Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.1 LAccepted-AOC NO 439 AHIV ADAN 11ND FLOOR 2RD STAGE INDIRA NAGAR BANGALORE 560 075 | BENGALURU URBAN | KARNATAKA | 560075 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹42.2 L+₹1.2 L (2.85%)Rejected-Finance 26 3 3RD CROSS GANESHA BLOCK SULTANPALYA RT NAGAR POST BANGALORE 560 032 | BANGALORE | BANGALORE | KARNATAKA | 560032 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹44.5 L+₹3.5 L (8.42%)Rejected-Finance | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹44.7 L+₹3.7 L (8.96%)Rejected-Finance | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹46.5 L+₹5.5 L (13.4%)Rejected-Finance 101 1ST FLOOR JASOL RESIDENCY 14TH CROSS KANAKANAGAR R T NAGAR POST BANGALORE 560032 | BANGALORE | BANGALORE | KARNATAKA | 560032 | L5 | Rejected-Finance Not Lowest |
Tender Value
Refer Docs
EMD Value
₹78,000
Closing Date
7 Dec 2022, 6:00 pmClosed
GARRISON ENGINEER NORTH BANGALORE
GARRISON ENGINEER NORTH BANGALORE T 64 MEANEE LINES MEG AND CENTRE BANGALORE 560042
SPL REPAIRS FOR REPLACEMENT OF LT OVER HEAD LINE TO UG CABLES INCLUDING POLES OTHER CONNECTED WKS AND INT WIRING TO BLDG NO T 117 RECT LIVING ACCN AT MEG CENTRE UNDER GE NORTH BANGALORE
2022_MES_565126_1
8358
Open Tender
Electrical and Maintenance Works
Item Rate
45 days
BLR
Class D Category b(i)
8 documents required · 8 mandatory
₹500
GARRISON ENGINEER NORTH BANGALORE
₹78,000
Yes
19 Dec 2022
24 Nov 2022
9 Dec 2022
24 Nov 2022
7 Dec 2022
30 Nov 2022
24 Nov 2022 - 30 Nov 2022
Amount
M & L excavation in trenches in hard/dense soil not exc 1.5 mtr wide and not exc 1.5 mtr in depth for laying of cables complete all as specified and as directed.
M & L excavation in trenches in hard/dense soil not exc 1.5 mtr wide and not exc 3 mtr in depth for etc complete all as specified and as directed.
M & L for returning, filling in trenches incl spreading leveling watering and well ramming in layers with hard/dense soil not exc 25 cm thick in each layer complete as specified and as directed
M & L for removing excavated soil to a distance not exc 1.5 mtr above the starting point complete all as specified and as directed
M & L for sand cushioning with a layer of river sand 23 cm thick under and above the cable complete all as specified and as directed. Note :- Punned thickness will be measured for payment.
Supply & laying sub class burnt bricks for cable protection complete as specified as directed
Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor connected with suitable lugs for following size :- 4 C x 10 Sqmm
As per item No. 7 above but for 4 C x 16 Sqmm
As per item No. 7 above but for 4 C x 25 Sqmm
As per item No. 7 above but for 3.5 C x 35 Sqmm
As per item No. 7 above but for 3.5 C x 50 Sqmm
As per item No. 7 above but for 3.5 C x 70 Sqmm
As per item No. 7 above but for 3.5 C x 95 Sqmm
As per item No. 7 above but for 3.5 C x 120 Sqmm
As per item No. 7 above but for 3.5 C x 185 Sqmm
As per item No. 7 above but for 3.5 C x 300 Sqmm
M&L for GI tubing light grade 40mm with all accessories for cable protection fixed on poles / bldgs / road and laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed.
M & L for GI tubing light grade 50mm with all accessories for cable protection fixed on poles/bldgs/road and laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed.
M & L for GI tubing light grade 80mm with all accessories for cable protection fixed on poles/road and laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed.
M & L for GI tubing light grade 100 mm with all accessories for cable protection fixed on poles/road and laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed.
M & L for GI tubing light grade 150 mm with all accessories for cable protection fixed on poles/road and laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed.
Dismantling the damaged unservicable RCC pole of any type.
Supply and errect steel tubular swaged poles complete with cast iron base plate,finial taper plug,bolts,nuts & screws as specified type 410SP-31, 9 mtr long .
M&L for PCC 1:3:6 type C1 with 20mm graded stone aggregate for couping of pole, filling and mass concrete of pole, make good to road surface, hard standing etc incl necessary form work all as specified and as directed
M&L for PCC 1:4:8 type D2 with 40mm graded stone aggregate in foundation of poles all as specified and as directed
Dismantling and taking down the existing LT over head ACSR line from any description all as directed
Dismantling and taking down the existing LT insulators of any type from any description all as directed
Dismantling cross-arms of M.S. channel or angle sections etc. complete all as specified and directed
Taking down earth wire 4 mm dia.
M&L for Out door type, double door sheet metal enclosure/ Bus bar chamber of size 70x60x30 cm with aluminium bus bar 600 Amps, IP-54 for 3 phase & neutral including MCCB 4 pole 415 volts 400 Amps 36 KA. complete all as specified and as directed
M&L for Bus bar chamber TPN-type (Al Busbar) with aluminium bus bar Spl 400 A TPN BBC (Al) with 4 o/g ways ,ingress protection IP-42 for 3 phase & neutral complete all as specified and as directed Make :- Indoasian Cat part No. CPPI1029 or equivalent makes.
M&L for Bus bar chamber TPN-type (Al Busbar) with aluminium bus bar Spl 200 A TPN BBC (Al) with 4 o/g ways ,ingress protection IP-42 for 3 phase & neutral complete all as specified and as directed Make :- Indoasian Cat part No. CPPI1026 or equivalent makes.
M&L cable end jointing kit for 1.1KV grade cable complete with jointing material and accessories suitable for 3.5 core/4core XLPE armoured aluminium conductor cable for following sizes:- 70 to 150 sq mm
As per item No. 33 above but for 185 to 300 sq mm
Supply and fixing moulded (FRP) junction box with IP 65 protection of size 300x200x80mm with 32 Amp 4 way heavy duty terminal block with 6 Amp MCB SP and two number of cable entry gland of standard size with suitable MS bracket to fix with pole complete all as directed
M&L of 2 runs of PVC insulated 2.5 sqmm single core multistranded copper conductor cable and one run of 2.5 sqmm copper wire as earth continuity conductor drawn through and incl rigid non metalic conduit 20 mm external dia fixed on poles & connecting up all as specified and as directed. Note: Two runs of cable and one run of earth wire and one run of conduit shall be measured as one length.
Supply & Fix GI pipe bracket made of 40mm bore light grade GI pipe1.5 mtr long suitably bent to shape and fixed on pole for fixing street light fitting with 2 Nos suitable MS clamps of size 25 x 3 mm size incluiding bolts, nuts, washersincluding taking down old unserviceable brackets all as specified and as directed.
Excavation in trenches by cutting of road crossing / PCC hard standing for laying of pipe/ cable including making good the existing surface with same finish ( PCC 1;3;6 type C2 40 mm graded stone aggregate / Bitumen) to match the original finish all as specified and as directed.
M & L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr connected to galvanized strip 25 x 4 mm as earth lead up to 7.5 mtr long by means of nuts, bolts, thimbles,check nuts and washers etc made of galvanized iron connected to earthing test point all as shown in electrical plate No 3 of SSR Part-I 2010 and as specified or indicated and testing on completion incl earth work and excavation in any type of soil PCC (1:3:6) type C1 chamber, pre cost slab 40mm thick in cement concrete (1:2:4) type B1 with 8 mm dia MS bars reinforced at 10 cm centre to centre both ways incl funnel with watering pipe wire mesh and lugs, incl test point complete all as specified and as directed
S&F LT MS cable route indicator , engraved the description on the disc not less than 6 inch dia and 6 mm thick welded with 40x6 mm MS strip of approximate length 90 cm duly painted on all steel parts as per colour code and provision of PCC 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) of not less than 0.05 cum in each at base burried under the ground including necessary earth work complete all as specified and as directed.
S&F LT Control panel board, Outdoor type, double door, cubical type,Sloppy roof front and back both side openable door, padestal mounted,CPRI approved with IP-54, overall size not less than 1250 x 1000 x 450 mm, having independent compartment for bus bar, incoming feeder and each out going feeders, dust and vermin proof & lockable, factory made, fabricated out of 3.15 mm thick CRCA sheet suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with aluminium bus bar of 800 Amp rating for 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators - 01 Set incl necessary copper cables of suitable size for MCCBs/MCBs / change over swicth / inter connections, common earth bus bar of GI Strip 32 x 6 mm at bottom with panel board at two earth terminals, cable glands with independent plates at bottom for each out going and in coming cables in cable alley panel board and painted with powder coating in siemens grey colour and provision for the following incoming and out going accessories all as specified and comprising as under :- Condt/---42
S & F LT Control panel board, Outdoor type, double door, cubical type,Sloppy roof front and back both side openable door, padestal mounted,CPRI approved with IP-54, overall size not less than 1250 x 1000 x 450 mm, having independent compartment for bus bar, incoming feeder and each out going feeders, dust and vermin proof & lockable, factory made, fabricated out of 3.15 mm thick CRCA sheet suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with aluminium bus bar of 600 Amp rating for 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators - 01 Set incl necessary copper cables of suitable size for MCCBs/MCBs / change over swicth / inter connections, common earth bus bar of GI Strip 32 x 6 mm at bottom with panel board at two earth terminals, cable glands with independent plates at bottom for each out going and in coming cables in cable alley panel board and painted with powder coating in siemens grey colour and provision for the following incoming and out going accessories all as specified and comprising as under :- Condt/--44
S & F LT Control panel board, Outdoor type, double door, cubical type,Sloppy roof front and back both side openable door, padestal mounted,CPRI approved with IP-54, overall size not less than 1000 x 750 x 450 mm, having independent compartment for bus bar, incoming feeder and each out going feeders, dust and vermin proof & lockable, factory made, fabricated out of 3.15 mm thick CRCA sheet suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with aluminium bus bar of 400 Amp rating for 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators - 01 Set incl necessary copper cables of suitable size for MCCBs/MCBs / change over swicth / inter connections, common earth bus bar of GI Strip 32 x 6 mm at bottom with panel board at two earth terminals, cable glands with independent plates at bottom for each out going and in coming cables in cable alley panel board and painted with powder coating in siemens grey colour and provision for the following incoming and out going accessories all as specified and comprising as under :- Contd/---46
S & F LT Control panel board, Outdoor type, double door, cubical type,Sloppy roof front and back both side openable door, padestal mounted,CPRI approved with IP-54, overall size not less than 1000 x 750 x 450 mm, having independent compartment for bus bar, incoming feeder and each out going feeders, dust and vermin proof & lockable, factory made, fabricated out of 3.15 mm thick CRCA sheet suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with aluminium bus bar of 400 Amp rating for 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators - 01 Set incl necessary copper cables of suitable size for MCCBs/MCBs / change over swicth / inter connections, common earth bus bar of GI Strip 32 x 6 mm at bottom with panel board at two earth terminals, cable glands with independent plates at bottom for each out going and in coming cables in cable alley panel board and painted with powder coating in siemens grey colour and provision for the following incoming and out going accessories all as specified and comprising as under :- Contd/---48
Taking out by unscrewing from boards outlet boxes, fittings & fixtures such as switch socket, ceiling rose , ceiling fiitings, old CFL/FTL / security light fittings & regulators etc and making good disturbed surface of walls and floors etc.
Material & labour for concealed point wiring by using 1.5 Sqmm PVC insulated unsheathed FRLS copper conductor multistrand drawn in suitable sunken box and frame cover plate for mounting of modular switches /sockets as required at site and provn of PVC rigid non metallic conduit medium density ISI marked fixed with all fittings and all accessories for mounting of switches and socket complete for one light/fan/socket point controlled by one switch including MS Sunken boxes, Cover frame and provn of 1.5 sqmm PVC insulated copper conductor contineous as earth wire connected to earth dolly complete for the followings: One light / ceiling fan and exhaust point controlled by one one way switch
As per item No 50 above but for One 3/5 pin socket outlet 5 Amps on the same board
As per item No 50 above but for One 3 pin socket outlet 5 Amps on independent board
As per item No 50 above but for 2.5 Sqmm cable for power switch socket 15A
S & F modular type switch single pole one way 5 Amps all as specified and as directed
S & F modular type socket out let multipurpose 5 pin 5 Amps all as specified and as directed
S & F modular type socket out let multipurpose 6 pin 5/15 Amps all as specified and as directed
supply and fix Ceiling rose surface bakelite, 65 x 50 mm three terminals 230 volts AC Single phase all as specified.
Submain wiring with 2 runs of 6 Sqmm single core multistanded PVC insulated unseathed cable 1100 Volts grade with copper conductor, drawn in and including conncealed rigid PVC conduit, conduit fittings and accessories concealed in wall / roof / floorwith one run of 6 Sqmm PVC insulated unseathed coper conductor cable as earth continuity conductor and connecting to common earth dolly including taking down unsv sub main wiring complete all as specified. Note 2 runs of cable one run of earth continuity conductor and one run PVC conduit for connections to DB,s complete.
S&F in repairs double door type DB SPN 12 Way 230 Volt with 200 Amps rated Bus Bar including necessary dummy plate.
S&F in repairs MCB SP 240 Volts of capacity 6-32 Amps.
S&F in repairs MCB single neutral (SPN), 240 Volts of capacity 40 Amps
S&F ceiling fan 1200 mm sweep 5 Star rated service value 6.00 BEE with and including modular fan regulator step type, 2 module 120W, Three Blade, down rod as per requirement along with all accessaries complete all as specified and directed. Make-HAVELLS (Enticer Art) or equivalent of Bajaj / CG.
S&F in repairs wall mounted LED batten, extruded aluminium heat sink provided for efficient heat dissipation & intgrated electronic driver 20W LED Model NoLHEWEBP6IN1W020 Make HAVELLS complete with all accessories internaly prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size including flourescent tube.
S&F in repairs outdoor type LED security light fitting of 35 watts comprising of epoxy powder coated hsg, enclosed with glass cover in frame , with protection complete with all accessories and lamp colour white and fixing all as specified and directed . make Havells or eqivalent of Bajaj/CG.
Earthing complete with galvanized steel earth plate electrode 60cmX60cmX6.3 mm thick buried in ground vertically to a depth not less than 2.25 metre below normal ground level, normal with top edge of earth plate not less than 1.5 metre below normal ground level, earth plate connected to a galvanised earth lead wire 4mm dia bymeans of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 of MES SSR Part-I (2009) connected to earth test point all as specified or indicated including testing on completion with and including 15 mm bore light grade GI protection pipe 7.5 meters long for earth including PCC 1:2:4 pit with pre cast RCC 1:2:4 type B1 cover 40 mm thick reinforced with 6mm dia MS bars @ 100mm both ways with lifting hook made out of 6mm dia MS bars watering arrangement with funnel wire, common salt and charcoal filling, necessary excavation and earth work in any type of soil incl taking down unsv earthing complete all as specified.
M&L in repairs earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthling etc. as required 4 mm dia galvanised iron or steel wire
Taking down carefully aluminium/ copper wiring / power point wiring (light, fan, call bell socket or power circuits) complete and making good the disturbed surface of walls, ceiling etc incl painting with same colour of the back ground complete all as specified and as directed by Engineer-in-Charge
Supply & fix Modular switch, one module, one way 16 Amps, 240 volts all as specified and as directed.
Supply & Fix GI bracket made of 25 mm bore light grade GI pipe1.5 mtr long suitably bent to shape and fixed on wall for fixing building security light fitting with 2 Nos suitable MS clamps of size 25 x 3 mm size with bolts, nuts, washers including taking down old unserviceable brackets all as specified and as directed.
G K CONSTRUCTIONS
C R R CONSTRUCTIONS
SREE VARU ELECTRICALS
Vasavi Electricals
UNIVERSAL ENGINEERING
M/S SIRI BUILDERS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .