Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹15.1 L
EMD Value
₹30,000
Closing Date
10 Aug 2023, 12:00 pmClosed
Executive Engineer MHCHD, Srinagar
Executive Engineer MHCHD, Srinagar
Repairs of Central Heating System at Govt. SMHS Hospital Srinagar
2023_PWDJK_222813_2
MHCHD/TS /2023-24/58/e-tendering Dt 21.07.2023
Open Tender
Repair and Maintenance Works
Item Wise
15 days
Govt SMHS Hospital
As Detailed in NIT
4 documents required · 4 mandatory
₹1,000
Executive Engineer MHCHD SGR
₹30,000
11 Aug 2023
21 Jul 2023
10 Aug 2023
21 Jul 2023
10 Aug 2023
21 Jul 2023
Amount
Dismantling of old leaking M.S piping feeding the OT alongwith insulation/ valves etc. and cast iron radiators of different sized (Nos) radiators and piping. The job includes carrying , storing and stacking of serviceable material to place near Boiler house and disposal of unsercible material beyond municipal limits. All tools tackles and transport to be arranged by the contractor/ firm.
Supply, Installation, Testing and Commissioning of Mild steel Class 'C' ERW pipes of following diameters with fittings like tees, elbows, bends, junctions unions, flanges etc. The job encompasses coating the M.S Pipeline with two coats of Paper
Providing & fixing of Thermally bonded polyster fibre based 75 gsm Fire Proof insulation of thickness as mentioned below (Mikron make) covered with chicken mesh and 26 gauge Al. cladding
20 mm (25 mm thk)
25 mm (25 mm thk)
32 mm (25 mm thk)
40 mm (25 mm thk)
50 mm (50 mm thk)
Providing & fixing of insulation for indoor with elestometric nitrile foam 90mm thick ove 20 mm dia pipe
Providing and fixing of Butterfly/ Ball valves as per relevant Is specification with follwoign diamters. The job includes providing and fixing of required nipples, flanges, etc as shall be required at site
Providing and fixing of 20 mm Air Release Valves with isolation valve
Providing & fixing of supports to be fabricated out of ISA 40x40x5mm, 50x50x6mm etc and to be fitted on walls with dash fasteners included a coat of printer
Providing and Fittign of ball valves of following dia inlcuding a set of flanges of the required size and other fittings as shall be requried. The job includes cutting the existing pipe line and fitting of the valves. The valves are to be fitted inside OT No. 02 Library of surgical unit at Govt. SMHS Hospital, Srinagar
25 mm ball valve
20 mm ball valve
15 mm ball valve
Replacement of damaged hot water radiators installed in different wards/ sections/ corridors of Govt. SMHS Hospital by way of dimantelling of damaged and not functional radiators followed by Supply, Installation, Testing and Commissioning of Radiators of different capacities complete with inlet outlet valves, air purge valves, flanges, pipples etc and M.S Piping with fittings (wherever required). The job also includes resizing of the existing connections (whereever required)
1000 Kcal/hr
1500 Kcal/hr
2000 Kcal/hr-Double Panel
2500 Kcal/hr-Double Panel
3000 Kcal/hr-Tripple Panel
Providing & Ftting of ball valves of following dia inlcuding a set of flangees of the required size and other fittings as shall be required. The job includes cutting the existing pipe line and fittings of the valves. The valves are to be fitted inside OT No. 02 & Library of Syurgical Unit at Govt. SMHS Hospital Srinagar
25 mm ball valve
20 mm ball valve
15 mm ball valve
Repairs to be damaged hot water radiators/ wall mounted fan coil units (assorted sizes) by way of replacement of valves, replacement of supporting clips etc. after proper cleaing and descaling of the radiators / FCUs. The radiators / FCUs are to be tested for smooth functioning
Complete testing of the hot water piping system including the radiators / FCUs installed in the SMHS Hospital to detect the leakages and rectifying of the same for smooth functioning of the Central Heating System. The job includes rplacing of the leaking/ damged fittings/ valve etc as shall be detected. The job also includes cleaning of cocked piping / radiators wherever required. In order to arrest the leakages found in the system. The damges caused in walls/ celing etc are to be made good as per the directions of the Charge Engineer
GOOD LUCK TRADERS
Elevate Engineers
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .