Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹82.1 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹91.7 L+₹9.6 L (11.7%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | L3₹93.0 L+₹11.0 L (13.4%)Admitted-Finance 1ST FLOOR KRISHNA TOWERS OPP TO THRIKKAKARA TEMPLE THRIKKAKARA P O COCHIN 682 021 | ERNAKULAM | KERALA | 682021 | L3 | Admitted-Finance | |
| 4 | Rejected-Technical | - | Rejected-Technical Not Eligible As per NIT criteria | |
| 5 | Not Admitted-Fee/PreQual/Technical 301 VARDHAMAN CHAMBER II VIKASPURI NEW DELHI 110018 | WEST | DELHI | 110018 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹1.9 L
Closing Date
5 Jun 2020, 6:00 pmClosed
AGM Engg E-I,SIA
Srinagar Intl Aiport, Srinagar
Annual Operation and maintenance of HVAC system, VRF System, Fire Alarm and Fire Fighting system, Split/Window ACs and Water Coolers etc. at Srinagar Intl Airport, Srinagar. (FOR THE YEAR 2020-21 and 2021-22)
2020_AAI_46125_1
AAI/SNR/Engg-E/HVAC
Open Tender
Electrical Works
Item Rate
730 days
Srinagar Intl Aiport, Srinagar
Please refer Tender documents.
18 documents required · 18 mandatory
₹1,120
Yes
AAI
₹1.9 L
Yes
26 Jun 2020
19 Mar 2020
12 Jun 2020
20 Mar 2020
5 Jun 2020
20 Mar 2020
20 Mar 2020 - 26 May 2020
Amount
SH-A: ARMO of HVAC Plant. Annual Operation and maintenance of HVAC system comprising of HSD Oil Fired 04 nos. each unit of 10 Lac K cal / Hr capacity hot brine generator, central Chiller Plant of capacity 3x200 TR capacity, 25 nos of AHU's of different capacities, brine make up pump, primary and secondary brine curculating pump, handling of HSD oil in under ground storage tank in General/shift duty on all working days i/c Saturdays, Sundays, Gazetted holidays & National holidays , The contractor has to deploy the following minimum man power (with one weekly off) (including Reliever) for the work to the entire satisfaction of the Engineer-in-Charge. (i) Supervisor (Highly Skilled) :- 01 no. (ii) A/C Operator (Skilled) :- 04 no. (iii) Helper (un-Skilled):- 04 no.
Servicing of central heating plant once in a year comprising of 04 nos. HSD oil fired 10 lakh K. Cal./ hour capacity hot brine generator 1No. Heat Exchanger installed in heating plant room, complete all as per scope of work given in the special condition of contract.
Repairing & Rewinding of following Hot/ Chilled Water circulating Centrifugal Pump set including, dismantling, repairing of shaft, replacing of defective mechanical seals,bearing, nuts, bolts, gaskets, gland etc complete as required. a) 3 Phase Induction motor, Make Crompton greaves/ ABB 20/15HP Motor, 1460RPM, 415V, +/- 10%, Frame ND160M,Centrifugal pump, Make Beacon Weir Ltd, Type BWC 80-100, Total Head 28 Metre, Capacity 25 lps, speed 1450rpm, Input 8.79BKW,EFF 79%
Supply, installation, commissioning of site fabricated GSS sheet metal rectangular/round ducting complete with vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. a) Thickness 0.63 mm sheet
Repairing of Following sizes of 3 Phase Induction motor, set including, rewinding of motor, dismantling, repairing of shaft, replacing of defective mechanical seals,bearing, nuts, bolts, gaskets, gland etc complete as required. (Rates also includes tranportation charges of motor upto workshop & taking back & fixing of motor in AHU Room)
25HP Motor
20HP Motor
15HP Motor
10HP Motor
7.5HP Motor
SH-B: Operation & Maintenance of Automatic Fire detection, fire alarm and fire hydrant ,sprinkler system etc Annual Operation and Maintenance of Automatic Addressable Fire Alarm & Detection system, Fire Hydrant & Fire Fighting system and automatic sprinkler system installed in Terminal Building including monitoring of control panel, Zonal panels, smoke/heat detectors, RI, manual call point, hooters, Isolator, etc. General/shift duty i/c maintaining log book etc and maintenance of the system. The contractor has to deploy the following minimum man power on all working days i/c Saturdays, Sundays, Gazetted holidays & National holidays (with one weekly off) (including Reliever) for the work to the entire satisfaction of the Engineer-in-Charge. (i) Electrician cum Operator (Skilled) - 04 No. (ii) Helper- (un-Skilled)- 02 Nos.
Carrying out of "B-check" maintenance of Kirloskar make Diesel engine pump set anually of 53 KW/ 72 HP capacity including supply and fixing of element fuel/oil filter, kit air cleaner, by pass filter including supply & replacement of lub oil etc. for the DG set as required. (B-check will be carried out by Authorised dealer of Kirloskar company or by OEM).
SH-C: ACMC of A/C's & Water coolers. Annual Comprehensive maintenance of 1.0/1.5 /2.0 ton split type Air conditioner units including the replacement of defective components supply and replacement of defective compressors by company Make compressor i/c comprehensive maintenance of voltage stabilizer for above units (wherever installed) complete as per inventory.
For the year 2020-21 (12 Months)
For the year 2021-22 (12 Months)
Annual Comprehensive maintenance of 3.0/ 4.0, 4.5/4.6 ton Tower type split Air conditioner units including supply and replacement of defective components and supply and replacement of defective compressors by company repaired compressor complete as required, as per inventory.
For the year 2020-21 (12 Months)
For the year 2021-22 (12 Months)
Annual Comprehensive maintenance of 3.0 ton Cassette type split Air conditioner units including supply and replacement of defective components and supply and replacement of defective compressors by company repaired compressor complete as required, as per inventory.
For the year 2020-21 (12 Months)
For the year 2021-22 (12 Months)
Annual Comprehensive maintenance of water coolers of different capacity & make including supply and replacement of defective components and replacement of defective compressors by company Make compressor i/c maintenance of voltage stabilizer for above units (wherever installed) complete as reqd, as per inventory.
For the year 2020-21 (12 Months)
For the year 2021-22 (12 Months)
Shifting of 1.5/2.0 TR air conditioing unit by dismentalling it from existing location and re-installation to new location complete along with stablizer, filling / topup of refrigerant, testing and commissioing etc as required. ( Required excess gas and pipe will be measured seperatly.)
Split Type unit
Supply of R-22 refrigerant suitable for airconditioning and water cooler units as and when required.
Supply and fixing of suction and discharge copper piping with suitable insulation and of suitable size as required.
Supply and fixing of 25mm hard PVC drain pipe complete as required .
SH-D: AICMC OF VRF System. AICMC of Variable Refrigerant Flow modular type airconditioning system of (TOSHIBA Make) i/c outdoor units (Hi side) ODU - 24 HP(Comprising 3 Nos.8 HP units) (19.2 TR Nominal Cooling Capacity) and indoor units (Ceiling Mounted 6 nos. Cassette Units) Ceiling Mounted Cassette Four Way Flow with Cassette Panel 3.2 TR Cooling Capacity with 1130 cfm airflow complete with Corded Remote Controller.Refrigerant Piping for VRV/VRF System, Transmission Control Wiring, Y-Joints etc complete as required.
For One Year 2020-21 (12 Months)
For One Year 2021-22 (12 Months)
V Save Electronics Pvt Ltd
Sterling and Wilson Pvt. Ltd
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .