Tender Value
₹22 L
EMD Value
₹44,000
Closing Date
23 Feb 2022, 6:00 pmClosed
CWE Jaipur
HQ CWE Jaipur, Kalyan Marg, Jaipur
REPAIR AND MAINT OF HT 11 KV NETWORK INCLUDING TRANSFORMER SWITCH GEAR AND CONNECTED ACCESSORIES AT ZONE-I AREA UNDER GE(S) JAIPUR
2022_MES_504358_1
CWE/JPR(S)/82127/E8
Open Tender
Miscellaneous Works
Item Rate
365 days
GE (S) Jaipur
enlisted with MES in Class E and above and category b(ii) or b(iii)
7 documents required · 7 mandatory
₹500
Yes
GE (S) Jaipur
₹44,000
Yes
21 Mar 2022
28 Jan 2022
25 Feb 2022
28 Jan 2022
23 Feb 2022
11 Feb 2022
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation etc or for shafts, wells, cess pits, manholes, pier holes, laying cables erection of poles / struts/stays etc not exceeding 10 Sqm on plan, not exceeding 1.5 metre in depth and getting out in any type of soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in any type of soil complete all as specified and directed.
Removing of excavated material (soil) to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.50metre above the starting point complete all as specified and directed.
Supplying and laying factory made un-reinforced PCC precast cable covers class HV, type I, flat, size 300mm x 180mm x 40mm complete all as specified and directed.
M&L for sand cushioning to PVC underground cable with tibba sand and punning to provide a required cover complete all as specified and directed. Note:- Punned thickness shall be considered for payment purpose
Taking out old unserviceable HT cable size 185 Sqmm, 3 core complete all as specified and directed
M&L pre-stressed cement concrete poles in repair, 11 metre long with minimum cross section 152 mm x 152 mm at top and minimum cross section 152 mm x 260 mm at bottom, class-9, conforming to IS-1678 etc complete all as specified and directed. NOTE: The necessary excavation, returning, filling and PCC shall be deemed to be included in rate quoted by contractor.
Dismantling and taking down existing HT insulators of any type and size complete all as specified and directed.
S&F of Disc type insulator, Porcelain, vitreous brown, white or green single disc assembly, 145mm high & 255mm dia ball & socket type, for tension clamps for conductors, working pressure 11000 volts complete all as specified and directed.
S&F of pin type, porcelain, vitreous brown, white or green insulator (HT), 150mm height and 150 mm dia, 11000 volts grade including one galvanised MS spindle, two GI washers and one GI nut complete all as specified and directed.
S&F of post insulator with GI post for holding fixed/moving contact assembly suitable for Air break gang operated switch 200 Amps, 11000 volts grade complete all as specified and directed.
Supply & fixing or laying in repair galvanised 100 mm bore steel tubing light grade (ISI marked) for protection of underground cable on poles / walls under road crossing etc complete all as specified and directed.
M&L earthing complete as per electrical plate No 3 of MES SSR Part-I with galvanised steel earth plate electrode 600 mmx600mmx6mm, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level connected to and including connected to galvanised earth lead wire/strip 4.0mm dia by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 40 mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. NOTE:- (i) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.00 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Quoted shall include the cost of 7.5 metre GI pipe for protection of earth wire/strip. (iii) Quoted shall include cost of 7.5 metre earth lead wire/strip. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides.
M&L earthing complete as per electrical plate No 3 of MES SSR Part-I with galvanised steel earth plate electrode 600 mmx600mmx6mm, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level connected to and including galvanised iron or steel earth strip 25mm x 4mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 40 mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. NOTE:- (i) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.00 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Quoted shall include the cost of 7.5 metre GI pipe for protection of earth wire/strip. (iii) Quoted shall include cost of 7.5 metre earth lead wire/strip. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides
M&L earthing complete as per electrical plate No 3 of MES SSR Part-I with galvanised steel earth plate electrode 600 mmx600mmx6mm, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level connected to and including galvanised iron or steel earth strip 32mm x 6mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 32mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. NOTE:- (i) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.00 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Quoted shall include the cost of 7.5 metre GI pipe for protection of earth wire/strip. (iii) Quoted shall include cost of 7.5 metre earth lead wire/strip. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides
M&L earthing complete as per electrical plate No 3 of MES SSR Part-I with galvanised steel earth plate electrode 600 mmx600mmx6mm, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level connected to and including galvanised iron or steel earth strip 20mm x 3mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 40 mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. NOTE:- (i) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.00 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Quoted shall include the cost of 7.5 metre GI pipe for protection of earth wire/strip. (iii) Quoted shall include cost of 7.5 metre earth lead wire/strip. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides
M&L for trimming of tree branches upto 75mm dia to clear the route of HT/LT over head lines around the 3m from the external conductors including removing the cut branches from site and depositing at places all as directed. NOTE: (i) One span from pole of distance nearest to 30 metres shall be considered as one unit
Supply, laying and commissioning in repair XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor 11000 volts grade IS-7098 marked, suitable for HT 11 KV (E) System laid in trenches/ ducts/ encased in GI pipe/ fixed to poles including jointing & testing complete all as specified and directed of following cross sectional area :-
(a) 95 Sqmm, 3 core
(b) 120 Sqmm, 3 core
(c) 185 Sqmm, 3 core
M&L for boring of existing road/path for laying of GI pipe protection for UG cable including making good disturbed area/surface all as specified and directed.
M&L for cable end termination, jointing kit, HT 11 KV grade, Heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade complete all as specified and directed of following sizes :-
(a) 50 to 95 Sqmm x 3 core
(b) 120 to 185 Sqmm x 3 core
(c) 240 to 300 Sqmm x 3 core
M&L for cable end termination, jointing kit, HT 11 KV grade size 120 to 185 Sqmm x 3 core, Heat shrinkable, indoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade complete all as specified and directed.
M&L for cable, jointing kit, HT 11 KV grade, Heat shrinkable, straight through type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade complete all as specified and directed of following sizes :-
(a) 95 Sqmm x 3 core
(a) 120 to185 Sqmm x 3 core
(b) 240 to 300 Sqmm x 3 core
Supply, installing, testing and commissioning of Air break, gang operated, triple pole switch 200 Amp rating complete with fuse carriers and HT fuse elements., outdoor, horizontal / vertical mounting type (ISI marked), mechanically operated, mounted on insulators and frame work with operating mechanism worked from ground level with locking arrangements including Godrej pattern 65mm pad locks with two keys, complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections including taking down old UNSERVICEABLE items complete all as specified and directed
S&F of lightening arrestor in repair expulsion type complete with all fittings transmission class discharge capacity 65 KA suitable for 11000 volts complete all as specified and directed
M&L scrapping/ removing old painted surfaces and preparation of surface of steel member on HT 2 Pole structure including two coats of aluminium paint to steel structure over one coat of red oxide using brush/spray at site complete all as specified and directed.
M&L scrapping/ removing old painted surfaces and preparation of surface of steel member on HT steel structure (bus bar and GOD of sigle transformer) including two coat of aluminium paint to steel structure over one coat of red oxide using brush/spray at site complete all as specified and directed.
M&L scrapping/ removing old painted surfaces and preparation of surface of steel member on HT steel structure (bus bar and GOD at Haldighati sub station complete and PH 4) including two coat of aluminium paint to steel structure over one coat of red oxide using brush/spray at site complete all as specified and directed.
M&L painting to HT PCC poles with two coats yellow and white paint alternatively all around the pole from the bottom of the pole as straps for identification of pole. The height of the strap shall be 30cm and number of straps shall be 05 Nos including scrapping/ removing old painted surfaces and preparation of surface complete all as specified and directed.
M&L for dismantling and taking down unserviceable HT gang operated air break switch any type & size including all accessories from HT feeder two/four pole structure and re-fixing the same in position including connection after necessary repair/replacement of u/s part complete all as specified and directed. NOTE: New spare/components shall be measured and paid separately
S&F of metallic (brass/alloy steel) fixed contact set single pole including fixing screwed nuts and washers suitable for air break gang operated switch of cap 200/400 amp 3 pole 11000 volts grade complete all as specified and directed.
S&F of metallic (brass/ alloy steel) moving contact set single pole including screws, nuts and washers suitable for air break gang operated switch of capacity200/400 Amp 11000 volts complete all as specified and directed.
S&F of flexible copper straps including fixing screws, nuts and washers suitable for air break gang operated switch 200/400 amps 11000 volts for single phase complete all as specified and directed.
M&L for shifting of trolley mounted step down transformer of any capacity at location of defective transformer and connecting to HT cable 11000 volt in coming from existing source and LT cable to exiting outgoing LT panel / OH conductor on pole, followed by shifting the same to MES store yard after disconnecting all the cables complete all as directed by Engineer-in-Charge. NOTE: T&P required for loading, unloading, shifting transporting the trolley mounted transformer back to E/M yard is deemed to be inclusive of the quoted rate.
M&L for Dehydration /filtration of transformer oil existing transformer installed at site with portable plant to improve the dielectric strength 60 KV filtration including testing of dielectric strength after dehydration at site complete all as specified and directed. NOTE: - Pre-heated oil shall be topped up as required at site before the process; oil will be measured and paid separately under respective item.
Supply & filling of transformer oil in transformer installed/ at site for toping up the level of oil having dielectric strength >60 KV during filling after initial filtration conforming to IS-335 complete all as specified and directed. NOTE: Transformer oil shall be supplied in sealed containerand empty barrel of transformer oil will be deposited by contractor in E/M store yard.
M&L for disconnecting of defective transformer (indoor/outdoor type) 11KV/433 volts copper/ Aluminium wound from power mains and dismantling the same from 2/4 pole structure/ platform mounted and transporting the same to authorised workshop and opening the transformer cover, draining out of transformer oil and keep safely for reuse after filtration, assembling, removing of the burnt parts ie tape, paper insulating strings etc gently and carefully, washing of the dust, rust and dirt from all parts including taking out HT/LT leg coil core tank and cooling tubes, painting the inner side tank by zinc chromate paint and preparing the same for re-assembling after carrying out required repair and installation on existing 2/4 pole structure/ platform with necessary fixing arrangement including connecting up electrically, commissioning and testing all as directed by Engineer-in-Charge and specified in particular specification of the following capacity :-
(a) 63 KVA to 125 KVA capacity
(b) 150 KVA to 250 KVA capacity
(c) 315 KVA to 400 KVA capacity
NOTE: U/S items required for replacement shall be measured and paid separately
Supply only HT/ LT leg coil with insulation for copper wound transformer of any capacity including rewinding complete all as specified and directed.
Supply only HT porcelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for following cap transformer :-
(a) 63 KVA to 125 KVA capacity
(b) 150 KVA to 250 KVA capacity
(c) 315 KVA to 400 KVA capacity
Supply only LT porcelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for following cap transformer :-
(a) 63 KVA to 125 KVA capacity
(b) 150 KVA to 250 KVA capacity
(c) 315 KVA to 400 KVA capacity
S&F in replacement of breather assembly of transformer with silica gel complete with end fitting complete all as specified and directed.
M&L for opening of transformer cover at site for carrying out repairs such as replacement of bushing rods gasket etc and re-assembling after carrying out required repair in the transformers complete all as specified and directed. NOTE: Bushing rods shall be measured and paid separately.
M&L for painting of outer body of transformer of following capacity applying two coats of synthetic enamel paint of specified colour by spraying painting complete including preparation of old surfaces, removing, cleaning of oil, grease,dirt all as specified and directed of following capacity :-
(a) 63 KVA to 125 KVA capacity
(b) 150 KVA to 250 KVA capacity
(c) 315 KVA to 400 KVA capacity
M&L in repair for refilling fresh Silica Gel into the breather complete all as specified and directed.
S&F in replacement of HT Jumper not more than 2 metre long on existing Two Pole/four Pole Structure of transformer/Junction point etc including using winding of ACSR Conductor (Weasel) 11000 Volt, including PG clamp Nut Bolts, Thimbles and washer etc as requirement as per site complete all as specified and directed.
M&L for surface Dressing/Cleaning of various 11/33 KV sub-stations and fencing free from vegetation of any type once in months for entire contract period including trimming of tree branches, bushes, creepers etc. complete all as specified and directed. Note:- quoted rates per sqm shall be for cleaning of one year with frequency of 2 Months.
Supplying and spreading of stone aggregate 40 mm size around transformer plinth, two/ four pole structure and HT yard etc. complete all as specified and directed.
Dismantling of cross arms, bracing, support, clamps, nut & bolt of mild steel channel or angle sections etc complete all as specified and directed.
M&L for MS work such as angle iron fencing post struts and flat iron fillets etc of grade Fe-310-0, including drilling holes, punching, splitting ends to secure chain link fencing or fixing of barbed wire to posts including all necessary cutting, welding drilling, bolting or riveting etc and including bands strap support for chain link, steel screw as required,flat iron strip fixed to secure the fencing on posts complete and rolled mild steel Framed work as in Gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering, Doors etc. to be prepared for hanging or sliding with & including either hooks & hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails & guides) & hanging; also fastening & fixing complete GDE Fe 410-0 or Fe 310-0 including taking down old fencing complete all as specified and directed.
S&F of chain link fencing of size 80mm x 80mm, 4mm dia including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc including provision of binding wire and taking out old fencing complete all as specified and directed.
M&L for dismantling damaged/ perished locking arrangement of GOD and making new locking arrangement with provision of 65mm Godrej lock with 2 keys complete all as specified and directed.
M&L for calibration and setting of protection relays of any make or type fitted on11 KV VCBs (details given below) as per IS and code of practice to ensure NO ERROR including setting for each fault over current with trip time delay in accordance to feeder load and other parameters of site including synchronizing of the setting to ensure that fault shall not travel to nearest source feeder including minor repairs, replacement of wiring etc, if required all as directed by Engineer- in- Charge. (a) Incoming VCB 11 KV – 03 Nos. (b) Outgoing VCB 11 KV – 09 Nos
NOTE: (i) The calibration and setting must be completed with in 30 days from the date of commencement to avoid any major break down. (ii) The calibration and setting shall be carried out by only qualified and experienced engineer. (iii) The relay setting shall be carried out once in a three month as per load and site conditions to avoid and any fault travel to next adjacent source breaker and shall be monitored regularly. (iv) For payment purpose the payment for calibration & setting of relay twice in 06 months is considered as each job. The cost of monitoring is also included in the item rate. (v) Calibration Certificate of authorised person should be submitted after calibration/ setting the VCBs.
M&L for disconnecting electric supply and overhauling / servicing of VCB of any make/ capacity including trolley of VCB, electro mechanical components, etc. by cleaning & removing dust particles from body, isolating contacts, moving parts, particularly from bus bar chamber, gear mechanism, motor charge spring mechanism, tightening of nuts & bolts of all components in entire mechanism and re-inserting VCB in trolley, re-connecting to load, re-commissioning complete all as specified and directed. NOTE: Cost of fixing of parts replaced are deemed to be included in quoted rate.
M&L for disconnecting electric supply and overhauling / servicing of conpact RMU of any make/ capacity without trolley of VCB, electro mechanical components, etc. by cleaning & removing dust particles from body, isolating contacts, moving parts, particularly from bus bar chamber, gear mechanism, motor charge spring mechanism, tightening of nuts & bolts of all components in entire mechanism and re-inserting VCB, re-connecting to load, re-commissioning complete all as specified and directed. NOTE: Cost of fixing of parts replaced are deemed to be included in quoted rate.
M & L for cutting the gas chamber and refilling for SF6 gas as suitable for RMU 3 way (Three SF6 breakers VCBs) and rewinding properly and leakage testing as per IP 67 complete all as specified and directed.
M & L for 11 KV resin cast Bushing complete all as specified and directed.
M&L for Cable Boot set for breakers complete all as specified and directed.
M&L for fault locating machine for fault finding on requirement for HT/LT cables of any type/size complete all as specified and directed.
M&L for relaying HT cable of any type and size complete all as specified and directed.
M&L for relaying of PCC cable cover of any type and size complete all as specified and directed.
M&L for cutting and removal of unserviceable PCC pole of any type and size from 0.6 Metre below ground level including necessary earth work and debris clearance complete all as specified and directed.
M&L for painting of "feeder names" on pipes / poles / walls / boards etc with black background (not more than 75cm X 20cm) & suitable white letters using synthetic enamel paint including cleaning, scrapping and preparation of the surface complete all as specified and directed.
Schedule of Credit
SHREE BHAGWATI ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .