| Sl No | Description | Qty | Unit | Ravinder Kumar Sahore L1 | SANJEEV THAKUR L2 | ANIL KUMAR VASHISHT(GOVT, CONTRACTOR) L3 |
|---|---|---|---|---|---|---|
| 1.00 | CIVIL WORK
Excavation in foundation, trenches in earth work in all kinds of soil,such as pick work,jumper work.blasting work in hard rock and soft rock and in saturated soil etc. i/c all leads and lifts , stacking the excavated soil not more than 3 mtrs. clear form the edge of excavation and then returning the stacked soil in 15 cm layers when required into plinth, sides of foundation etc. consolidating each deposited layers by ramming and watering and then disposing of all surplus excavated earth as per the direction of the Engineer-in-Charge. | 206.95 | Cum | - | - | - |
| 2.00 | Providing and laying cement concrete 1: 6: 12 ( 1 cement : 6 graded stone aggregate 40 mm nominal size) and curing complete excluding the cost of form work in foundation and plinth in all leads and lifts and as per the direction of the Engineer-in-Charge. | 48.65 | Cum | - | - | - |
| 3.00 | Ist class brick work using common burnt clay building bricks in foundation and plinth in cement mortor 1:6 ( 1 cement: 6 sand ) in all leads and lifts as per the direction of the Engineer-in-Charge. | 157.21 | Cum | - | - | - |
| 4.00 | Ist class brick work using common burnt clay building bricks in superstructure in cement mortor 1:6 (1 cement :6 sand) in all lead and lifts as per the direction of the Engineer-in-Charge. | 42.04 | Cum | - | - | - |
| 5.00 | Providing and laying Damp proof course 38 mm thick cement concrete 1:2:4 (1 Cement : 2 sand:4 graded stone aggregate 2.50 mm nominal size ) in all leads and lifts and as per the direction of the Engineer-in -Charge. | 7.25 | Sqmt. | - | - | - |
| 6.00 | Applying a coat of hot bitumen ( Mexphalt 80/100 of equivalent ) using 1.70 Kg/sqmtrs. On damp proof course after cleaning the surface with a piece of cloth lightly soaked with kerosene oil in all leads and lifts | 7.25 | Sqmt. | - | - | - |
| 7.00Providing and fixing pressed steel door frame manufactured from commercial MS sheets of 1.25 mm thickness including hinges jump lock jamb, bead if required angle thrshold of MS angle 50x25 mm or base ite of 1,25 mm presses MS welded or rigidly fixed together by mechanical means, adjustable lugs with split and tails to each jamb including steel butt hinges 2.5 mm thick with guards, lck strike plate and shock as specified and laying a coat of steel | ||||||
| 7.01 | Profile "A" | 161.2 | Rmt. | - | - | - |
| 7.02 | Profile "B" | 35.6 | Rmt. | - | - | - |
| 8.00 | Providing and fixing pannelled glazed and panalled and glazed shuttrs for doors ,windows and clerestory windows including bright finshied /black enemelled iron butt hinges with necessary screws fIst class deodar wood 40 mm thick. 2 nd class deodar wood complete in all respect and as per the direction of the Engineer - in- Charge. | 46.47 | Sqmt. | - | - | - |
Tender Value
₹1.2 Cr
EMD Value
₹1.5 L
Closing Date
26 Dec 2019, 5:00 pmClosed
Executive Engineer IPH Divn No.1 Una HP
Executive Engineer IPH Divn No.1 Una HP
as per NIT
2019_HPIPH_33201_1
No. IDU-I/TA/E-tender/19- 10486-10515 dt 7-12-2019
Open Tender
Civil Works
Item Rate
365 days
Haroli Consty
as per NIT
8 documents required · 8 mandatory
₹1,500
Yes
Executive Engineer IPH Divn No.1 Una HP
₹1.5 L
Yes
29 Jan 2020
7 Dec 2019
27 Dec 2019
7 Dec 2019
26 Dec 2019
7 Dec 2019
7 Dec 2019 - 26 Dec 2019
Amount
CIVIL WORK Excavation in foundation, trenches in earth work in all kinds of soil,such as pick work,jumper work.blasting work in hard rock and soft rock and in saturated soil etc. i/c all leads and lifts , stacking the excavated soil not more than 3 mtrs. clear form the edge of excavation and then returning the stacked soil in 15 cm layers when required into plinth, sides of foundation etc. consolidating each deposited layers by ramming and watering and then disposing of all surplus excavated earth as per the direction of the Engineer-in-Charge.
Providing and laying cement concrete 1: 6: 12 ( 1 cement : 6 graded stone aggregate 40 mm nominal size) and curing complete excluding the cost of form work in foundation and plinth in all leads and lifts and as per the direction of the Engineer-in-Charge.
Ist class brick work using common burnt clay building bricks in foundation and plinth in cement mortor 1:6 ( 1 cement: 6 sand ) in all leads and lifts as per the direction of the Engineer-in-Charge.
Ist class brick work using common burnt clay building bricks in superstructure in cement mortor 1:6 (1 cement :6 sand) in all lead and lifts as per the direction of the Engineer-in-Charge.
Providing and laying Damp proof course 38 mm thick cement concrete 1:2:4 (1 Cement : 2 sand:4 graded stone aggregate 2.50 mm nominal size ) in all leads and lifts and as per the direction of the Engineer-in -Charge.
Applying a coat of hot bitumen ( Mexphalt 80/100 of equivalent ) using 1.70 Kg/sqmtrs. On damp proof course after cleaning the surface with a piece of cloth lightly soaked with kerosene oil in all leads and lifts
Providing and fixing pressed steel door frame manufactured from commercial MS sheets of 1.25 mm thickness including hinges jump lock jamb, bead if required angle thrshold of MS angle 50x25 mm or base ite of 1,25 mm presses MS welded or rigidly fixed together by mechanical means, adjustable lugs with split and tails to each jamb including steel butt hinges 2.5 mm thick with guards, lck strike plate and shock as specified and laying a coat of steel
Profile "A"
Profile "B"
Providing and fixing pannelled glazed and panalled and glazed shuttrs for doors ,windows and clerestory windows including bright finshied /black enemelled iron butt hinges with necessary screws fIst class deodar wood 40 mm thick. 2 nd class deodar wood complete in all respect and as per the direction of the Engineer - in- Charge.
Providing form work with steel plates 3.15 mm thick welded with angle iron in frame 30x30x5mm. so as to give a fair finish including centering, shuttering, struting and propping etc. with wooden battens and ballies, height of propping and centering below supporting floor to ceiling not exceeding 4 mtrs. and removal of the same for in situ-reinforced concrete and plain Concrete work in :-
Flat surfaces such as soffits of suspended floors, roofs, landing and the like Floors etc. upto 200 mm thickness in all leads and lifts and as per the direction of the Engineer-in-Charge.
Beams,cantilever,girders and lintels.Sides and soffits of beams,beam haunchings, cantilevrs, bressumers and lintles not exceeding 1.00 mtr.in depth in all heights from floor.
Providing and laying cement concrete M-20 grade with cement, sand, graded stone aggregate 20 mm nominal size) with minimum and maximum cement contents of 300 Kg/ M3 and 400 Kg/ M3 respectively and maximum water cement ratiio 0.50 as per IS 456-2000 and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in :-
Suspended floors, roofs, landing and shelves and their support balconies, beams, girders, bressumers and cantilevers upto floor to level complete in all respect i/c carriage of materials with in all leads and lifts.
Cement concrete flooring 1:2:4 (1 cement : 2 sand : 4 graded stone aggregate 20 mm nominal size) laid in one layer finished with floting coat of neat cement in all leads and lifts and as per the direction of the Engineer-in-Charge
40 mm thick.
25 mm thick.
Providing mild/tor steel reinforcement of RCC work i/c bending ,binding and placing in position in complete up to floor two level in all leads and lifts and as per the direction of the Engineer-in-Charge.
Half brick work using common burnt clay building bricks in super structure above 1st. floor level in cement mortar 1 : 4 ( 1 cement :4 sand) of 2nd. Class bricks complete in all lead and lifts as per the direction of the Engineer-in-Charge.
Pointing on brick work with cement mortor 1:3 ( 1 cement: : 3 sand ) in all leads and lifts as as per the direction of the Engineer - in- Charge.Cut or weather struck.
6 mm thick cement plaster to ceiling with cement mortar 1:3( 1 cement : 3 sand ) including carriage of material with in all leads and lifts and other incidentals.
15 mm cement plaster in single coat on rough side of brick masonry for interior plastering upto floor two level including arrises, internal rounded angle, chamfers and or rounded angles not exceeding 80 mm in girth and finished even and smooth with cement mortor 1:6 ( 1 cement :6 sand ) in all leads and lifts as per the direction of the Enginner-in-Charge.
Providing and fixing MS grills of required pattern in wooden frame / pressed steel frame with MS flates square / rounds bars 12 mm dia with round headed bolts and nuts of by screws in all leads and lifts and as per the direction of the Engineer - in- Charge Plain grills.
Providing plinth protection 50 mm thick in cement concrete 1:3:6 ( 1 cement :3 sand : 6 graded stone aggregate 20 mm nominal size ) in all lead and lifts as per the direction of the Engineer - in- Charge.
Providing 40x3mm flat iron hold fast 40 cms long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block 30x10x15 cms 1:3:6 ( 1 cement :3 sand : 6 graded stone aggregate 20 mm nominal size ) complete in all respect as per the direction of the Engineer -in- Charge.
P/F MS fan clamps type 1 of 16 mm dia bar bent to shape with hooked ends in RCC slab during laying including painting the exposed portion of roof as per standard design complete in respect .
White washing with lime on undecorated wall surface ( three coats) to give an even shade including throughly brooming the surface to remove all dirt ,dust mortor drops and loose scale of lime wash and other foreign matter complete in in all respect as per the direction of the Engineer-in-Charge.
Finishing wall with water proofing cement paint of approved brand and manufacture and of required shade on undecorated wall surface (two coats) to give an even shade after thoroughly brushing the surface to remove all dirt & remains of loose powdered materials complete in all respect
Providing and fixing sliding door bolts anodized transparent or dyed to required shade and colour with screws etc. complete in all respect 250x16 mm
Providing and fixing tower bolts barrel type anodized transport or dyed to required shade and colour with screws com lete in all respect.
-do- 250x10mm.
-do- 150x10mm.
Providing and fixing aluminium handle anodized transparent or dyed to required shade and colour with screws etc. complete in all respect 100mm
Applying priming coat over new steel and other metal surfaces after and including preparing the surface by throughly cleaning oil grease, dirt,and other foreign metter with ready mixed paint brushing wood primer pink complete in all respect as per the direction of the Engineer-in-Charge.
Painting two coats (excluding priming coat) on new steel and other metal surfaces with enamel paint to give an even shade including cleaning the surface of dirt ,dust and other foreign matter with enamel with enamel paint other than white complete in all respect as per the direction of the Engineer-in-Charge.
Applying priming coat over new wood and wood based surfaces after and including preparing the surface by throughly cleaning oil, greas,dirt,and other foreign metter with ready mixed paint brushing wood primer pink complete in all respect as per the direction of the Engineer-in-Charge.
Painting two coats excluding priming coat on new wood and wood surfaces with enamel paint to give an even shade including cleaning the surface of dirt ,dust and other foreign matter sand papering and stoping complete in all respect as per the direction of the Engineer - in - Charge.
P/F of angle iron door, window, clerestory windows manufactured from MS angle iron section of 50x50x6mm thickness including hinges jamb, lock, jamb, bead and if required angle threshold of mild steel angle 50x25 mm welded or rigidly welded by mechanical means, lungs withsplit end tail to each jamb i/c. steel butt hinges 2.5 mm thick with provision for locking arrangement and shock observer as specified & applying a coat of approved steel primer after pretreatment of furface as directed by the Engineer-in-Charge.
P/F of 1 mm thick MS Sheet garage door with frame of 40x40x6mm angle iron 3.15 mm gusset plates at the junctions and corners, all necessary fitting complete including applying a priming coat of red lead paint using flats 30x5mm for diagonal braces and central cross pieces.
Steel work welded built up sections, trusses and framed work , including cutting , hoisting , fixing in position and applying a priming coat of red lead paint in beams joists channels, angles , tees, flats with connection plates or gratings framed guard bars, ladders,. railling, brackets and similar works.
Providing / fixing vitreous china water closet squatting pan ( Indian type WC pan ) size 580 mm ( Earth work, bed concrete, foot rest and trap to be measured and paid for seperately Orissa pattern.
Providing / fixing of PVC "P" Trap complete in all respect.
Providing / fixing of PVC bend 50 mm dia complete in all respect.
Providing / fixing of PVC waste pipe and ventilating pipes complete in all respect.
110 mm dia
50 mm dia
Fixing of wall ceiling and floor galvanized MS tube (Light) tube fitting and clamps including making good the wall ceiling and floor 15 mm dia complete in all respect.
Providing / fixing of CP brass bib cock with capstan head 15 mm dia complete in all respect.
Providing / fixing of CC Hume pipes each 750 mm dia 1200 mm long required for excavation at site complete in all respect.
P/F 10Ltrs. Capacity PTMT coloured /Poly propytene 10 ltrs capacity (full flush) European standard control low level flushing cistern with fitting 15 mm nominal size brass ball valves with polygthene float. including cutting holes in walls and making good the same and connecting the flush bend with cistern and closet ( Overflow) pipe to be measured and paid for seperately.
Hirmachi colour wash on undecorated wall surfaces (Three coats) to give an even shade including thoroughly brooming the surfaces to remove all dirt,dust, mortar drops and other foreign matter complete in in all respect as per the direction of the Engineer-in-Charge.
Excavation in earth work and filling in 15 cm. layers in foundation & plinths including ramming, watering and consolidating complete in all respect including carriage of materials within all leads and lifts and as per the direction of the Engineer-in-Charge.
Wiring for light/Fan point/Exhaust fan point/call bell point with 1.5 Sq.mm PVC insulated copper conductor cable in surface/recessed PVC conduct at required including carriage of all material within all leads and lifts. Group "C"
Wiring for light/power plug with 2 x 4 Sq.mm PVC insulated copper conductor or single core cable in surface/recessed steel conduit alongwith 1 No. 4 Sqmm dia bare copper wire for loop earthing as required including carriage of materials within all leads and lifts.
Wiring for circuit wiring with 2 x 1.5 Sq.mm PVC insulated copper conductor single core cable in surface/recessed steel conduit as required including carriage of material within all leads and lifts.
Wiring for sub-main wiring with the following size of copper conductor single core cable in surface/recessed steel conduit as required including carriage of materials upto all leads and lifts. 2x6 Sq.mm
Supplying and fixing metal box of 180 x 100 x 60mm deep (Nominal size) on surface/recess with suitable size phonolic leminated sheet cover fixing 3 pim 5/6 amps socket tumber/piano type switch connections painting etc. including carriage of materials within all leads and lifts.
Supplying and fixing backellite batten/angle holder including connection as required.
Providing, installing, testing and commissioning of ceiling fan and regulator including wiring the rod of standard length (upto 30cm) with 1.5 Sqmm PVC insulated copper conductor single core cabe etc. as required sweep type. Cat. A (1200 mm sweep)
Providing, installation, testing and commissioning of prewired flourscent tube fitting complete with ballast, starter and capactors but excluding flourscent tube rod, suitable to operate on 230 volts single phase A.C.supply directly on surface with copper wiring as required including carriage of materials within all leads and lifts tube fixture 1 x 36 watt Box type Category "A".
Supplying and fixing 40Amps to 63 Amps rating 240 Volts "L" series miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required including carriage of material within all leads and lifts. Category- A, 63 Amps.
Supplying and fixing of following way single pole and neutral sheet steel MCB distribution board 240 volts on surface/recessed completed with tinned, copper busher neutral link, earth bar, detachable gland plate inter -connections, including painting, earthing etc. as required Bus bar 8 way.
Supplying and fixing 6Amps to 32 Amps rating, 10 KA breaking capacity 240 volts, C series miniature circuit breaker of following poles in the existing MCB, DB complete with connections testing and commissioning etc. Category "A", single pole.
Earthing with G.I. pipe earth, pipe 4.5 mtrs length, 40mm dia including accessories and providing masonry enclousres with cover plate having locking arrangement and watering pipe etc.( but without charcal coke and salt) complete as required including carriage of materials within all leads and lifts.
Extra using salt and charcoal for pipe earth electrode as required, including carriage of materials within all leads and lifts.
Supplying and laying 6 Sqmm G.I.wire at 0.50 mtr below ground level for conductor earth electrode, including soldering etc. as required including carriage of materials within all leads and lifts.
Providing, fixing & testing Street Light Fixture with CFL of 36 watt, copper ballast, G.I. Pipe bracket, complete in all respects including carriage of materials within all leads and lifts..
PROVIDING AND LAYING OF RISING MAIN Excavation in foundation trenches ( for pipes and pits ) upto all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft / hard rock or chieselling soft/ hard rock where blasting is prohibited, in all lifts including trimming and dressing of sides, levelling of beds to correct grade including, shoring, strutting, planking, timbering and dewatering, wherever required, stacking the useable and unuseable material/ soil separately and after laying, jointing and testing of pipes returing the useable soil in trenches in 15 cm ( Fifteen centimeter ) layers including consolidating of such deposited layer by ramming and watering and then disposing of all surplus excavated soil /un-useable materials as directed within all leads and lifts including restoration of un-metalled surface to its original condition and including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respect within all leads and lifts as per the directions of Engineer-in-Charge.
Providing, laying, jointing and testing in trenches of 200 mm dia.4.80mm thick GMSERW pipe levelled end BIS marked conforming to IS/ISO 3183-2007 Grade L-210/A in a random length of 4 mtr. to 7 mtrs. and capable with standing required test pressures as prescribed in BIS code. The pipes end shall be levelled, suitable for butt welding including cost of manufacturers of all digree, bends, tail pieces, tees and other special manufacturing from parent pipes as applicable to the particular reach and of approved/ specification as per the site condition and cutting of pipe where ever required as per site requirement. The M.S flanges are to be provided 5% of the total joints as per table below confirming to IS 6392-1971 ( latest ammendment ) and welding of flanges with pipes as per IS: 816-1965 with electrode as per IS 814-1967 required Nos. and size of M.S Nuts & Bolts as per IS: 1369-1967 and compressed asbestos fibre jointing gasket sheet not less than 3mm thick as per Is: 2712-1965. The welding of flanges to be done on both faces in two layers to make the joints leak proof and to the entire satsfication of Engineer-in- charge. The laying of pipes should be confirmed to IS: 5822-1994 ( earth work in trenches, MS Flanges and Butt Welded to be measured and paid for separately ). The pipe shall have Zinc coating as per IS: 4736 in factory latest with uptodate ammendments. The pipe shall be coated from both side ( inside ) or outer side with the required thickness and zinc coating as per two coats main above including entire carriage of material in all leads and lifts as per the direction of the Engineer-in-Charge.200 mm dia.4.80mm
Laying, jointing and testing in trenches plain ended GMS pipes (Medium grade) confirming to ISI (1239-2004) specification including commissioning and cost of all fittings i.e. bends, tail pieces, tees & other special manufacturing from parent pipes as applicable to the particular reach & of approved/sepecification as per site condition and cutting of pipes where ever required as per site requirement in respect of following diameters in Rising Main ( The earth work in trenches shall be measured and paid for separately ) including entire carriage of material in all leads and lifts as per the direction of the Engineer-in-Charge. 150 mm dia. (Medium grade)
Providing, Fixing and welding of MS flanges conforming to table as specified below of BIS code 6392-1971( Latest with upto date ammendments) welding of M.S. flanges on ( Two layers on inner face and one layers on outer face of each flange) GMSERW pipes & bends on both ends ( The GMSERW pipe to be measured and paid for separately )The welding of flanges conforming to IS 816-1998 with electrodes as per IS 814-1997, prov.& fixed with nuts, bolts of required size conforming to IS 1364, provide & fixes 3 mm (Minimum) thick compressed asbestos fibre / synthetic rubber gasket conforming relevant BIS Code IS 2712-1965 in trenches complete in all respect and including entire carriage of materials in all leads and lifts as per the directoon of the Engineer-in-Charge 200 mm dia Table-5
Providing, Fixing and welding of MS flanges conforming to table as specified below of BIS code 6392-1971( Latest with upto date ammendments) welding of M.S. flanges on ( Two layers on inner face and one layers on outer face of each flange) GMS pipes & bends on both ends ( The GMS pipe to be measured and paid for separately )The welding of flanges conforming to IS 816-1998 with electrodes as per IS 814-1997, prov.& fixed with nuts, bolts of required size conforming to IS 1364, provide & fixes 3 mm (Minimum) thick compressed asbestos fibre / synthetic rubber gasket conforming relevant BIS Code IS 2712-1965 in trenches complete in all respect and including entire carriage of materials in all leads and lifts as per the directoon of the Engineer-in-Charge 150 mm dia Table-5
-do- 150 mm dia Table-17
Providing butt welding joints to GMSERW pipe of following dia with two layers on each end of welding using 3 mm & 4 mm dia electrodes after levelling the pipe encs according to relevant ISI specification of the Engineer-in-Charge 200mm Dia
Providing Butt Welding joints to GMS pipe of 150 mm dia with two layers on each end of welding using 3 mm & 4 mm dia electrodes after levelling the pipe encs according to relevant ISI specification of the Engineer-in-Charge 150 mm Dia
S/E of Submersible Pumping Machinery for LIS Singha Supply of submersible pumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut/ lubi/ Hindustan/Groundfos confirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear tear.It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable ,errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. a Pumps :- Specifications i) Make ii) Model iii) No. of stages iv) Manufacter's certificate to be attached Performance i) Discharge ii) Head iii) Efficiency of Pump a) Duty Head b) (+) 10% Duty Head. c) (-) 15% Duty Head d) Performance curve to be attached b) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed v) Insulation
Discharge, (Q) 14.49 LPS
Total Head ( H ) 193.83 Mts.
a) SWL in Tubewell = 131.10 Mtr. bgl.
c) R.L. point of discharge =322.90 Mtr.
d) Seasonal fluctuation + draught condition + bowl assembly. 4.55 Mtrs.
e) Drawdown in Tubewell 21.35 Mtrs.
f) R.L of lowest point of pumpset installation =142.10 Mtrs.
g) Static Column lift = 157.00 Mtrs.
Rising main. Column Pipe.
Length 630 Mtrs. Length 167.00 mtrr.
Dia meter.150 mm Dia 125 mm
Class GMS ( M) Class GMS. (M)
Pumping hours hours
Altitude of installations above M.S.L. __________mtr.
Characteristic of water.
a) Temperature _______ Deg Cel.
b) Turbidity ________JTU.
c) Allkanity. ___________mg/ l Ca Co3
d) Size of solids ____________mm
e) others
Depth of T/well mtr.
Dia of T/ well assembly 200 mm.
Length of assembly pipe.
Dia of housing pipe 300 mm.
Length of housing pipe
OPERATING CONDITIONS.
Type of Current :- A.C.Three Phase.
Frequency:- 50 Cycles /Sec.
Rated Voltage 415 +/- 15 % Volts.
System of earthing: Double Loop earthing as per BIS 3843-1987 Latest.
Speed of Revolution ____________ RPM 2900
MOTOR.
Ref. to BIS code BIS 9283-1979 with upto date amendments.
Type of enclosure of motor: As per BIS ; 4691-1985 ( latest )
Mechanical out put in H.P.
Class of insulation :Class B
The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations.
Ref. to BIS code ; BIS ; 5659-1978 with upto date amendments.
Drive Type: Electric driven.
Operating Range: -15 % to+10 % of Total head at duty point.
Deliver size of Pump : ________( To be quoted by tenderer.)
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch: i) Make : ii) Type : iii) Capacity :200 Amp.
Providing MS Sheet steel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections. . Panel /Switch Board. i) Drawing.ii) layout Plan.
OCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or without intial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. OCB 1) Make. ii) Type iii) Range. 200 Amp. iv) Capacity.
ii) ELR of recommended make L&T / Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. ELR i) Make. ii) Type iii) Range. 200 Amp. iv) Capacity.
iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relay i) Make ii ) Type iii) Range 0-500
d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Make iii) Rating
Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) with upto date amendments. 3 phase indicators
e) Capacitor of BHEL / GEC / L&T / Mecheil make as per IS ; 2834-1968 with upto date amendments,to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter / IEC make ) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitor i) Type ii) Make iii) Range 16 KVAR
Providing suitable starter of L&T /BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. Starter i) Type ii) Make Single phase preventor i) Type ii) Make
Providing and fixing double flanged Cast Iron/Ductile Iron Sliuce valve of Leader / Kirloskar/Kartar/LP Brand make for the Column pipe of pump and capable of withstanding the normal seat pressure and as per IS 780-1992 with latest ammendments Class PN 1.00 For Column Pipe 125 mm dia Sluice valve i) Make ii) Class PN 1.00 iii) Material cast iron / DI
Providing and fixing double flanged Cast Iron/Ductile Iron Reflux valve of Leader / Kirloskar/Kartar/LP brand make having by pass arrangement on the delivery line of pump and capable of withstanding the normal seat pressure and as per IS 6312-1984 P-I with latest ammendments 150 mm dia Sluice valve i) Make ii) Class PN 1.00 iii) Material cast iron / DI
Providing and fixing pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements Pressure Gauge i) Make
Supply of PVC jointless,flat water proof cable with copper conductor as per BIS 694-1998 latest with upto date ammendments of Havelles/Finolex make suitable for the pumpsets offered from OCB to motor including all other electrical equipments / accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor.The type, size and make shall be subject to approval of HPSEB authorities. Submersible cable i) Finolex/ Havells make ii) Size 25 mm2 (iii) Core=3
Lowering of GMS Column pipe for assembly 125 mm dia including MS flanges' of Table 17 as per IS : 6392-1971 with upto date amendments, rubber / asbestos gasket of min.3 mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 .The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No.5 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main .The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2 Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge.( The pipe shall be supplied by the department free of cost from Divisional store Malahat ) Column pipe i) Size 125 mm dia ii) Class (M) iii) Length
Installation of all items appearing at S.No 65 to 73 as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havells make including all other accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switch i) Size 50 mm2 ii) Make iii) Type iv) Capacity v) core
Providing and fixing double loop earthing with GI plate of 600x600x6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI flat 32x6mm above 50HP
S/E of Submersible Pumping Machinery for LIS Lower Badehra (57) Supply of submersible pumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut/ lubi/ Hindustan,Groundfos confirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear tear.It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable ,errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. a Pumps :- Specifications i) Make ii) Model iii) No. of stages iv) Manufacter's certificate to be attached Performance i) Discharge ii) Head iii) Efficiency of Pump a) Duty Head b) (+) 10% Duty Head. c) (-) 15% Duty Head d) Performance curve to be attached b) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed v) Insulation
Discharge, (Q) 23.50 LPS
Total Head ( H ) 32.58 Mts.
a) SWL in Tubewell =0.00 Mtr. bgl.
c) R.L. point of discharge =204.90 Mtr.
d) Seasonal fluctuation + draught condition + bowl assembly. 9.00 Mtrs.
e) Drawdown in Tubewell 10.50 Mtrs.
f) R.L of lowest point of pumpset installation =180.50 Mtrs.
g) Static Column lift = 19.50 Mtrs.
Rising main. Column Pipe.
Length 350.00 Mtrs. Length 29.50 Mtr.
Dia meter. 200 mm Dia 125 mm
Class GMSERW Class GMS. (M)
Pumping hours hours
Altitude of installations above M.S.L. __________mtr.
Characteristic of water.
a) Temperature _______ Deg Cel.
b) Turbidity ________JTU.
c) Allkanity. ___________mg/ l Ca Co3
d) Size of solids ____________mm
e) others
Depth of T/well mtr.
Dia of T/ well assembly 200 mm.
Length of assembly pipe.
Dia of housing pipe 300 mm.
Length of housing pipe
OPERATING CONDITIONS.
Type of Current :- A.C.Three Phase.
Frequency:- 50 Cycles /Sec.
Rated Voltage 415 +/- 15 % Volts.
System of earthing: Double Loop earthing as per BIS 3843-1987 Latest.
Speed of Revolution ____________ RPM 2900
MOTOR.
Ref. to BIS code BIS 9283-1979 with upto date amendments.
Type of enclosure of motor: As per BIS ; 4691-1985 ( latest )
Mechanical out put in H.P.
Class of insulation :Class B
The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations.
Ref. to BIS code ; BIS ; 5659-1978 with upto date amendments.
Drive Type: Electric driven.
Operating Range: -15 % to+10 % of Total head at duty point.
Deliver size of Pump : ________( To be quoted by tenderer.)
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch: i) Make : ii) Type : iii) Capacity : 63 Amp.
Providing MS Sheet steel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections. . Panel /Switch Board. i) Drawing.ii) layout Plan.
MCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or without intial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. MCB 1) Make. ii) Type iii) Range. 63 Amp. iv) Capacity.
ii) ELCB of recommended make L&T/Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. ELCB 1) Make. ii) Type iii) Range. 63 Amp. iv) Capacity.
iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relay i) Make ii ) Type iii) Range 0-500
d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Make iii) Rating
Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) with upto date amendments. 3 phase indicators
e) Capacitor of BHEL / L&T make as per IS ; 2834-1968 with upto date amendments,to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter / IEC make ) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitor i) Type ii) Make iii) Range 5 KVAR
Providing suitable starter of L&T /BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. Starter i) Type ii) Make Single phase preventor i) Type ii) Make
Providing and fixing double flanged Cast Iron/Ductile iron Sliuce valve of Leader / Kirloskar/Kartar/LP brand make for the Column pipe of pump and capable of withstanding the normal seat pressure and as per IS 780-1992 with latest ammendments Class PN 1.00 For Column Pipe 125 mm dia Sluice valve i) Make ii) Class PN 1.00 iii) Material cast iron / DI
Providing and fixing double flanged Cast Iron/Ductile iron Reflux valve of Leader / Kirloskar/Kartar/LP Brand make having by pass arrangement in rising main of pump and capable of withstanding the normal seat pressure and as per IS 6312-1984 P-I with latest ammendments 200 mm dia Sluice valve i) Make ii) Class PN 1.00 iii) Material cast iron / DI
Providing and fixing pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements Pressure Gauge i) Make
Supply of PVC jointless,flat water proof cable with copper conductor as per BIS 694-1998 latest with upto date ammendments of Havelles/Finolex make suitable for the pumpsets offered from MCB to motor including all other electrical equipments / accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor.The type, size and make shall be subject to approval of HPSEB authorities. Submersible cable i) Finolex/ Havells make ii) Size 4 mm2 (iii) Core=3
Lowering of GMS Column pipe for assembly 125 mm dia including MS flanges' of Table 17 as per IS : 6392-1971 with upto date amendments, rubber / asbestos gasket of min.3 mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 .The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No.5 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main .The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2 Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge.( The pipe shall be supplied by the department free of cost from Divisional store Malahat ) Column pipe i) Size 125 mm dia ii) Class (M) iii) Length
Installation of all items appearing at S.No 77 to 85 as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havells make including all other accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switch i) Size 16 mm2 ii) Make iii) Type iv) Capacity v) core
Providing and fixing double loop earthing with GI plate of 600x600x6.3mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt,25x5mm strip as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI Flat 25x3 mm.
S/E of Submersible Pumping Machinery for LIS Badehra (59) Supply of submersible pumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut/ lubi/ Hindustan,Groundfos confirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear tear.It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable ,errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. a Pumps :- Specifications i) Make ii) Model iii) No. of stages iv) Manufacter's certificate to be attached Performance i) Discharge ii) Head iii) Efficiency of Pump a) Duty Head b) (+) 10% Duty Head. c) (-) 15% Duty Head d) Performance curve to be attached b) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed v) Insulation
Discharge =( Q) 24.85 LPS
Total Head =( H) 66.08 Mts.
a) SWL in Tubewell = 20.00 Mtr. bgl.
c) R.L. point of discharge =214.90 Mtr.
d) Seasonal fluctuation + draught condition + bowl assembly. 9.00 Mtrs.
e) Drawdown in Tubewell =11.00 mtrs.
f) R.L of lowest point of pumpset installation =160 Mtrs.
g) Static Column lift =40 Mtrs.
Rising main. Column Pipe.
Length 550 Mtrs. Length 50 Mtr.
Dia meter. 200 mm Dia 125 mm
Pumping hours hours
Altitude of installations above M.S.L. __________mtr.
Characteristic of water.
a) Temperature _______ Deg Cel.
b) Turbidity ________JTU.
c) Allkanity. ___________mg/ l Ca Co3
d) Size of solids ____________mm
e) others
Depth of T/well mtr.
Dia of T/ well assembly 200 mm.
Length of assembly pipe.
Dia of housing pipe 300 mm.
Length of housing pipe
OPERATING CONDITIONS.
Type of Current :- A.C.Three Phase.
Frequency:- 50 Cycles /Sec.
Rated Voltage 415 +/- 15 % Volts.
System of earthing: Double Loop earthing as per BIS 3843-1987 Latest.
Speed of Revolution ____________ RPM 2900
MOTOR.
Ref. to BIS code BIS 9283-1979 with upto date amendments.
Type of enclosure of motor: As per BIS ; 4691-1985 ( latest )
Mechanical out put in H.P.
Class of insulation :Class B
The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations.
Ref. to BIS code ; BIS ; 5659-1978 with upto date amendments.
Drive Type: Electric driven.
Operating Range: -15 % to+10 % of Total head at duty point.
Deliver size of Pump : ________( To be quoted by tenderer.)
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch: i) Make : ii) Type : iii) Capacity : 100Amp.
Providing MS Sheet steel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections. . Panel /Switch Board. i) Drawing.ii) layout Plan.
MCCB of L&T/ Havells / Standard make of suitable capacity on incoming feeder with or without intial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. MCCB 1) Make. ii) Type iii) Range. 100Amp. iv) Capacity.
ii) ELR of recommended make L&T Havells / Standard / Kilburn as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. ELR 1) Make. ii) Type iii) Range. 100 Amp. iv) Capacity.
iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relay i) Make ii ) Type iii) Range 0-500
d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ; 8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Make iii) Rating
Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 (P- I&II ) with upto date amendments. 3 phase indicators
e) Capacitor of BHEL / GEC / L&T / Mecheil make as per IS ; 2834-1968 with upto date amendments,to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter / IEC make ) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitor i) Type ii) Make iii) Range 9 KVAR
Providing suitable starter of L&T / BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. Starter i) Type ii) Make Single phase preventor i) Type ii) Make
Providing double flanged Cast Iron/ Ductile iron Sliuce valve of Leader / Kirloskar/Kartar/LP brand make for the Column pipe of pump and capable of withstanding the normal seat pressure and as per IS 780-1992 with latest ammendments Class PN 1.00 For Column Pipe 125 mm dia Sluice valve i) Make ii) Class PN 1.00 iii) Material cast iron / DI
Providing double flanged swing type Cast Iron/ductile iron Reflux valves of Leader/ Kirloskar/ Kartar/LP brand make having Bye Pass arrangement on the rising main of pump and capable of with standing the normal seat pressure and as per 5312-1992 with latest ammendment PN 1.00 for R/main 200 mm dia. Reflex valve i) Make ii) Class PN 1.00 iii) Material cast iron / DI
Providing pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements Pressure Gauge i) Make
Supply of PVC jointless,flat water proof cable with copper conductor as per BIS 694-1998 latest with upto date ammendments of Havelles/Finolex make suitable for the pumpsets offered from MCCB to motor including all other electrical equipments / accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor.The type, size and make shall be subject to approval of HPSEB authorities. Submersible cable i) Finolex/ Havells make ii) Size 10 mm2 (iii) Core=3
Lowering of GMS Column pipe for assembly 125 mm dia including MS flanges of Table 17 as per IS : 6392-1971 with upto date amendments, rubber / asbestos gasket of min.3 mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 .The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No.5 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main .The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2 Nos.) at the top of T/well assembly, and as per the direction of Engineer-in-Charge. (The pipe shall be supplied by the department free of cost from Divisional store Malahat) Column pipe i) Size 125 mm dia ii) Class (M) iii) Length
Installation of all items appearing at S.No 89 to 97 as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havells make including all other accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switch i) Size 16mm2 ii) Make iii) Type iv) Capacity v) core
Providing and fixing double loop earthing with Copper plate of 600x600x3.15 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) Copper wire 4 SWG beyond 35HP to 50HP
S/E of Submersible Pumping Machinery for LIS Palkwah (Peerthan) Supply of submersible pumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut/ lubi/ Hindustan,Groundfos confirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear tear.It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable ,errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. a Pumps :- Specifications i) Make ii) Model iii) No. of stages iv) Manufacter's certificate to be attached Performance i) Discharge ii) Head iii) Efficiency of Pump a) Duty Head b) (+) 10% Duty Head. c) (-) 15% Duty Head d) Performance curve to be attached b) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed v) Insulation
Discharge =( Q) 19.20 LPS
Total Head =( H) 130.91 Mts.
a) SWL in Tubewell = 36.57 Mtr. bgl.
c) R.L. point of discharge =354.30 Mtr.
d) Seasonal fluctuation + draught condition + bowl assembly. 9.00 Mtrs.
e) Drawdown in Tubewell =12.19 mtrs.
f) R.L of lowest point of pumpset installation =242.24 Mtrs.
g) Static Column lift =57.76 Mtrs.
Rising main. Column Pipe.
Length 780 Mtrs. Length 67.76 Mtr.
Dia meter. 150 mm Dia 125 mm
Class GMS Class GMS. (M)
Pumping hours hours
Altitude of installations above M.S.L. __________mtr.
Characteristic of water.
a) Temperature _______ Deg Cel.
b) Turbidity ________JTU.
c) Allkanity. ___________mg/ l Ca Co3
d) Size of solids ____________mm
e) others
Depth of T/well mtr.
Dia of T/ well assembly 200 mm.
Length of assembly pipe.
Dia of housing pipe 300 mm.
Length of housing pipe
OPERATING CONDITIONS.
Type of Current :- A.C.Three Phase.
Frequency:- 50 Cycles /Sec.
Rated Voltage 415 +/- 15 % Volts.
System of earthing: Double Loop earthing as per BIS 3843-1987 Latest.
Speed of Revolution ____________ RPM 2900
MOTOR.
Ref. to BIS code BIS 9283-1979 with upto date amendments.
Type of enclosure of motor: As per BIS ; 4691-1985 ( latest )
Mechanical out put in H.P.
Class of insulation :Class B
The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations.
Ref. to BIS code ; BIS ; 5659-1978 with upto date amendments.
Drive Type: Electric driven.
Operating Range: -15 % to+10 % of Total head at duty point.
Deliver size of Pump : ________( To be quoted by tenderer.)
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch: i) Make : ii) Type : iii) Capacity :200 Amp.
Providing MS Sheet steel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections. . Panel /Switch Board. i) Drawing.ii) layout Plan.
OCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or without intial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. OCB 1) Make. ii) Type iii) Range. 200 Amp. iv) Capacity.
ii) ELR of recommended make L&T / Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. ELR i) Make. ii) Type iii) Range. 200 Amp. iv) Capacity.
iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relay i) Make ii ) Type iii) Range 0-500
d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Make iii) Rating
Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) with upto date amendments. 3 phase indicators
e) Capacitor of BHEL / L&T make as per IS ; 2834-1968 with upto date amendments,to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter / IEC make ) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitor i) Type ii) Make iii) Range 16 KVAR
Providing suitable starter of L&T /BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. Starter i) Type ii) Make Single phase preventor i) Type ii) Make
Providing and fixing double flanged Cast Iron/Ductile iron Sliuce valve of Leader / Kirloskar/Kartar/LP Brand make for the Column pipe of pump and capable of withstanding the normal seat pressure and as per IS 780-1992 with latest ammendments Class PN 1.00 For Column Pipe 125 mm dia Sluice valve i) Make ii) Class PN 1.00 iii) Material cast iron / DI
Providing and fixing double flanged Cast iron/ Ductile iron Reflux valve of Leader / Kirloskar/Kartar/LP Brand make having by pass arrangement on the delivery line of pump and capable of withstanding the normal seat pressure and as per IS 6312-1984 P-I with latest ammendments 150 mm dia Sluice valve i) Make ii) Class PN 1.00 iii) Material cast iron/ DI
Providing and fixing pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements Pressure Gauge i) Make
Supply of PVC jointless,flat water proof cable with copper conductor as per BIS 694-1998 latest with upto date ammendments of Havelles/Finolex make suitable for the pumpsets offered from OCB to motor including all other electrical equipments / accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor.The type, size and make shall be subject to approval of HPSEB authorities. Submersible cable i) Finolex/ Havells make ii) Size 25 mm2 (iii) Core=3
Lowering of GMS Column pipe for assembly 125 mm dia including MS flanges' of Table 17 as per IS : 6392-1971 with upto date amendments, rubber / asbestos gasket of min.3 mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 .The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No.5 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main .The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2 Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge.( The pipe shall be supplied by the department free of cost from Divisional store Malahat ) Column pipe i) Size 125 mm dia ii) Class (M) iii) Length
Installation of all items appearing at S.No 101 to 109 as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havells make including all other accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switch i) Size 50 mm2 ii) Make iii) Type iv) Capacity v) core
Providing and fixing double loop earthing with GI plate of 600x600x6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI flat 32x6mm above 50HP
S/E of Submersible Pumping Machinery for LIS Haroli Supply of submersible pumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut/ lubi/ Hindustan,Groundfos confirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear tear.It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable ,errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. a Pumps :- Specifications i) Make ii) Model iii) No. of stages iv) Manufacter's certificate to be attached Performance i) Discharge ii) Head iii) Efficiency of Pump a) Duty Head b) (+) 10% Duty Head. c) (-) 15% Duty Head d) Performance curve to be attached b) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed v) Insulation
Discharge =( Q) 14.97 LPS
Total Head =( H) 168.62 Mts.
a) SWL in Tubewell = 43.00 Mtr. bgl.
c) R.L. point of discharge =280.7 Mtr.
d) Seasonal fluctuation + draught condition + bowl assembly. 9.00 Mtrs.
e) Drawdown in Tubewell 13.00 Mtrs.
f) R.L of lowest point of pumpset installation =131.00 Mtrs.
g) Static Column lift = 65.00 Mtrs.
Rising main. Column Pipe.
Length 1360 Mtrs. Length 75.00Mtr.
Dia meter. 150 mm Dia 125 mm
Class GMS(M) Class GMS. (M)
Pumping hours hours
Altitude of installations above M.S.L. __________mtr.
Characteristic of water.
a) Temperature _______ Deg Cel.
b) Turbidity ________JTU.
c) Allkanity. ___________mg/ l Ca Co3
d) Size of solids ____________mm
e) others
Depth of T/well mtr.
Dia of T/ well assembly 200 mm.
Length of assembly pipe.
Dia of housing pipe 300 mm.
Length of housing pipe
OPERATING CONDITIONS.
Type of Current :- A.C.Three Phase.
Frequency:- 50 Cycles /Sec.
Rated Voltage 415 +/- 15 % Volts.
System of earthing: Double Loop earthing as per BIS 3843-1987 Latest.
Speed of Revolution ____________ RPM 2900
MOTOR.
Ref. to BIS code BIS 9283-1979 with upto date amendments.
Type of enclosure of motor: As per BIS ; 4691-1985 ( latest )
Mechanical out put in H.P.
Class of insulation :Class B
The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations.
Ref. to BIS code ; BIS ; 5659-1978 with upto date amendments.
Drive Type: Electric driven.
Operating Range: -15 % to+10 % of Total head at duty point.
Deliver size of Pump : ________( To be quoted by tenderer.)
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch: i) Make : ii) Type : iii) Capacity :200 Amp.
Providing MS Sheet steel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections. . Panel /Switch Board. i) Drawing.ii) layout Plan.
OCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or without intial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. OCB 1) Make. ii) Type iii) Range. 100 Amp. iv) Capacity.
ii) ELR of recommended make L&T / Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. ELR i) Make. ii) Type iii) Range. Amp. iv) Capacity.
iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relay i) Make ii ) Type iii) Range 0-500
d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Make iii) Rating
Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) with upto date amendments. 3 phase indicators
e) Capacitor of BHEL / L&T make as per IS ; 2834-1968 with upto date amendments,to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter / IEC make ) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitor i) Type ii) Make iii) Range 13 KVAR
Providing suitable starter of L&T /BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. Starter i) Type ii) Make Single phase preventor i) Type ii) Make
Providing and fixing double flanged Cast Iron/Ductile iron Sliuce valve of Leader / Kirloskar/Kartar/LP brand make for the Column pipe of pump and capable of withstanding the normal seat pressure and as per IS 780-1992 with latest ammendments Class PN 1.00 For Column Pipe 125 mm dia Sluice valve i) Make ii) Class PN 1.00 iii) Material cast iron?DI
Providing and fixing double flanged Cast Iron/Ductile iron Reflux valve of Leader / Kirloskar/Kartar/LP brand make having by pass arrangement on the delivery line of pump and capable of withstanding the normal seat pressure and as per IS 6312-1984 P-I with latest ammendments 150 mm dia Sluice valve i) Make ii) Class PN 1.60 iii) Material cast iron/DI
Providing and fixing pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements Pressure Gauge i) Make
Supply of PVC jointless,flat water proof cable with copper conductor as per BIS 694-1998 latest with upto date ammendments of Havelles/Finolex make suitable for the pumpsets offered from OCB to motor including all other electrical equipments / accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor.The type, size and make shall be subject to approval of HPSEB authorities. Submersible cable i) Finolex/ Havells make ii) Size 16 mm2 (iii) Core=3
Lowering of GMS Column pipe for assembly 125 mm dia including MS flanges' of Table 17 as per IS : 6392-1971 with upto date amendments, rubber / asbestos gasket of min.3 mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 .The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No.5 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main .The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2 Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge.( The pipe shall be supplied by the department free of cost from Divisional store Malahat ) Column pipe i) Size 125 mm dia ii) Class (M) iii) Length
Installation of all items appearing at S.No 113 to 121 as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havells make including all other accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switch i) Size 35 mm2 ii) Make iii) Type iv) Capacity v) core
Providing and fixing double loop earthing with GI plate of 600x600x6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI flat 32x6mm above 50HP
PROVIDING AND LAYING OF DISTRIBUTION NETWORK Excavation in foundation trenches ( for pipes and pits ) upto all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft / hard rock or chieselling soft/ hard rock where blasting is prohibited, in all lifts including trimming and dressing of sides, levelling of beds to correct grade including, shoring, strutting, planking, timbering and dewatering, wherever required, stacking the useable and unuseable material/ soil separately and after laying, jointing and testing of pipes returing the useable soil in trenches in 15 cm ( Fifteen centimeter ) layers including consolidating of such deposited layer by ramming and watering and then disposing of all surplus excavated soil /un-useable materials as directed within all leads and lifts including restoration of un-metalled surface to its original condition and including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respect within all leads and lifts as per the directions of Engineer-in-Charge.
Providing and laying cement concrete 1:4:8 ( 1 cement : 4 sand : 8 graded stone aggregate 40 mm.nominal size ) and curing complete excluding cost of form work in foundation and plinth .
Ist class brick work using common burnt clay building bricks in foundation and plinth in cement mortor 1:4 ( 1 cement:'4 sand )
50 mm thick Cement concrete flooring 1:2:4 (1 cement : 2 sand : 4 graded stone aggregate 20 mm nominal size ) laid in one layer finished with floting coat of neat cement in all leads and lifts and as per the direction of the Engineer-in-Charge
40 mm thick Cement concrete flooring 1:2:4 (1 cement : 2 sand : 4 graded stone aggregate 20 mm nominal size ) laid in one layer finished with floting coat of neat cement in all leads and lifts and as per the direction of the Engineer-in-Charge
15 mm thick cement plaster in single coat on fair side of brick/ stone masonry/concrete for interior plastering upto floor two level including arrises internal rounded angles chamfers angle not exceeding 80 mm in girth and finished even & smooth in cement mortor 1:3 (1 cement:3 sand) in all leads and lifts.
Providing, Laying ( to level or slope), jointing and testing in trenches HDPE pipes of following diameters & classes as per IS 4984-1995 , PE-63 and jointing the pipes through push type compression joints by hydraulically operated machines upto 110 mm diameter and butt fussion ( heat fusion process) above 110 mm diameter i/c necessary fittings,bends,tees & reducers fabricated in accoradance with IS 8360 & IS 8008 with latest ammendments & shall be provided as per site conditions. (Earth work in trenches to be measured and paid for separately) and jointing shall be complete in all respects including testing at site upto entire satisfaction of Engineer-in charge.
125 mm dia PN 4
140 mm dia PN 4
160 mm dia PN 4
Providing, Laying ( to level or slope), jointing and testing in trenches reinforceemnt cement concrete light duty socketted & spigotted non pressure pipe I.S. class NP2 or P of the following internal diameters with jointing with rubber rings including testing of joints duly ISI marked as per ISI 458- 2003( latest) with upto date ammendements .
150 mm dia NP-2
250 mm dia NP-2
250 mm dia P-1
Pdg. and fixing C.I. alfa valve of the following diameter complete in all respect as per the in all leads and lifts as per the'direction of Engineer -in-Charge
150mm dia
250mm dia
Laying, jointing and testing in trenchesplain ended GMS pipes (Medium grade) confirming to ISI (1239-2004) specification including commissioning and cost of all fittings i.e. bends, tail pieces, tees & other special manufacturing from parent pipes as applicable to the particular reach & of approved/sepecification as per site condition and cutting of pipes where ever required as per site requirement in respect of following diameters in Rising Main ( The earth work in trenches shall be measured and paid for separately ) including entire carriage of material in all leads and lifts as per the direction of the Engineer-in-Charge. 150 mm dia. (Medium grade)
Providing Butt Welding joints to GMS pipe of 150 mm dia with two layers on each end of welding using 3 mm & 4 mm dia electrodes after levelling the pipe encs according to relevant ISI specification of the Engineer-in-Charge 150 mm Dia
SANJEEV THAKUR
ANIL KUMAR VASHISHT(GOVT, CONTRACTOR)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.13 MB
Tendernotice_2.pdf
PDF • 0.64 MB
Tendernotice_3.pdf
PDF • 0.19 MB
Tendernotice_4.pdf
PDF • 0.21 MB
BOQ_47845.xls
BOQ • 0.47 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .