Loading…
Loading…
Tender Value
₹1.3 Cr
EMD Value
₹2.0 L
Closing Date
16 Jul 2026, 6:00 pm
Similar tender results from the same govt authority in the past 3 years.
HQ CWE Meerut
29J The Mall Road Meerut Cantt Uttar Pradesh 250001
CONVERSION OF LT OVER HEAD LINES INTO U/G CABLES INCLUDING REPLACEMENT OF LT PANELS AND ALLIED WORKS AT 416 ENGR BDE, RVC ORs LINE, 19 ENGR REGT, DOGRA FARM FAMILY QTR, FAFA ACCN AND OLD SF QTR NEAR UMRAO SINGH ENCLAVE UNDER GE (U) MEERUT CANTT
2026_MES_772935_1
94387/MRT/2026-27/E8
Open Tender
Civil Works
270 days
Meerut Cantt
Please refer tender documents.
7 documents required · 7 mandatory
₹1,000
GE (U) Meerut
₹2.0 L
Yes
18 Jun 2026
18 Jun 2026
23 Jul 2026
18 Jun 2026
16 Jul 2026
9 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installing, testing and commissioning of LT out door type factory made(CPRI Approved ), junction box of size 750mmX600mm X500mm (over all dimension )with mild steel angle iron of size 40X40X5mm vertical frame and legs with mild steel flat iron 40X6 mm in horizontal sides of the frame LT Junction box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, The panel shall be dust and vermin proof, IP 56 class protection and made of 3.15mm MS sheet and 40x40x5 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & back opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified and directed. With double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock-2Nos with 3 keys. Aluminium bus bar of 450 Amps rating with drilled holes for incoming /outgoing cable core connection including aluminium lugs, GI bolts, Nuts and washers of suitable size. Porcelain / synthetic bridge insulators, heavy duty with necessary steel / GI screws, bolts, nuts and washers, complete all as specified and as directed. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 50 sqmm to 400 Sqmm by drawing /digging out cable from loops in trenches outside the Bldg inclusive of necessary | 10 | Each | - | - |
| 1.01 | excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable lugs for terminal connections of cables, Platform of U shape for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class `B’, old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 (using 20 mm graded crushed stone aggregate) on top and grouting bolts etc for Feeder pillar box complete all as specified and as directed.
Note:- All types of certificates and design verification with switch gears (ACB/MCCB) confirming to IS/IEC 61439/2011 Part- I & II with short circuit test 4000 A with breaking capacity 65 KA shall be submitted by the contractor before execution of work.. | - | - | - | - |
| 2 | Supply, installing, testing and commissioning of LT out door type factory made (CPRI Approved), Feeder pillar box of size 900mmX800mmX500mm (over all dimension )with mild steel angle iron of size 40X40X5mm vertical frame and legs with mild steel flat iron 40X6 mm in horizontal sides of the frame LT FPB (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, The panel shall be dust and vermin proof, IP 56 class protection and made of 3.15mm MS sheet and 40x40x5 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & back opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indicated in Hindi and English complete all as specified and directed with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock-2Nos with 3 keys. with MCCB 4 pole, 415 volts AC grade, 200 Amps rating and 25 KA rupturing capacity - 01 No Aluminium bus bar of size 10X6mmX400mm long with drilled holes for incoming /out going cable core connection including aluminium lugs ,GI bolts ,Nuts and washers of suitable size. Porcelain / synthetic bridge insulators, heavy duty with necessary steel / GI screws ,bolts, nuts and washers , all as specified and as directed., Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone aggregate, 15 cm thick in foundation, brick work in CM 1:6 with sub class `B’, old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 | 44 | Each | - | - |
| 2.01 | (using 20 mm graded crushed stone aggregate) on top and grouting bolts etc for Feeder pillar box. The platform shall be such that it is of a height 45 cm above the nearest road level including connections of all out going/in coming existing cables of size 50 sqmm to 400 Sqmm by drawing /digging out cable from loops in trenches outside the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable lugs for terminal connections of cables complete all as specified and directed by Engr-in-charge
Note :- All types of certificates and design verification with switch gears (ACB/MCCB) confirming to IS/IEC 61439/2011 Part- I & II with short circuit test 4000 A with breaking capacity 65 KA shall be submitted by the contractor before execution of work. | - | - | - | - |
| 3 | Supply, installing, testing and commissioning, factory made and tested . LT feeder pillar box (KIOSK) 1500mm x1200x 700mm size, outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 1000 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door LT panel etc with voltage and danger indiated in Hindi and English with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 10 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. Platform of U shape for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone aggregate, 15 cm thick in foundation, brick work in CM 1:6 with sub class `B’, old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for Feeder pillar box complete all as specified and directed including connections of all out going/in coming existing cables of size 25/35/50/95/120/ 150 sqmm by drawing /digging out cable from loops in trenches out side the Bldg inclusive of necessary excavation | 1 | Each | - | - |
| 3.01 | and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, , All out going feeders shall be connected by cable through suitable size gland plate / glands.& The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old skelton type panel with control switches complete all as specified and as directed.
Note :- All types of certificates and design verification with switch gears (ACB/MCCB) confirming to IS/IEC 61439/2011 Part- I & II with short circuit test 4000 A with breaking capacity 65 KA shall be submitted by the contractor before execution of work. | - | - | - | - |
| 3.02 | The scope of work includes the following :-
(I) Incoming :-
(i) ACB 4 Pole, Tharmal Magnetic adjustable type 630A, Breaking capacity 50 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals
(ii) Digital voltmeter 0-500 volts with selector switch - 01 No
(iii) Digital Amp meter 0-630 Amp with selector switch & CT - 01 No
(iv) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set
(II) Outgoing :-
(i) MCCB 4 Pole, Thermal Magnetic Based adjustable type 250A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals
(ii) MCCB 4 Pole, Thermal Magnetic Based adjustable type 160A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, protection, -04 Nos along with Spreader terminals
(iv) MCB TPN 63 Amp 10 KA C-Curve - 1No
(v) Indicator lamp LED type (R, Y, B) complete with fuse -06 Set | - | - | - | - |
| 4 | All as per Srl item No 3 here-in-before complete but Size 1200 x1000x600 mm and Busbar 600 Amps rating complete all as specified and directed. | 3 | Each | - | - |
| 4.01 | (I) Incoming :-
(i) MCCB 4 Pole, Tharmal Magnetic adjustable type 400A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals.
(ii) Digital voltmeter 0-500 volts with selector switch - 01 No
(iii) Digital Amp meter 0-630 Amp with selector switch & CT of ratio 630/5- 01 No
(iv) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set
(II) Outgoing :-
(i) MCCB 4 Pole, Thermal Magnetic Based adjustable type 200 A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, protection, -02 Nos along with Spreader terminals
(ii) MCCB 4 Pole, Thermal Magnetic Based adjustable type 100A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals
(iii) MCB TPN 40 Amp 10 KA C-Curve - 2 Nos
(iv) Indicator lamp LED type (R, Y, B) complete with fuse -05 Set | - | - | - | - |
| 5 | M&L for plate earthing for sub station equipments complete with galvanized steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground (Earth pit not less than 2.25 Mtr deep below normal ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level connecting with galvanized iron iron strip 32x6mm as earthing lead by means of bolt nut check nuts and washers of galvanized iron and provision of GI tubing light grade (ISI marked)of size 40 mm for protection of GI earth wire upto test point, 20mm dia GI tubing medium grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in soft / loose soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion. NOTE :-Rates inclusive of necessary excavation in soft / loose soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing) . | 116 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.26 MB
TD1.pdf
Tender Documents • 0.38 MB
TD2.pdf
Tender Documents • 0.21 MB
TD3.pdf
Tender Documents • 0.24 MB
TD4.pdf
Tender Documents • 0.57 MB
BOQ_865520.xls
BOQ • 3.45 MB
Download all tender documents and submit your bid