Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹11.6 LAccepted-AOC | 1 | Accepted-AOC LOWEST AND REASONABLE | |
| 2 | 2₹19.5 L+₹7.2 L (58.3%)Rejected-Finance | 2 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
21 Sept 2021, 6:00 pmClosed
CWE AF SRINAGAR
CWE AF SRINAGAR C/O 56 APO
REPAIRS MAINT OF HT NETWORK INCLUDING CALIBRATION OF VCBs AVR ETC AND OTHER CONNECTED WORKS UNDER GE AF SRINAGAR
2021_MES_469975_1
CWE(AF)SGR/SGR-17/2021-22
Open Tender
Civil Works
Item Rate
180 days
AF STATION SRINAGAR
As per NIT
9 documents required · 9 mandatory
₹500
GE AF SRINAGAR
₹40,000
Yes
9 Oct 2021
23 Aug 2021
23 Sept 2021
23 Aug 2021
21 Sept 2021
7 Sept 2021
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for taking out HT underground cable and laying of new underground cable in replacement and getting out in any type of soil complete all as directed by the Engr-in-Charge.
Returning, filling in, including spreading, leveling, watering and well ramming in layers n.exc 25 cms. thick in soft / loose soil complete all as specified and directed by Engr -in -charge .
Removal of surplus soil to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed by Engr-in-Charge.
Material and Labour for sand cushioning in trenches including spreading and consolidation in layers of 8cm thick before laying the cable & 15 cm thick after laying the cable and punned down to form a bed complete all as specified and directed by Engr-in-Charge. Note:- Punned down thickness will be measured for payment.
Supplying and laying Un-reinforced precast concrete cable cover ' factory made' of class HV, Type 1 with peak, of size 300 mm x 180 mm x 40 mm complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement 100 mm dia galvanized iron tube light grade for protection of cable at road crossing complete all as specified and as directed by Engr-in-Charge.
Supply, Laying, jointing, and testing of under ground cables XLPE insulated screened PVC bedded galvanized steel strips armoured electric power cable (heavy duty) with aluminium conductor HT 11000 volts grade(Earthed) and cross sectional area 120 sqmm 3 core confirming to latest IS and ISI marked complete all as specified and as directed by Engr-in-Charge.
Dehydration/filtration of transformer oil of transformer in position till the dyelectric strength of transformer oil is achived not less than 50 KV when measured at 2.5 mm gap for one minute including filling of new transformer oil as required for top up upto required oil level complete all as specified and as directed by Engr-in-Charge. Note : - New transformer oil as required shall be measured and paid separatly under respective item as supply only.
Supply only new transformer oil with dielectric strength not less than 60 KV when measured at 2.5 mm gap for duration of one minutes, complete all as specified and as directed by Engr-in-Charge.
Supply and fixing HT feeder pillar box outdoor type factory made weather and vermin proof made out from 3.15 mm sheet supported with legs 45 cm long made of angle iron 50x50x5 mm of size 1.2 mtrx1 mtrx1 mtr with 3 Nos 0.8mtr Aluminium bus bar of size 40x10mm or 400 Amps for 11 KV , 11 KV post Insulator 6 Nos duly drilled hole for HT Cable connection including front and rear side openable with locking arrangment suitable for 11 KV HT and provision for incoming and out going HT cable connection including painting with two coats of smoke gray synthetic enamels paint over a coat of red oxide primer complete and providing security fence XPM jally type of 2 mtr height from ground level square type all rounded 2.5 mtr length with 9nos angle iron of 25x25x5mm of hight 2.25mtr (2mtr above ground 0.25 mtr under ground) including necessary location gate of same XPM jally all as specified and directed . Note:- Feeder piller box shall be mounted on brick plate form built in (1:4) not less then 60 cm above ground level with suitable PCC foundation rendering 15 mm in CM (1:6), applying two coats and cement base paints and XPM jally supported on 9 nos angle iron with concrete base.
Material and labour for earthing complete with galavanised steel earth plate electrode of size 60mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below gound level with top edge of the earth plate not less than 1.5 m below normal gound level connected to galvanised steel earth strip of size 32x6 mm by means of bolts, nuts, check nuts and washers of galavanised iron/steel and conneted to main control board as directed and including proivison of concrete pit in PCC (1:2:4) type B1 pre cost RCC earth pit cover reinforced with 8 mm dia TMT bars @ 150mmc/c of size 54cmx54cmx8cm with two handle for lifting made out of 8mm dia MS bar, provision of funnel, wire mesh, 20mm bore galavanised steel tubing (med grade) for watering. Charcoal 250 Kg and salt 200 Kg in alternate layers, 40mm bore galavanised steel tubing light grade for protection of earth lead connection including necessary excavation and earth work and testing complete all as shown on electrical plate No 3 of SSR Part-I. Note : Earth strip and protection pipe upto 7.5m is included in the unit rate of this item. Contractor shall quote his rate accordingly.
Material and labour for earthing complete with copper earth plate electrode of size 60mm x 600mm x 3mm thick buried directly in ground (earth pit not less than 2.25m deep below gound level with top edge of the earth plate not less than 1.5 m below normal gound level connected to copper earth strip of size 20x3mm by means of bolts, nuts, check nuts and washers of copper and conneted to main control board as directed and including proivison of concrete pit in PCC (1:2:4) type B1, pre cost RCC earth pit cover reinforced with 8 mm dia TMT bars @ 150mmc/c of size 54cmx54cmx8cm with two handle for lifting made out of 8mm dia MS bar, provision of funnel, wire mesh, 20mm bore galavanised steel tubing (med grade) for watering. Charcoal 250 Kg and salt 200 Kg in alternate layers, 40mm bore galavanised steel tubing light grade for protection of earth lead connection including necessary excavation and earth work and testing complete all as shown on electrical plate No 3 of SSR Part-I Note : Earth strip and protection pipe upto 7.5m is included in the unit rate of this item. Contractor shall quote his rate accordingly.
Supply, installation and testing in replacement of Lightening Arrestor expulsion type for outdoor use complete with all fittings transmission class discharge capacity 65 kilo Amps suitable for 11000 V including bracket, clamps, nuts and washers and connecting to earth wire complete all as specified and as directed by Engr-in-Charge.
Taking down defective transformer from any location of installation, transporting the same to authorised work shop for repair and return back and installed on original location after repair including connection complete all as specified and directed by engr-in-charge.
Opening/striping off transformer 11 KV/0.433 KV step down capacity from 63 KVA to 160 KVA including draining out oil, lifting the core & coil assembly, washing & cleaning dust, dirt and sludge deposit etc from all parts. Removing damaged/defective parts requires replacement, making internal connection servicing of tap changer and reassembling the transformer after repair and replacement work including new cork sheet gasket, packing nuts, bolts, washer etc complete as required filling fresh transformer oil and testing complete.
Opening/striping off transformer 11 KV/0.433 KV step down capacity from 200 KVA to 500 KVA including draining out oil, lifting the core & coil assembly, washing & cleaning dust, dirt and sludge deposit etc from all parts. Removing damaged/defective parts requires replacement, making internal connection servicing of tap changer and reassembling the transformer after repair and replacement work including new cork sheet gasket, packing nuts, bolts, washer etc complete as required filling fresh transformer oil and testing complete. Note for items 16 and 17 :- Fresh transformer oil and other spare parts shall be measured under relevant items of Schedule.
Replacement of burnt copper coil winding complete with suitable size/gauge of super copper enameled wire of high quality matching with existing wiring of transformer of capacity 100 KVA to 500 KVA complete all as specified and directed by Engr-in-Charge.
Insulation of copper strip limb for LT side with existing coil of transformer of capacity 100 KVA to 500 KVA complete all as specified and directed by Engr-in-Charge.
Supply only HV porcelain bushing of 11 KV grade with gasket complete all as specified and as directed by Engr-in-Charge.
Supply only LV porcelain bushing of 1100 volts grade with gasket suitable for the following capacity of transformer :-
(i) 63 KVA to 160 KVA
(ii) 200 KVA to 400 KVA
(iii) 500 KVA
Supply only LT brass stud with 5 Nos brass nut, brass washers, check nuts, conical rubber bush for the following capacity of Transformer.
(i) 63 KVA to 160 KVA
(ii) 200 KVA to 400 KVA
(iii) 500 KVA
Supply only HT brass stud with 3 Nos brass nut, brass washers, check nuts conical rubber bush for the following capacity of transformer.
(i) 63 KVA to 160 KVA
(ii) 200 KVA to 400 KVA
(iii) 500 KVA
Supply only tap changer rotary type suitable up to 500 KVA capacity Transformer complete all as specified and as directed by Engr-in-Charge..
(i) 63 KVA to 160 KVA
(ii) 200 KVA to 400 KVA
(iii) 500 KVA
Supply only breather assembly with fresh filling of silica-gel (colour of silica gel should be deep sky blue) capacity in non metallic breather of transformer up to 500 KVA capacity complete all as specified and as directed by Engr-in-Charge.
Supply only oil level indicator suitable for Transformer up to 500 KVA capacity complete all as specified and as directed by Engr-in-Charge.
Supply only of Oil temperature gauge as per IS specification complete as specified and directed, suitable for Transformer up to 500 KVA capacity complete all as specified and as directed by Engr-in-Charge.
Preparation of old painted surfaces of transformer and painting with two coats of synthetic enamel paint including writing SM No and MES No with approved colour paint with letters 30 mm high for the following capacity of transformer:-
(i) 63 KVA to 200 KVA
(ii) 250 KVA to 400 KVA
Material and Labour for HT Cable path indicator shall be provided in distance min 100 mtrs and every joint,and turning of cable . The cable path indicator should be brown colur and fixed on MS angle iron frame, complete all as specified and as directed by Engr-in-Charge.
Material and Labour for servicing of 33 KV VCB / 11KV VCB / bus coupler by dismantling, cleaning and greasing the complete VCB with attached relays bus bar etc insulation testing, setting the contact gap by measuring as required reassembling the VCB and reinstalling back to its original position checking and repairing the current circuit panel wiring, replacement of new spares as required complete including operational testing and comrnissioning all as directed. Note : New spares will be measured and paid separately under relavent item of' this schedule.
Supply, connecting and testing tripping coil DC 30 Volt suitable for 11KV VCB panel complete all as specified and directed by Engr in charge.
Supply, connecting and testing closing coil DC 30 Volt suitable for 11KV VCB panel complete all as specified and directed by Engr in charge.
Supply, connecting Ammeter digital type 144 sqmm with CT ratio 100/5 and current rating 0-50 Amp suitable for 11 KV VCB panel complete all as specified and directed by Engr in charge.
Supply, connecting Voltmeter digital type 0-15 KV PT ratio, 11KV/110 Volt suitable for 11 KV VCB panel complete all as specified and directed by Engr in charge.
Supply and Fixing LED type indicating lamp fitting suitable for 24 /30 Volt DC complete all as specified and directed by Engr in charge.
Supply only gear system assembly with handle for charging discharging of VCBs complete all as specified and directed by Engr in charge.
Supply only spring charging motor for VCBs complete all as specified and directed by Engr in charge.
Supply only breaker control switch for 11 KV breakers.
Supply only Auxiliary spring set as per sample.
Supply only Vacuum interrupter type WL3379M3.
Supply only rachet assembly buterfly as per sample.
Supply and Fixing sealed maintenance free batteries 12 volt 42AH connected in series 6 Nos with stand made out of 45X45X5 mm to accommodate battery bank and making electrical connection all as specified and direted by Engr in charge.
Supply and Fixing sealed maintenance free batteries 2 volt connected in series 12 Nos suitable for VCB upto100 AH with stand made out of angle iron 45X45X5 mm to accommodate battery bank and making electrical connection all as specified and direted by Engr in charge.
Supply and Fixing in repair online UPS 3 KVA capacity single Phase 72 Volt. Model No. NM72MX3KK11 of Microtek.
Supply and Fixing in repair copper wounded battery charger input voltage120 Volts to 240 Volts , output voltage 36 Volt along with protection DC MCB on DC side for reverse polarity, AC MCB on AC side,inbuilt stabiliser and fault indicator.
Supply and Fixing microprocessor based over current and earth fault relay with highest element event recording & current scanning/display feature suitable for 30 Vto 110 V AC/DC .
Supply and Fixing 12 KV indoor epoxy resin current transformer with CT ratio 750-375/5-5-2.89A match as per existing CT complete all as per directed by Engr in charge.
Material and Labour for carrying out primary & secondary injection test of 33 KV or 1 1 KV indoor /outdoor type current transformer (Set of three) of VCBs by using standard injection test method and checking the electrical circuits for fault condition, all relay testing and proper foact;oning incl submitting the test report all as directed by Engr in charge. (Note : PIT/SIT for VCB will be carried out in 6 months intervals and each primary & secondary injection test will be measured and paid)
Supply and Fixing in repairs moving carbon rollers of existing size and make suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Tie & Tac brass connector suitable for 2000 KVA AVR Unit.
Supply and fixing in repairs Chain rack (double) including bearing as per existing make & model.
Supply and fixing in repairs Limit switch suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs SS coupling suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Chain assembly suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Synchronous motor suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs PCB card suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs PT unit 11000/110 volts suitable for 2000 KVA buck booster Unit as per existing make & model.
Supply and fixing Winding temperature relay complete suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Oil temperature relay complete suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Buchloz relay assembly complete suitable for 2000 KVA AVR Unit/ Transformer as per existing make & model.
Supply and fixing in repairs Aux contactor suitable for 2000 KVA AVR Unit as per existing make & model.
CHINAR CONSTRUCTION TRADERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .