant piping & cabling shall run in PVC sleeve. Quoted price shall include cost of : Steel supporting structure for outdoor units suitable for wall mounting / floor mounting etc.Voltage stabiliser also to be provided with split AC.
Condensate Drain Piping:: Providing, fixing and testing GI Class B drain piping for condensate from unit to nearest suitable drain system as per site conditions as per instructed at site engineer complete with all required fittings and providing clean out plug at suitable location for the pipe when required complete with 6mm thick elastomeric nitrile rubber insulation over GI pipe:
32mm Dia.
25mm Dia.
Chilled Water Piping
MS C class Chilled water piping, Y-Strainer, Valves, Expansion Tank etc. complete with companion flanges, nuts, bolts, gas kits fittings support etc. as required and as per specifications and drawings Duly Insulated with sections/roll of rockwool/fibre glass/------ of thickness as per specifications.
Piping Insulation
Underground Piping Insulation Thickness(mm)
Over Ground Piping Insulation Thickness(mm)
Butterfly Valves/Gate Valves
Butterfly valves Insulation Thickness(mm)
Balancing(Double Regulating Valve) Insulation Thickness(mm)
Non-Return Valve Insulation Thickness(mm)
Y-Strainer Insulation Thickness(mm)
Motorised Butterfly Valves
Motorised butterfly valves complete with actuator as per specifications & drawings.
Pressure Independent Control Valve for FCU
Pressure Independent Control Valve for FCU
For following pipe size Insulation thickness
Pressure Gauges with nipple, elbow and ball valve including of syphon & lock.
Thermometers
Flow Switches
Differential Pressure Switch
Air & dirt Separators & Vacuum Degasser as per specifications For Chiller Plant
Expansion Tank
Closed type Expansion Tank of size for operating pressure up to 10 bars as per specifications.
1000 Ltrs. Capacity
500 Ltrs. Capacity
Flexible Couplings:
TOTAL OF V.01
Supply, installation, testing and commissioning of following equipment.
Supply, installation, testing and commissioning of Propeller type fan complete with motor suitable for 220±6% volt, 1 phase, 50 Hz AC supply, mounting frames and louvers.
Size 610 mm dia - 900 RPM
Size 450 mm dia - 1400 RPM
Size 380 mm dia - 1400 RPM
Size 380 mm dia - 900 RPM
Size 300 mm dia - 900 RPM
Size 225 mm dia - 1400 RPM
Axial Flow Fans: Supply, Installation, Testing and Commissioning of axial flow fans for the following capacity. Fan shall be supplied with GI gravity louvers, bird screen and fan guard.
17000 CMH - 25 mm WG St Pr.
6800 CMH - 20 mm WG St Pr.
5440 CMH - 20 mm WG St Pr.
2500 CMH - 15 mm WG St Pr.
1200 CMH - 15 mm WG St Pr.
936 CMH - 15 mm WG St Pr.
Supplying, Installing, Testing and Commissioning of Tube Axial Flow fans with back draft gravity dampers, adjustable pitch blade, GSS/MS casing, cast aluminum alloy impeller complete with TEFC Sq. cage induction motor with class 'F' insulation , 1450 RPM, suitable for 415 volts +/- 10%, 50 Hz+/- 3%, three phase AC supply with support, mountings and flexible connection etc. & of following capacity.
13500 CFM (20 mm static pressure)
7000 CFM (20 mm static pressure)
INLINE FAN: Supply, installation, testing and commissioning of ceiling suspended Inline fans complete with Louvers,bird screen,speed regulator, rain guard, 5m length copper cable, earthing wire all compete as required of following capacities and shop drawing mentioned.
850CFM ,15mm St.Pr.
1700CFM ,15mm St.Pr.
Note:- All inline fans should be single phase supply with 3 speed regulators etc.
Supply , Installation testing & Commissioning of Air Curtain 1200mm width & door height 7 to 8Ft .Velocity 20-22 MPS
Supply, installation, testing and commissioning of synthetic fill pad type air washer at 500 FPM velocity across pads giving 90% adiabatic saturation efficiency, DIDW Class-I backward curved centrifugal fan with TEFC weather proof, High efficiency motor of IP:55 protection suitable for 415 +10% Volts, 3 phase, 50 cycles power supply, mounted on a common base , multi sleeve pulleys for fan and fan motor. The fan capacity shall be based on outlet velocity not exceeding 2000 FPM, complete with 8" thick celdek fill, 3mm thick FRP steel reinforced tank, water pump 2 Nos. (1+1), cover pipe, distribution pipe, distribution pan, filters at air inlet, water piping, make up water with ball valve, drain and overflow connection, all housed in double skin casing mounted on vibration isolators complete in all respects as per specifications.
8000 CFM with 50mm Static Pressure
18500 CFM with 50mm Static Pressure
Supplying, Installing, Testing and Commissioning of Wet Scrubber . complete with fan, double skin casing, FRP coated steel tank, DIDW centrifugal backward curved fan with V belt drive motor monoblock pumps complete with all fittings as per specification. Scrubber duct shall be in 18 G
Capacity 4500 CFM static pressure 65mm blower motor
Capacity 10500 CFM static pressure 65mm blower motor
TOTAL OF V.02
Supplying, fabricating, installing and testing of factory fabricated G.I. Sheet metal ducts with flanges complete with supports, vanes, dampers, links, levers and quadrants etc. as per specifications and drawings. The rates shall include all materials of the duct and labour for suspension and supporting arrangement for plenums, ducts, complete with fire retardant flexible connection as required and specifications.
0.63 MM (24 Gauge)
0.80 MM (22 Gauge)
1.00 MM (20 Gauge)
1.25 MM (18 Gauge)
Grilles and Dampers
Providing, fixing, testing and commissioning of powder coated extruded aluminum sections grills/diffusers
Exhaust air with dampers
Exhaust air without damper
Providing and fixing, testing and commissioning of powder coated extruded aluminium section grills/diffusers with dampers for supply air terminal.
Providing and fixing, testing and commissioning of powder coated extruded aluminium section Linear grills/diffusers for supply/ Return air.
Providing, fixing, testing and commissioning of exhaust air/fresh air louvers of powder coated extruded aluminium construction with bird screen, minimum 80 mm deep.
Providing, fixing, testing and commissioning of duct/ wall mounted MS Fire dampers suitable with spring return type motor actuator for automatic damper operation and interlocking with Fire Alarm System Panel, 90 minute fire rating, CBRI approved as per specification.
Supplying, installation, testing & commissioning of external thermal insulation on ducts with closed cell cross linked Polythylene (XLPE) foam of density 33 Kg/m3 with 13 mm thick & thermal conductivity not exceeding 0-035 w/mk at an average temp of 40 oc. The material shall be rated as class 1 as per BS 476, part7. the smoke density as per AS-1530.3 shall not exceed 1. the material shall have fire approval fron CBRI, rorkee and no toxicity under flamming & non-flaming condition as per AITM 3.000 (1993). Adhesive used for setting the insulation shall be non-flamable vapour proof. all joints should be sealed with 3mm thick, 50mm wide PE tape & flange to be overlapped with 6" width of same material thickness. finally duct insulated should be strapped by 12mm plastic packing strip at every random meter & conforming to standard specification.
13mm thick closed cell cross linked polyethylene (XLPE) foam with factory laminated Al PE foil for supply air duct.
Supplying and fixing of accoustic lining of duct with fiber glass rigid board of density 48 kg/m3 sealed in fiberglass tissue paper and covered with 0.5mm perforated aluminium sheet & conforming to standard specification. 12mm thick fiber glass rigid board.
TOTAL OF V.03
NOTE-Roof Extractors/Turbo Ventilators shall be included in the scope of PEB Contractor.
TOTAL (V.01 +V.02+V.03)
COMPRESSED AIR SYSTEM
The BOQ specified below include the latest relevent standards, specifications, drawing details and the contractor is required to go through them as referred in tender document while quoting the rates. All the samples/ material intended to be used in the works shall be subject to approval before use as the Employer's representative may opt.
The description as mentioned in BOQ, specifications, special conditions, GCC drawing and the conditions mentioned therein whichever is stringent shall be applicable, acceptable and complied with.
Sub-letting of work by the contractor shall only be permitted in accordance with Special Conditions of Contract.
The items indicating zero quantity can also be operated and variation clause shall be applicable as stipulated in GCC / SCC.
Contractor's shall quote resonably rates against each item of BOQ (both in word and figure)
Supply, installation ,testing and commissioning of air compressor capacity 170 CFM at 10 bar with 30 KW Electrical motor 3 Phase 440 Volts complete with all accessories along with Electrical Control panel, necessary wiring , earthing,reservoir tank of 1500 litres capacity with apropriate inlet and outlet flanges designed for full rated capacity of 2 compressors etc. complete in all respects and as per specifications.
Providing MS pipes conforming to IS 1239 (Class C) complete with all fittings such as elbows, sockets, tees, unions, reducers, flanges,clamps and plugs etc with threading, jointing and making connections including cutting hole in wall/floor/slab and making good the same with cement concrete 1:2:4 complete in all respect as per specifications including painting pipe and fittings with two or more coat of synthetic enamel paint of approved quality as per pipe colour over a coat of red oxide primer outside with 1 coat of primer and 2 coats of enamel paint,complete.
100 mm dia nominal bore
80 mm dia nominal bore
65 mm dia nominal bore
25 mm dia nominal bore
20 mm dia nominal bore
15 mm dia nominal bore
Providing M.S. structural work, fabricated from standard sections eg. M.S. rods, angles channels including cutting to size, drilling holes, fixing fastener /insert plates in RCC structural members as directed by the Engineer-in-Charge including cutting and making good the walls and floors (for supports,clamps,M.S. ladders,gratings etc.)
Providing gunmetal ball valve with SS ball & teflon seats and seals inside spindle type tested to 500 psi, complete.
25 mm dia nominal bore
20 mm dia nominal bore
15 mm dia nominal bore
Wafer Type, Cast Steel, Non Return Valves, Suitable for ASA 150 flanges,.
Size 100 mm NB
Size 63 mm NB
Providing cast iron body PN 16, IS: 210 FG 220 and double flange simple operation type butterfly valve conforming to IS: 13095 with SS304 disc and shaft nitnile rubber replaceable seat of the following size complete with bolts, nuts, washers and rubber isertions as per specification.
100 mm dia
65 mm dia
Pressure Gauges, 150 mm Dial, complete with mounting nipple and isolation valve. Range 0 - 10 Kg/Cm Sq.
Auto Drain Assembly, with Solenoid Valve and Timer. Timer should be adjustable between 5 Mins to 120 Mins. Size 15 mm NB.
Providing Filter regulator 1/2" at every droplet after the ball valve suitable for 10 bar pressure.
TOTAL SUM OF M.01
Providing and fixing MS pipes conforming to IS 1239 (Class C) complete with all fittings such as elbows, sockets, fees, unions, reducers, flanges,clamps and plugs etc with threading, jointing and making connections including cutting hole in wall/floor/slab and making good the same with cement concrete 1:2:4 complete in all respect as per specifications including painting pipe and fittings with two or more coat of synthetic enamel paint of approved quality as per pipe colour over a coat of red oxide primer outside with 1 coat of primer and 2 coats of enamel paint, complete.
50 mm dia nominal bore
15 mm dia nominal bore
Providing and fixing M.S. structural work, fabricate from standard sections eg. M.S. rods, angles channels including cutting to size, drilling holes, fixing fastenera/insert plates in RCC structural members as directed by the Engineer-in-Charge including cutting and making good the walls and floors (for supports, clamps, M.S. ladders, gratings etc.)
Providing and fixing gunmetal ball value with SS ball & teflon seats and seals inside spindle type tested to 500 psi, complete.
50 mm dia nominal bore
15 mm dia nominal bore
Pressure Gauges, 150 mm Dial, complete with mounting nipple and isolation valve. Range 0 - 10 Kg/Cm Sq.
Auto Drain Assembly, with Solenoid Valve and Timer. Timer should be adjustable between 5 Mins to 120 Mins. Size 15 mm NB.
Providing and fixing Filter regulator 1/2" at every droplet after the ball valve suitable for 10 bar pressure.
TOTAL SUM OF M.02
Supplying, Installing, testing and commissioning of air compressor capacity 21 CFM at 10 bar with 5.5 KW electrical motor 3 Phase 440 Volts complete with all accessories along with Electrical control panel, necessary wiring, earthing with Filter regulator and PU tube (10 meter) along with cleaning air gun etc. complete in all respects as per specifications & as required nothing extra is payable.
Providing and fixing MS pipes (Not more then 20 meter) conforming to IS 1239 (Class C) complete with all fittings such as elbows, sockets, fees, unions, reducers, flanges,clamps and plugs etc with threading, jointing and making connections including cutting hole in wall/floor/slab and making good the same with cement concrete 1:2:4 complete in all respect as per specifications including painting pipe and fittings with two or more coat of synthetic enamel paint of approved quality as per pipe colour over a coat of red oxide primer outside with 1 coat of primer and 2 coats of enamel paint, complete.
TOTAL SUM OF M.03
TOTAL OF M.01+M.02+M.03
Supply, Installation, Testing & Commissioning of submersible sump pumps in S.S-316. for dewatering with 40 mm thick solid handling capacity suitable for operation on 415 ± 10% V, 50 Hz A/C power supply & lifting arrangement.
Set of Two Pumps for Drainage (1W+1SB)
Capacity 180 LPM each
Head 8-10 Mts
Supply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with body, impeller, Casing, shall made of SS 316 and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+10% Volts, 3 phase 50 Hz A.C. Supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating under foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.
Domestic Water Transfer Pumps to O.H. Tank at Water Supply Pump Room
Set of two Pumps ( 1Working +1Stand hy)
Capacity - 5.0 LPS
Head - 50 M
Irrigation Pumps at STP Pump Room
Set of two Pumps ( 1Working +1Stand by)
Capacity - 4.0 LPS
Head 40 M.
Domestic Water Transfer Pumps to Auto Coach Washing plant
Set of two Pumps ( 1Working +1Stand by)
Capacity - 7.0 LPS
Head - 40 M
Raw Water Transfer Pumps to Buildings from Pump Room
Set of two Pumps ( 1Working +1Stand by)
Capacity - 5.0 LPS
Head - 50 M
Providing and fixing horizontal monoblock pumping set with C.I. body and bronze impeller, shaft of SS-316 and M.S. base & head, mechanical seal, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm M.S. section base plate bolted to cement concrete foundations complete
Filter Feed Pumps at Water Supply Pump Room
Capacity - 5.0 lps
Head - 22 M.
Set of two Pumps ( 1Working +1Stand by)
Supply, Installation, Testing & Commissioning of submersible pump-set as per specification with direct coupled motor rated for 3 phase, 50 Hz 415 ±10% volts. AC supply with the following cluty:
Total head-100 mtr. Approx.)
Flow rate-12000 lt/ hr (Approx)
TOTAL SUM OF P.01
WATER TREATMENT PLANT
Whether explicitly specified or not, the Water Treatment Plant and Pumps specified herein, must conform to the M & W Specifications and Motors must conform to the M & W Specifications, in addition to the description give in respective item of BOQ. BOQ shall be read alongwith technical specifications.
Rates quoted shall be inclusive of all structural supports, clamps etc. as per approved design / specifications.
DUAL MEDIA FILTER
Providing and fixing of mild steel (rubber Lined) pressure vessel confirming to IS:2825 dual media filter complete in all respects as
1) Capacity = 2 Cum / hr
2) Rate of flow = As per Vendor requirement
3) Wall thickness of shell and of dished ends as per IS:2825
4) Initial charge of media.
5) Sample valves
6) Sockets and valve for dosing chemicals.
7) Pressure gauge at inlet and outlet with isolating cocks and supports.
ACTIVATED CARBON FILTER
Providing and fixing of mild steel (rubber Lined) pressure vessel confirming to IS:2825 dual media filter complete in all respects as
1) Capacity = 2 Cum / hr
2) Rate of flow = As per Vendor requirement
3) Wall thickness of shell and of dished ends as per IS:2825
4) Initial charge of media.
5) Sample valves
6) Sockets and valve for dosing chemicals.
7) Pressure gauge at inlet and outlet with isolating cocks and supports.
CHEMICAL DOSING PUMP
Providing , fixing ,Installation and commissioning of chemical dosing pump capacity 6 lph with 100 ltrs capacity chemical tank including suitable length of flexible pipe as per required dia for complete in all respect.
Providing all materials and labour for supplying, Installation, Testing & Commissioning of multi level indicator cum controller,and having the controller equipped with level monitoring system and phase monitoring system for automatic opeartions of various pumps & having multi level 4 nos. visual indications on panel with alarm system and timer including necessary cable and acknowledge facilities as per requirement and all complete as approved providing repeater panel in control room for water level indications in various tanks.
Water tanks(UGT'S & OHT'S)
All above level Controllers / Indicators to be complete with sensors, switches, relays, all wiring from the sensors to the Control Unit, Control Units to Motor Control Centers of the various Pumps and to the various alarm and indicating devices.
Sensors Terminal Units would be in weather proof enclosures (minimmum IP-56).
Cotroller with low voltage relays, stainless steel probes and PVC shroud, wiring from tank top to probe of required length. ( No of probes as required for the function of each controller).
For domestic water transfer to building
To cut off duty pump on low water level in the treated water tank (UGT) and higher water level in the OHT. To start pump at low water level in OHT.
For irrigation STP pump
To cut off duty pump on low water level in the treated water tank (UGT) and higher water level in the OHT. To start pump at low water level in OHT.
For domestic water transfer to auto coach
To cut off duty pump on low water level in the treated water tank (UGT) and higher water level in the OHT. To start pump at low water level in OHT.
For raw water transfer to building
To cut off duty pump on low water level in the raw water tank (UGT) and higher water level in the OHT. To start pump at low water level in OHT.
For filter feed pump.
To cut off duty pump on low water level in the raw water tank (UGT) and higher water level in the treated water tank (UGT).
TOTAL SUM OF P.02
TOTAL OF P.01+P.02
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.31 MB
Vol_02_GCC_SCC.pdf
Tender Documents • 0.95 MB
Vol_08_Geo_Tech_Report.pdf
Tender Documents • 22.43 MB
Vol_01_NIT_ITT_FOT_2.pdf
Tender Documents • 0.78 MB
Vol_07_SHE.pdf
Tender Documents • 6.96 MB
Vol_06_Drawings.pdf
Tender Documents • 31.83 MB
Vol_05_BOQ.pdf
Tender Documents • 0.33 MB
Vol_04_Technical_Specifications.pdf
Tender Documents • 28.71 MB
Vol_03_ER.pdf
Tender Documents • 1.42 MB
BOQ_308232.xls
BOQ • 1.55 MB
Download all tender documents and submit your bid