Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.0 LAccepted-AOC | L1 | Accepted-AOC Being a lowest bidder | |
| 2 | L2₹21.5 L+₹4.1 L (23.6%)Rejected-Finance | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹23.8 L+₹6.4 L (37.0%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹26.5 L+₹9.1 L (52.6%)Rejected-Finance | L4 | Rejected-Finance Other than lowest bidder | |
| 5 | L5₹29.7 L+₹12.3 L (70.5%)Rejected-Finance 02 JAMEEWAR COMPLEX RING ROAD HANUMAN NAGAR GONDIA MAHARASHTRA 441614 | GONDIA | MAHARASHTRA | 441614 | L5 | Rejected-Finance Other than lowest bidder |
Tender Value
₹29 L
EMD Value
₹58,000
Closing Date
20 Jul 2024, 6:00 pmClosed
GE (AF) Bamrauli
GE (AF) Bamrauli
REPAIR/MAINT TO INTERNAL ELECTRIFICATION SYSTEM OF MD ACCN NORTH CAMP, AIR ENCLAVE, OTM ACCN, SMQS SOUTH CAMP, 4 AFSR, BILLETS AND ADJOINING AREA AT AF STN BAMRAULI
2024_MES_662845_1
8911/E8
Open Tender
Civil Works - Others
Works
180 days
GE (AF) Bamrauli
Please refer tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Bamrauli
₹58,000
Yes
26 Oct 2024
29 Jun 2024
22 Jul 2024
29 Jun 2024
20 Jul 2024
13 Jul 2024
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc.
M&L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through new PVC concealed conduit mediem grade, ISI marked and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty, fabricated branded modular metal flush box duly make embossed, concealed in walls with suitable modular inner and outer plate for housing switches , socket outlet and fan regulators etc, complete all as specified and as directed for the followings:-
(a) One light, fan, bell point controlled by one switch.
(b) One 3 pin switch socket outlet point 5 Amps on independent board.
(c) One 3 pin switch socket outlet point 5 Amps on same board with other switch.
All as per item No 2 above here in before but with copper conductor cable for one 3 pin socket outlet, 15 amp independent, with cable 2.5 Sqmm size.
M&L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through new PVC casing caping mediem grade, ISI marked and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty, fabricated branded modular metal flush box duly make embossed, concealed in walls with suitable modular inner and outer plate for housing switches , socket outlet and fan regulators etc, complete all as specified and as directed for the followings:-
(a) One light, fan, bell point controlled by one switch.
(b) One 3 pin switch socket outlet point 5 Amps on independent board.
(c) One 3 pin switch socket outlet point 5 Amps on same board with other switch.
All as per item No 4 above here in before but with copper conductor cable for one 3 pin socket outlet, 15 amp independent, with cable 2.5 Sqmm size.
S&F in repair Switch piano 6 amps, single pole, one way, 230 volts
S&F in repair Switch piano 16 amps, single pole, one way 230 volts
S&F in repair Socket outlet 6 Amp 2pin & 3 pin, flush type
S&F in repair Socket out let, 16 amp and 6 amp, flush type
S&F in repair Electronic fan regulator 5 step 230 volts,switch type
S&F in repair Electronic fan regulator 5 step 230 volts, socket size
S&F in replacement Switch socket combination 2 IN 1 3 PIN 6/16 Amp 220 Volt flush type.
S&F in repair Lamp holder, insulated body, with back plate 230 Volt suitable for batten fittings.
S&F in repair Capacitor 230 volt, 1 Mfd all as specified and directed by Engr-in-Charge.
S&F in repair Capacitor 230 volt, 2.5 Mfd for ceiling fans
S&F in repair Capacitor 230 volt, 3.15 Mfd for ceiling fans
S&F in repair Switch modular type, 230 volts, single pole, one way, 10 Amp, one module.
S&F in repair Switch modular type, 230 volts, single pole, one way, 16 Amp one module.
S&F in repair Socket out let 5 pin, 10 Amp, 230 volts modular type.
S&F in repair Socket out let 5 pin, 10 amp & 20 amp, 230 volts modular type.
S&F in repair Modular Fan step regulator, 120W - 2 module complete all as specified and directed.
S&F ceiling rose surface backlite 65x50mm 3 terminals complete.
S&F in replacement PVC box comprising of switch socket combination multi - purpose 5 pin, 6/16 Amp box type complete all as specified and as directed.
S&F in replacement PVC box comprising of switch socket combination multi - purpose 3 pin, 6 Amp box type complete all as specified and as directed.
S&F in replacement calling bell ding dong type 220 volt 50 Htz
S&F in replacement of driver for 2x2 feet LED panel of 36 watt of any model any make as par existing 240 volt 50 Htz 120 watt/lumen 6500k/2700k.
S&F in replacement driver/ballast suitable for LED light 18 Watt
S&F in replacement Rope light complete with adaptor.
S&F in repair LED batten luminaire surface mounted, 4 feet system wattage of 20 Watts, > 2200 systems lumen outputwith lifetime of 50000 burning including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed complete all as specified and directed.
S&F in repair LED batten luminaire surface mounted, 2 feet system wattage of 10 Watts, > 1000 systems lumen outputwith lifetime of 50000 burning including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed complete all as specified and directed.
S&F in repair 2x2 LED fitting recess mounting flate panel 36 watt, down light 240 volt 50 Htz 150 luumen/watt comprising driver locking arrangement prewired completely.
S&F adore LED lamp 3 star rating 5 watt lumen out put 500 Lm all as specified and directed by Engr-in-Charge.
S&F in replacement 18 Watt LED tube 4 pin type ultra bright LED PL-L with high efficacy suited for installation in existing 2G11 lamp holder Havells cat part No-PLL419TL18WLED 865SPC of equivelent make of Bajaj and Crompton as approved by GE.
S&F wall mounted decorative fancy type bedroom light LED type with frosted glass mounted on metalic frame with holder including 12 watt LED bulb Philips cat part No-45617 or equivelent list of make as approved by GE.
S&F bed side lamp LED 3 Watt all as specified and directed by Engr in Charge. Make Philipis Model No 48042/30/3 and eqvt particular specification.
S&F decorative wall light 2x 20 Watt TOR Compete all as specified and directed by Engr-in-Charge. Make Philips model No 3430/11C/86 and eqvt as specified in list of make and approved by GE.
S&F in replacement of Recess mounted complact vertical round shaped down light LED 5 watt suitable for low ceiling height complete all as specifie.
S&F in replacement of Recess mounted complact vertical round shaped down light LED 2 watt suitable for low ceiling height complete all as specifie.
S&F show case led lamp light 3 Wat complete all as spd and directed.
S&F in replacement of Recess mounted complact vertical round shaped down light LED 15 watt suitable for low ceiling height complete all as specifie.
S&F in replacement surface mounted, suare LED down light fitting12 watts with die cast aluminium housing and system wattage of 12W, including connecting up with PVC sheathed 3 core 1.5 Sqmm copper conductor flexible wire fixed complete all as specified and directed.
S&F in replacement PVC cable copper conductor multi strandrad flexible 23/76 twin core and making connections from ceiling rose to fan complete all as directed.
S&F in replacement 1.5 Sqmm FR PVC insulated stranded copper conductor cable 1100 volts grade all as specified and directed.
S&F in replacement 2.5 Sqmm FR PVC insulated stranded copper conductor cable 1100 volts grade all as specified and directed.
S&F in replacement 4.0 Sqmm FR PVC insulated stranded copper conductor cable 1100 volts grade all as specified and directed.
S&F in replacement 6.0 Sqmm FR PVC insulated stranded copper conductor cable 1100 volts grade all as specified and directed.
S&F in repair PVC gang box ISI marked three module for mounting one 5 amp socket & switch
S&F in repair PVC gang box ISI marked fourmodule for mounting one 15 amp socket & switch Make plaza/Anchor
S&F in repair PVC gang box ISI marked six module for mounting two 5 amp socket & two switch
S&F in repair PVC gang box ISI marked 9 module for mounting three 5 amp socket & three switch
S&F in replacement white cover plate with frame three module for modular switches and sockets complete all as specified and directed.
S&F in replacement white cover plate with frame six module for modular switches and sockets complete all as specified and directed.
S&F in replacement white cover plate with frame twelve module for modular switches and sockets complete all as specified and directed.
S&F metal flush box three module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
S&F metal flush box six module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
S&F metal flush box twelve module 1.6 mm for mounting modular switches and sockets complete all as specified and directed.
Supply only hylum sheets 3 mm thick (ISI marked) 8" x 10" incl cuttings for switches and sockets 6/16Amps as directed.
Supply only hylum sheets 3 mm thick (ISI marked) 10" x 12" incl cuttings for switches and sockets 6/16Amps as directed.
S&F terminal box of 1.6 mm thick suitble size for fixing 3 mm thick hylam sheet complete all as specified
S&F bulkhead fitting enviornmental friendly, ultra modern, energy saving, surface mounted, decorative oval bulkhead edgelit LED luminaire comprising of highbrightness LEDs of 10 watt
S&F Sub main wiring with 2 run of single core PVC insulated and PVC Unsheathed, multistranded copper condutor of nominal area 6 sqmm FRLS, 1100 Volts grade cable drawn into and including rigid non metalic PVC Conduit of including all fittings and one run of PVC insulated and PVC unsheathed, multistranded copper conductor of nominal area 6 sqmm FRLS 1100 volts grade cable continuous earth wire of green colour code complete. Note:- (a) Two runs of 6.0 sqmm cable and one run of 6 Sqmm cable as earth lead with conduit shall be measured as one unit length for payment. (b) Quoted rate shall deem to be included cost of cutting chasses in wall for concealling conduit and making good to match with existing finish.
S&F Sub main wiring with 2 run of single core PVC insulated and PVC Unsheathed, multistranded copper condutor of nominal area 4 sqmm FRLS, 1100 Volts grade cable drawn into and including rigid non metalic PVC Conduit of including all fittings and one run of PVC insulated and PVC unsheathed, multistranded copper conductor of nominal area 4 sqmm FRLS 1100 volts grade cable continuous earth wire of green colour code complete. Note:- (a) Two runs of 4.0 sqmm cable and one run of 4 Sqmm cable as earth lead with conduit shall be measured as one unit length for payment. (b) Quoted rate shall deem to be included cost of cutting chasses in wall for concealling conduit and making good to match with existing finish.
S&F Factory made sheet metal enclosure distribution boards, (protection class IP-65) double door, vertiical type suitable for mounting isolator fixing MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, SP and N, 12 ways, 240 volts, Make Legrand/Hager/siemense Note : MCBs shall be measured and paid for separately under respective item of this schedule.
S&F Factory made sheet metal enclosure distribution boards, (protection class IP-65) double door, vertiical type suitable for mounting isolator fixing MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, SP and N, 8 ways, 240 volts,
S&F factory made epoxy powder coated Distribution board (MCCB DB) TPN 4 way vertical type, IP - 43 Protection made out of min 1.6 mm thick CRCA sheet, fabricated, metal double door fixed to wall and suitable for universal mounting and including 200 Amps rated copper bus bar, neutral bar, standard DIN rail, earth bar and cable ties for cable management, top and bottom removeable gland plated with knockouts and suitable for TPN MCCB 125/160 Amps as incomer and 12 SP or 04 Nos TP MCBS as outgoing complete all as specified and confirming to IS : 8623 complete all as specified and directed.
S&F MCCB, four pole, 415 Volt ,125 Amp rating, 10 KA ultimate breaking capacity fixed in DBs catered herein before.
S&F MCCB, four pole, 415 Volt ,100 Amp rating, 10 KA ultimate breaking capacity fixed in DBs catered herein before.
S&F MCB, tripple pole and neutral, 415 volts, 32 to 63 Amps rating, 10KA, "C" series fixed in DBs catered herein before.
S&F in replacement MCB, SP, 6 to 32 Amp rating, 230 volt, 10 KA, 'C' series fixed in DBs catered herein before.
S&F in replacement MCB, SP, 230 volts, 35 to 63 Amp rating, 10 KA, C series fixed in DBs catered herein before.
S&F MCB, single pole and neutral, 230 volts, 40 to 63 Amp rating, 'C' series fixed in DBs catered here-in-before.
S&F connecting and testing LED street light 30 watt 6000k new generation energy saving and enviornmental friendly long life versatile pressure die cast aluminium housing IP-66 roadway luminaries with high power LED as light source and electronic driver complete with connection and accessories for fixing with with including grade 40mm dia GI pipe as bracket in appropriate length complete including taking down old light fitting.
S&F in repair Fresh air fan motor of capacity 1/6 HP 230 volts, 50 Hz, AC supply suitable for 250/200 mm size Fresh air fan as per sample complete all as spd and directed.
Supply only exhaust fan motor capacity 1/4 HP 230 volts suitable for 230/300 mm size exhaust fan complete all as directed.
Supply only single pole and neutral enclosure with a two pin earth plug and socket complete with one single pole MCB 20 Amp complete all as specified and directed.
Supply only 12 W LED Bulbs warm white , high energy efficiency LED luminaries to be fitted on existing holders 240 V,50 Hz,
Supply only 9 W LED Bulbs warm white , high energy efficiency LED luminaries to be fitted on existing holders 240 V,50 Hz,
M&L for in replacement for only twin core PVC insulated unarmoured cable 4 Sqmm Flat 1100 Volts with Aluminium multi stranded conductor all as specified and directed by Engr-in-Charge.
M&L for in replacement for only twin core PVC insulated unarmoured cable 6 Sqmm Flat 1100 Volts with Aluminium multi stranded conductor all as specified and directed by Engr-in-Charge.
M&L for tape roll all as specified and directed by Engr-in-charge.
S&F adore warm white LED bulb 9W pin type 810 lm rated correlated colour temp F 3000K, 240 V AC all as specifed and directed by Engr-in-Charge.
S&F adore warm white LED bulb 9W thread type 810 lm rated correlated colour temp F 3000K, 240 V AC all as specifed and directed by Engr-in-Charge.
S&F adore warm white LED bulb 2.8 W thin thread type 210 lm rated correlated colour temp F 3000K, 240 V AC all as specified and directed by Engr-in-Charge.
S&F adore warm white LED bulb 2.8 W thick thread type 210 lm rated correlated colour temp F 3000K, 240 V AC all as specified and directed by Engr-in-Charge.
S&F in replacement of Recess mounted complact vertical round shaped down light LED 5 watt suitable for low ceiling height complete all as specifie.
S&F in replacement of Recess mounted complact vertical round shaped down light LED 2 watt suitable for low ceiling height complete all as specifie.
S&F LED Tube rod fittings 4 feet long single side connection complete all as specified and directed.
S&F in replacement of decorative type wall mounted luminaire (Comet) with unbreakable poly carbonate materials suitable for 1x12 watt LED bulb B22 base complete all as specified and directed by Engineer in charge .
Note :- Credit shown in credit schedule of tender document shall be considered by the tenderer while quoting the rates of various items. The same shall be recovered from various payment to contractor before handing over old material
Ambrish Builders (BID ID -3068021)
M/S MALHOTRA ENGINEERING WORKS (BID ID -3068198)
Raj Contruction (BID ID -3066968)
M/S R S Traders (BID ID -3068258)
M/S SWASTIK BUILDERS (BID ID -3068155)
gangotri enteriprises (BID ID -3067995)
Bharat Trading Company (BID ID -3069110)
chauhan construction (BID ID -3067882)
Avion Industries (BID ID -3068553)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .