GE DSSC
GE DSSC WELLINGTON BARRACKS POST, WELLINGTON, THE NILGIRIS, PIN 643 231.
SPECIAL REPAIRS TO LT PANEL BOARD, FEEDER PILLAR BOX, SWITCH GEARS WITH CONNECTING ACCESSORIES, REPLACEMENT OF CONVENTIONAL FITTINGS TO LED FITTINGS AT INSIDE COLLEGE AND ADJOINING AREAS, MEMORIAL VIEW, RV, KINARA ETC AT DSSC WELLINGTON.
2019_MES_298313_1
8079/E8
Open Tender
Civil Works
Item Rate
120 days
WELLINGTON
PLEASE REFER TENDER DOCUMENT AND NIT
8 documents required · 8 mandatory
₹500
GE DSSC WELLINGTON
₹84,000
Yes
9 Sept 2020
16 Nov 2019
9 Dec 2019
16 Nov 2019
7 Dec 2019
23 Nov 2019
Amount
Supply, install, testing & commissioning of LT control panel board "out-door type" of size 1500 mm (height) x 1200 mm (breadth) x 500 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming ACB/MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) complete all as specified & as directed with & including the following accessories :
(i) (FILTER HOUSE MAIN DG DISTRIBUTION PANEL) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 400 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 200 to 250 A - 01 Nos. Make : L & T, Cat No : CM92109OOP1OG or techno-commercially equivalent of Legrand /Siemens. (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 250 Amps, 415 Volts, 4 Pole, AC 23A - 01 No. Make : L & T, Cat No : CO32500OOOO or equivalent in ABB/ Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 32 to 40 Amps - 02 Nos. Make : L & T, Cat No : CM91712OOFOOG or techno-commercially equivalent of Legrand /Siemens.
(b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 40 to 50 A - 01 No. Make : L & T, Cat No : CM91712OOGOOG or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 50 to 63 A - 02 Nos. Make : L & T, Cat No : CM91712OOHOOG or techno-commercially equivalent of Legrand /Siemens. (d) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 02 Nos. Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens. (e) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 100 to 125 A - 03 Nos. Make : L & T, Cat No : CM92108OOL1OG or techno-commercially equivalent of Legrand /Siemens. (f) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 36 KA & of rating 125 to 160 A - 02 Nos (1W+1S). Make : L & T, Cat No : CM92108OOM1OG or techno-commercially equivalent of Legrand /Siemens. (g) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete. Make : L&T /Legrand /Siemens. (h) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand /Siemens. (j) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
All as per item No 1 here in before but with & including the following accessories : (LT Panel near FSH) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 400 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.
PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 200 to 250 A - 01 No. Make : L & T, Cat No : CM92109OOP1OG or techno-commercially equivalent of Legrand /Siemens. (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 250 Amps, 415 Volts, 4 Pole, AC 23 Amps - 01 No. Make : L & T, Cat No : CO32500OOOO or equivalent of ABB /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 32 to 40 Amps - 02 Nos. Make : L & T, Cat No : CM91712OOFOOG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 50 to 63 A - 03 Nos. Make : L & T, Cat No : CM91712OOHOOG or techno-commercially equivalent of Legrand /Siemens.
All as per item No 1 here in before but with & including the following accessories : (LT Panel near Pines) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 400 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 36 KA & of rating 250 to 320 Amps - 01 No. Make : L & T, Cat No : CM98401OOQOOG or techno-commercially equivalent of Legrand /Siemens. (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 315 Amps, 415 Volts, 4 Pole, AC 23 Amps - 01 No. Make : L & T, Cat No : CO33150OOOO or equivalent of ABB/Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 32 to 40 Amps - 02 Nos (1W+1S). Make : L & T, Cat No : CM91712OOFOOG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 160 to 200 Amps - 01 No. Make : L & T, Cat No : CM92109OOP1OG or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 200 to 250 Amps - 02 Nos (1W+1S). Make : L & T, Cat No : CM92109OOP1OG or techno-commercially equivalent of Legrand /Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand/Siemens.
All as per item No 1 here in before but with & including the following accessories : (LT Panel near Iscoyd) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 600 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 36 KA & of rating 320 to 400 Amps - 01 No. Make : L & T, Cat No : CM98403OOROOG or techno-commercially equivalent of Legrand /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 32 to 40 Amps - 05 Nos. Make : L & T, Cat No : CM91712OOFOOG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 40 to 50 Amps - 02 Nos (1W+1S). Make : L & T, Cat No : CM91712OOGOOG or techno-commercially equivalent of Legrand/Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 36 KA & of rating 250 to 320 Amps - 04 Nos (3W+1S). Make : L & T, Cat No : CM98403OOQOOG or techno-commercially equivalent of Legrand/Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand /Siemens.
All as per item No 1 here in before but with & including the following accessories : (LT Panel backside of Woodside) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 500 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 250 to 320 A - 01 No. Make : L & T, Cat No : CM98403OOQOOG or techno-commercially equivalent of Legrand /Siemens. (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 315 Amps, 415 Volts, 4 Pole, AC 23 Amps - 01 No. Make : L & T, Cat No : CO33150OOOO or equivalent of ABB/Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 32 to 40 Amps - 01 No. Make : L & T, Cat No : CM91712OOFOOG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 50 to 63 Amps - 03 Nos (2W+1S). Make : L & T, Cat No : CM91712OOHOOG or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 200 to 250 Amps - 02 Nos (1W+1S). Make : L & T, Cat No : CM92109OOP1OG or techno-commercially equivalent of Legrand /Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand /Siemens.
All as per item No 1 here in before but with & including the following accessories : (GH PH S/S 400 KVA TR) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 800 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with microprocessor release, adjustable short circuit & adjustable overload setting, suitable for isolation, inbuilt instantaneous protection, having breaking capacity 50 KA & of rating 320 to 800 Amps - 01 No. Make : L & T, Cat No : CM96111OOOOX1 or techno-commercially equivalent of Legrand /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 Amps - 01 No. Make : Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 40 to 50 Amps - 01 No. Make: L & T, Cat No : CM91712OOGOOG or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 100 to 125 Amps - 01 No. Make : L & T, Cat No : CM92108OOL1OG or techno-commercially equivalent of Legrand /Siemens. (d) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 36 KA & of rating 125 to 160 Amps - 01 No. Make : L & T, Cat No : CM92108OOM1OG or techno-commercially equivalent of Legrand /Siemens.
All as per item No 1 here in before but with & including the following accessories : (GH PH S/S 300 KVA TR) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 700 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 36 KA & of rating 500 to 630 Amps - 01 No. Make : L & T, Cat No : CM94106OOT1OG or techno-commercially equivalent of Legrand /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 200 to 250 Amps - 03 Nos (2W +1S). Make : L & T, Cat No : CM92109OOP1OG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 160 to 200 Amps - 01 No. Make : L & T, Cat No : CM92108OOM1OG or techno-commercially equivalent of Legrand /Siemens. (c) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete. Make : L&T/Legrand /Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand /Siemens. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 Nos. Make : L&T /Legrand/ Siemens.
All as per item No 1 here in before but with & including the following accessories : (S/S NO-05 200 KVA TR/1) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 500 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 36 KA & of rating 320 to 400 Amps - 01 No. Make : L & T, Cat No : CM98403OOROOG or techno-commercially equivalent of Legrand /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 100 to 125 Amps - 03 Nos (2W+1S). Make : L & T, Cat No : CM92108OOL1OG or techno-commercially equivalent of Legrand /Siemens. (b) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete. Make : L&T/Legrand /Siemens. (c) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T /Legrand/Siemens. (d) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T/Legrand /Siemens.
All as per item No 1 here in before but with & including the following accessories : (S/S NO-05 200 KVA TR/2) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 500 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 320 to 400 Amps - 01 No. Make : L & T, Cat No : CM98403OOROOG or techno-commercially equivalent of Legrand /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 100 to 125 Amps - 01 No. Make : L & T, Cat No : CM92108OOL1OG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 125 to 160 Amps - 02 Nos (1W +1S). Make : L & T, Cat No : CM92108OOM1OG or techno-commercially equivalent of Legrand /Siemens. (c) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete. Make : L&T /Legrand /Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T /Legrand /Siemens. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T /Legrand /Siemens.
All as per item No 1 here in before but with & including the following accessories : (S/S NO-06 200 KVA TR) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 500 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 320 to 400 Amps - 01 No. Make : L & T, Cat No : CM98403OOROOG or techno-commercially equivalent of Legrand /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 160 to 200 Amps - 02 Nos (1W +1S). Make : L & T, Cat No : CM92108OOM1OG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 125 to 160 Amps - 01 No. Make : L & T, Cat No : CM92108OOM1OG or techno-commercially equivalent of Legrand /Siemens. (c) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 80 to 100 Amps - 01 No. Make : L & T, Cat No : CM91712OOKOOG or techno-commercially equivalent of Legrand /Siemens. (d) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 40 to 50 Amps - 01 No. Make : L & T, Cat No : CM91712OOGOOG or techno-commercially equivalent of Legrand /Siemens. (e) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete. Make : L&T /Legrand /Siemens. (f) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps- 02 Nos. Make : L&T /Legrand /Siemens. (g) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
All as per item No 1 here in before but with & including the following accessories : (CTL S/S 200 KVA TR) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 500 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 320 to 400 Amps - 01 No. Make : L & T, Cat No : CM98403OOROOG or techno-commercially equivalent of Legrand /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 125 to 160 Amps - 02 Nos (1W +1S). Make : L & T, Cat No : CM92108OOM1OG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 50 to 63 Amps - 03 Nos. Make : L & T, Cat No : CM91712OOHOOG or techno-commercially equivalent of Legrand /Siemens. (c) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete. Make : L&T /Legrand /Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand /Siemens. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T /Legrand/Siemens.
All as per item No 1 here in before but with & including the following accessories : (Gorkha Camp S/S 200 KVA TR) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 500 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 320 to 400 Amps - 01 No. Make : L & T, Cat No : CM98403OOROOG or techno-commercially equivalent of Legrand /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 50 to 63 Amps - 02 Nos (1W +1S). Make : L & T, Cat No : CM91712OOHOOG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 32 to 40 Amps- 04 Nos. Make : L & T, Cat No : CM91712OOFOOG or techno-commercially equivalent of Legrand /Siemens. (c) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete. Make : L&T /Legrand /Siemens. (d) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T /Legrand /Siemens. (e) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand /Siemens.
All as per item No 1 here in before but with & including the following accessories : (LT Panel near PB-15, PA-16, CSQ 1 to 3) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 200 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 100 to 125 Amps - 01 No. Make : L & T, Cat No : CM92108OOL1OG or techno-commercially equivalent of Legrand /Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 32 to 40 Amps - 07 Nos (5W +2S). Make : L & T, Cat No : CM91712OOFOOG or techno-commercially equivalent of Legrand /Siemens. (b) Time switch 415 Volts, 3 Phase of 20 Amps rating with Contactor complete. Make : L&T /Legrand /Siemens. (c) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand /Siemens. (d) MCB TPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 01 No. Make : L&T /Legrand/Siemens.
All as per item 1 here in before but of size 1200 mm (height) x 1000 mm (breadth) x 500 mm (depth) (minimum dimensions) with & including the following accessories : (LT Panel near RP FSH) BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 200 Amps rated, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 36 KA & of rating 100 to 125 Amps - 01 No. Make : L & T, Cat No : CM92108OOL1OG or techno-commercially equivalent of Legrand /Siemens. (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 160 Amps, 415 Volts, 4 Pole, AC 23 Amps - 01 No. Make : L & T, Cat No : CO21600OOOO or equivalent of ABB/Siemens. OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 50 to 63 Amps - 01 No. Make : L & T, Cat No : CM91712OOHOOG or techno-commercially equivalent of Legrand /Siemens. (b) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 Amps - 02 Nos (1W+1S). Make : L & T, Cat No : CM91712OOJOOG or techno-commercially equivalent of Legrand /Siemens. (c) MCB SPN "C" series having breaking capacity 10 KA of rating 06 to 32 Amps - 02 Nos. Make : L&T/Legrand /Siemens.
Supply, install, commissioning & testing of CPRI type tested maintenance free, low carbon copper coated earth rod of 3.0 metre electrode having diameter 17.2 mm with copper coating thickness of 250 micron tested as per IEC 62561-2 provided with universal clamp made of SS to connect earth rod with the flat conductor. Earth conductivity enhancing compound shall be of 25 Kg/pit & tested as per IEC 62561-7, TCLP tested. The above arrangements shall be provided with heavy duty earth chamber of 5000 Kg load bearing capacity complete including excavation, returning & filling & removal of earth all as specified & as directed by the Engr-in-Charge. Make : OBO, Cat Part Nos : 5450012, 5450068, 5450058 & 5450030 (for different components) or techno-commercially equivalent.
IMPORTANT NOTES : (i) Design / drawing / BOM of the complete Chemical Earthing system showing the layout & dimensions is to be obtained from OEM strictly keeping in view the actual ground/site requirement & the same is to be got approved from Engr-in-Charge before placing final order to the manufacturer. (ii) Anything missed out in the technical specifications but technically required for efficient working of the earthing system is deemed to be included in the quoted rates. (iii) The entire installation & testing work is to be got done from the OEM or their auth Rep/Sister Concern/Channel Partners only. (iv) The quantity of earth conductivity enhancing compound indicated above is generally for normal/good soils. In case the soil resistivity is high, the quantity should be increased & cost of the same is deemed to be included in the unit quoted rates. (v) On completion of the complete work/job the Contr is to perform earth resistance tests for each earthing job in the presence of the Engr-In-Charge or his rep & submit test certificates duly signed & certified. If the test results are not satisfactory or not within the permissible limits of relevant Standards/IS then the job is to be redone without any extra cost to the Dept till the results are satisfactory.
S & F 32 x 6 mm galvanised iron strip as earth continuity conductor including connection complete with the help of chromium plated washers, nuts etc. to Transformer Body /Neutal , Generator Body /Neutral etc., complete all as specified and as directed.
S & F 40 mm dia GI pipe light grade on walls, floors under ducts/culverts etc. for protection of earthing lead complete all as specified and as directed. Make : TATA/JINDAL/PRAKASH.
M & L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6.3 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L.) and connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC (1:2:4) type B1 earth chamber with pre cast RCC cover slab incl suitable reinforcement and handle made out of 8mm dia round bar, including necessary excavation and earth work in any type of soil, 20 mm dia medium grade galvanized steel tube for watering with one end fixed with cast iron funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection (upto 7.5m long) & common salt, charcoal in alternate layers etc. complete all as shown in Electric Plate No 3 of SSR Part 1 and testing on completion complete all as specified and as directed. Note: If the desired earth resistance is not obtained, the earthing is to be redone at no additional cost, to the entire satisfaction of Engr-in-Charge.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed. Make : HAVELLS/GLOSTER/POLYCAB.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed. Make : HAVELLS/GLOSTER/POLYCAB.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 Sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed. Make : HAVELLS/GLOSTER/POLYCAB.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 Sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed. Make : HAVELLS/GLOSTER/POLYCAB.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sq mm 4.0 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed. Make : HAVELLS/GLOSTER/POLYCAB.
Supply, laying, jointing & testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 Sq mm 3.5 core in trenches / through GI pipe / fixed along with pole structure etc with all fixing & connecting accessories complete all as specified & as directed. Make : HAVELLS/GLOSTER/POLYCAB.
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for laying of pipe and getting out in hard/ dense soil complete all as specified and as directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick with excavated soil all as specified and as directed.
Removing of excavated material (soil) to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point all as specified and as directed.
M & L for boring under road manually with labour suitable for inserting 100 mm bore pipe at a depth 0.75 to 1.0 mtr complete all as specified and as directed.
S & F for GI pipe light grade 80mm bore with all running fittings (ISI Marked), laid in trenches, under road or fixing on wall/pole/crossing drain/nallah etc., complete all as specified and directed. Make : TATA/JINDAL/PRAKASH.
S & F for GI pipe light grade 50mm bore with all running fittings (ISI Marked), laid in trenches, under road or fixing on wall/pole/crossing drain/nallah etc., complete all as specified and directed. Make : TATA/JINDAL/PRAKASH.
Supply, spreading and compacting of approved river bed sand or M sand in trenches for cable cushion on both top and bottom of cable, including ramming for protection of UG cable all as specified and as directed by Engineer-in Charge. Note : Punned thickness shall be measured.
Supply and laying sub class "B" bricks in trenches for protection of UG Cable with width equal to length of bricks, laid dry & flat complete all as specified & as directed.
Taking down carefully by unscrewing from boards/ outlet boxes, fittings and fixtures such as lamp holders, brackets, ceiling fittings, bulk head fittings, tube light fittings etc. removing materials for taking credit all as specified and as directed.
S & F Wall mounted LED batten with integrated electronic driver & diffused optics complete with all accessories, prewired, including 10 W 2 feet tube light and flexible wire twin core with and including flexible hose pipe from ceiling rose to fitting complete all as specified and as directed. Make: Havells, Cat No: ENDURALINEARNEO BS10WLED865SPCWH or techno-commercially equivalent in Philips /Luker.
S & F Wall mounted LED batten with integrated electronic driver & diffused optics complete with all accessories, prewired, including 20 W, 6000 K LED 4 feet tube light and flexible wire twin core with and including flexible hose pipe from ceiling rose to fitting complete all as specified and as directed. Make: Havells, Cat No: ENDURALINEARNEO BS20WLED840SPCWH or techno-commercially equivalent in Philips/Luker.
S & F surface mount down light LED 10 W with white powder coated polycorbonate housing and pressure die cast heat sink having high efficency complete all as specified and as directed. Make: Havells, Cat No: INTEGRANEOSURFA CEDLS10WLED857S or techno-commercially equivalent in Philips/Luker.
S & F energy saving new generation 10W LED, 6000K bulk head luminaire with opal diffuser with and including lamp 10W LED 6000k complete all as specified and as directed. Make: Havells, Cat No: RUGBYNEONFT10W LED860SSYMTOPC or techno-commercially equivalent in Philips/Luker.
S & F wall mounting Bed side Decorative fixture SS finish with opal glass diffuser with and including 3 W warm white LED lamps of E14 Cap all as specified and as directed. Make : Havells, Cat No : LHJE01106499( For Fixture), or equivalent in Philips/Luker. Make : Havells, Cat No:LHLDEROEMD9X003 (For Lamps) or equivalent in Philips/Luker.
S & F wall mounting Decorative fixture SS finish with with textured glass diffuser with and including 5 W warm white LED lamps of E14 Cap all as specified and as directed. Make : Havells, Cat No : LHJE04104499 ( For Fixture), or techno-commercially equivalent in Philips/Luker. Make : Havells, Cat No: LHLDERUEML8X005 (For Lamps) or techno-commercially equivalent in Philips/Luker .
S & F energy saving and environment friendly long life LED security light of 25W made up of pressure die cast aluminum housing with acrylic cover as diffuser with IP 66 protection including suitable brackets and clamps all as specified and directed including electric connection complete with & including flexible hose pipe from ceiling rose to fitting. Make: Havells, Cat No: ENDURAPEARLSL 25WLED757SASYTOPC or techno-commercially equivalent in Philips/Luker.
Refixing of existing Servicable LED fitting at existing or different location after proper cleaning and check the serviceable status all as specified and as directed by Engr-in-charge.
S & F of ceiling rose surface mounted PVC / polycarbonate, isolated body with face bakelite three terminal complete all as specified and directed. Make : Havells/ Anchor/CG/C&S/Legrand
SVG CONTROL SYSTEMS PRIVATE LIMITD
M/s.Rejoy Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .