Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.5 LAccepted-AOC RAJBARI PARA JALPAIGURI | JALPAIGURI | JALPAIGURI | WEST BENGAL | L1 | Accepted-AOC L1 BIDDER | |
| 2 | L2₹21.5 L+₹1,280 (0.06%)Rejected-Finance 344 1 SB GORAI ROAD HILL VIEW PARK NORTH ASANSOL | ASANSOL | WEST BENGAL | L2 | Rejected-Finance NOT L1 BIDDER | |
| 3 | L3₹21.5 L+₹4,728 (0.22%)Rejected-Finance 181 SREEPALLY MAIN ROAD ASANSOL 4 | ASANSOL | L3 | Rejected-Finance NOT L1 BIDDER | |
| 4 | L4₹21.5 L+₹7,678 (0.36%)Rejected-Finance 778 N LOWER CHELIDANGA ASANSOL PASCHIM BARDHAMAN | ASANSOL | PASCHIM BARDHAMAN | WEST BENGAL | L4 | Rejected-Finance NOT L1 BIDDER |
Tender Value
Refer Docs
EMD Value
₹43,000
Closing Date
21 Jan 2025, 4:00 pmClosed
Executive Engineer,AMD P.H.E Dte
Office of the Executive Engineer,Asansol Mechanical Division,Public Health Engineering Directorate,JANASASTHYA KARIGORI BHAVAN SEN-RALEIGH ROAD PASCHIM BARDHAMAN 713 305
Operation and maintenance of Sub-Station (11 KV/0.433 KV,3X 1250KVA Transformer) and other Electrical Accessories at Kalajharia under RCFA Part- II Water Supply Scheme.
2024_PHED_791980_19
WBPHED/EE/AMD/NIeT-40 of 2024-2025
Open Tender
Miscellaneous Works
Item Wise
365 days
Kalajharia
Please refer Tender documents.
4 documents required · 4 mandatory
₹43,000
12 Mar 2025
30 Dec 2024
24 Jan 2025
30 Dec 2024
21 Jan 2025
30 Dec 2024
Amount
Daily labour charges with bonus once in a year for operation of 11/0.433 KV , comprising of 3 nos 1250 KVA indoor type transformer along with 1 no. HT VCB, along with LT PDB Panel having ACBs of 2000A, 1600A and 1000A, MCCBs of 400A, 630A, 250A along with APFC panel including operation of all other electrical accessories and ancilliaries for 24 hours a day. (6 Nos. Operator and 1 No. Electrician to be engaged)
Periodical inspection twice in a month by electrical supervisor having valid suprevisor's certificate of competency from directorate of Electricity (Licensing board),govt. of West Bengal or under any other State Government of India along with Pump Technician / Supervisor. Each Visit should be recorded in the log book (with date and time) to be supplied by the agency and kept in the pump house building . The Supervisor requires to have thorough / in-depth instruction of all the electrical appliances to ascertain the healthy / fault free operational condition of each equipment i.e. 630 Amp HT VCB, LT PDB Panel having 2000 amp , 1600 amp & 1000 amp ACBs, MCCBs of 630 amp, 400 amp and 250 amp ,APFC panel, different relays, contactors, timers, SFU along with in house lighting system including cleaning of contacts by CRC 226 spray in HT& LT panels cleaning of all terminal socket and checking of healthy condition of all drawout feeders.
Day to day maintenance for upkeepment of all electrical & mechanical installation by engaging licensed electrician / machanic as and when required by providing all necessary incidental charges including supplying CRC-226, control Fuses, safety Gloves etc.as required to execute maintenance as well as guarding work.
Testing of all relays viz. earth fall, over load, buchholz, and chacking of muster trip,trips circuit Supervisor, CT, PT, spring charging system, closing/trips coil, ACB ,and breaker of L.T. Panel, , Di-electric test of transformer oil , APFC Panel, etc. including calibration of Ammeter, Voltmeter etc. by agency approved by Directorate of Electriciity/ WBSEDCL/Any Power Generating Unit once in six month and submission of the Test Report to Department in each case.
EASTERN INDIA SALES AND SERVICE (BID ID -5977609)
Ciemenics (BID ID -5954654)
M/s. SOMA ENTERPRISE (BID ID -5954692)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .