Karnataka Power Corporation Limited
Haseena K
Brief scope of works includes-a) Design, Manufacture and Supply of 2 Nos. of 3ph, 750kVA, 11kV/433V, ONAN, Dyn11, Outdoor Type, Copper wound Generator Auxiliary Transformer with off load tap changer. b) Supply of 400sq.mm, 3.5 core, 1.1kV grade, PVC armored, Copper LT power cable along with cable termination accessories required for connecting LV side of Auxiliary Transformer to LTAC panel. c)Supply of essential spares as per the bid requirement d) Laying and Termination of supplied 400sq.mm, 3.5core copper cable from Auxiliary Transformer to LTAC Panel along with necessary termination accessories. e) Dismantling of old 2 Nos. of 750KVA, 11kV/400V auxiliary transformers along with old OIP cables connected from auxiliary transformers to LTAC panel. f) Erection, Testing and commissioning of newly supplied 3ph, 750kVA, 11kV/433V Auxiliary Transformers.
KPCL/2025-26/PS/WORK_INDENT3509/CALL-2
KPCL/2025-26/PS/WORK_INDENT3509/CALL-2
Open
Power stations
Two Tender Document System(Two Cover)
KPCL Executive Engineer EMO Office SVP MGHE
11 documents required · 9 mandatory · 2 optional
The bidder shall be a contractor/Agency with Class -1 Electrical License shall have proven experience in the field of supply, erection, testing and commissioning of transformers of capacity 500 kVA, 11kV/433V and above to power utilities or any other reputed organizations. In proof of the above, the bidder shall furnish at least one work order/ purchase order copy not less than 30.7Lakhs and corresponding work done issued from the competent authority and copy of Class -1 Electrical License. OR The bidder shall be a manufacturer /Supplier shall have proven experience in the field of supply of transformers of capacity 500 kVA, 11kV/433V & above to power utilities or any other reputed organizations and should carry out the subject tendered work through Class-1 licensed Contractor. In proof of the above, the bidder shall upload at least single work order/ purchase order copy not less than 30.7 Lakhs and corresponding work done /supply completion certificate issued from the competent authority and an undertaking for carry out the work through Class-1 Electrical Licensed contractor
The Bidders in the last five financial years (2020-21, 2021-22, 2022-23, 2023-24, 2024-25) should have achieved in at least two financial years an average annual financial turnover of Rs.61.4 lakhs. In proof Annual Report/turn over certificates duly certified by chartered accountant shall be furnished.
Satisfactoriy completed (atleast 90%) as prime contractor at-least one such similar work of value not less than Rs. xxxxxxx (80% of estimated cost of tender)
Executed in any one year the following minimum quantities of work (Cement Concrete - xxxx cum, Earthwork - xxxx cum, etc) (80% of peak rate of construction)
Tenderer or his identified Sub Contractor should possess valid Electrical License for executing building electrificatio works and should have executed similar electrical works totallng Rs. xxxxxx (not less than 50% of electrical works) n any one year
Tenderer or his identified Sub Contractor should possess valid license for executing water supply / sanitary engineering works and should have executed similar works totallng Rs. xxxxxx (not less than 50% of electrical works) n any one year
Owning the following key and critical equipment for this work (xxxx, xxxx, xxxx)
Liquid assets and /or availability of credit facilities of no less than Rs. xxxxxx Lakhs (estimated cash flow for 3 months of peak construction period)
Total value of civl engineering works executed and payments received in the last five years (year-wise)
List of existing commitments and ongoing works
List of works for which tenders already submitted
Banker Details for reference
Construction equipment owned by the tenderer and equipment proposed to be deployed on this contract, if awarded
Reports on the financial standing of the tenderer, such as profit and loss statements and auditors reports for the last five years
Qualification and experience of the key technical and management personnel in permanent employment with the tenderer and those that are proposed to be deployed on this contract, if awarded
List of Financial Resources with Certificates
₹1,540
₹1.2 L
16 Jan 2026
16 Jan 2026
2 Feb 2026
22 Jan 2026
23 Jan 2026
TECHNICAL PARTICULARS OF UNIT AUXILIARY TRANSFORMER
Sl. No. DETAILS
I 0_) Name of the manufacturer As per bidder
0_) Type of service (indoor/outdoor) Outdoor
0_) Applicable standards The Transformer shall comply with the latest edition of the standards and other relevant IEC standards
0_) No-load voltage ratio (guaranteed)
0_) Guaranteed continuous rating for the specified cooling, temperature rise over the ambient temperature (KVA)
0_) Rated voltage
0_) Rated frequency Hz
0_) No. of phases
0_) Current at rated voltage & on principal tap
0_) Vector group reference and symbol
0_) Guaranteed rated temperature rise above reference peak ambient temperature of air (deg. cen.)
a)Top oil by thermometer
b) of winding by resistance
0_) i. Guaranteed no-load losses at rated voltage & frequency at principal tap (KW) (without tolerance)
ii. No-load losses at the voltage corresponding to the highest tap (KW)
0_) No-load loss
a. At 90% rated voltage (KW)
b. At 100% rated voltage (KW)
c. At 110% rated voltage (KW)
0_) i. Guaranteed load losses at rated output, rated frequency and at 75 deg. cen. average winding temperature at principal tap (KW) (without tolerance)
ii. Load losses at rated output, rated frequency and at 75 deg. cen. average winding temperature at
0_) Guaranteed total losses at normal ratio, rated output, rated voltage and rated frequency and at 75 deg. cen. (KW) (without tolerance)
0_) Positive sequence impedance on rated MVA base at rated current & frequency at 75oC winding temperature at,
i) Principal tap(%)
ii) Highest tap(%)
iii) Lowest tap(%)
0_) Zero Sequence impedence at 750 C
i) Principal tap (%)
ii)Highest tap (%)
iii)Lowest tap (%)
0_) Resistance voltage drop at 750 C average winding temperature and rated full load expressed as percentage of rated MVA(All values to be referred to primary)
0_) Reactance voltage drop at 750 C and full load between windings expressed as % of rated voltage between H.V & L.V (%)
0_) Guaranteed impedance voltage at normal tap and at 75 deg.cen. average winding temperature expressed as percentage of rated voltage (%)
0_) Impedance per phase
i. Referred to H.V side (Ohms)
ii. Referred to L.V side (Ohms)
0_) Regulation at full load & 75 deg.cen. winding temperature expressed as a % of normal voltage
i) at unity P.F
ii) at 0.8 P.F(lagging)
0_) a) Efficiencies at normal ratio, rated voltage, rated frequency and 75 deg. cen. average winding temperature for the output at unity p.f. & 0.8 p.f. corresponding to
0_) i) Maximum efficiency(%)
ii)Load at which maximum efficiency occurs (% of full load)
0_) Permissible overloading
0_) Insulating & cooling medium
0_) External short circuit withstand capacity (MVA) & duration(secs.)
0_) Overflux withstand capability of the transformer corresponding to
ii) Factor 1.25
iii) Factor 1.4
0_) Ideal heating time or thermal time constant (Hours)
II Additional technical particulars
0_) Details of core
i) Type of core construction
ii) Type of joint between core limb & yoke
iii) Maximum flux density at rated voltage & frequency and at principal tap
a) Core (weber/sq.mtrs)
b) Yoke (weber/sq.mtrs)
iv)Max. flux density in iron at voltage and frequency 10% higher than normal (webers/sq.mtrs.)
v)Magnetising current at normal ratio & frequency
i) 90% of rated voltage
ii) 100% of rated voltage
iii) 110% of rated voltage
vi)power factor of magnetising current at normal voltage, ratio & frequency
vii) a)Material of core lamination and grade
b) Thickness of core lamination
c) Insulation between core lamination
d) Insulation of core bolts
e) Insulation of core bolt washers
f) Core bolt insulation withstand voltage for 1 minute(kV rms)
g) Are the core bolts grounded. If so how
h)Area of cross section of core lamination.
viii) a) Material of core clamping plate
b) Thickness of core clamping plate
c) Insulation of core clamping plate
ix) Describe location/method of core grounding
x) Details of oil ducts in core
xi) Exciting va/kg or w/kg of lamination material at
i) 15,000 gauss
ii) Rated induction (vide item iii(a))
iii) Induction as per item (iv)
0_) DETAILS OF WINDINGS:
i)Type of Winding
ii) Material of the winding conductor
iii) Maximum current density of windings and conductor area (at rated current)
a) Current density(A/cm2)
b) Conductor area(cm2)
iv) Type of joints in the windings
v) Resistance of (Approx)
i) HV winding(ohms/ph)
ii) LV winding(ohms/ph)
vi) Whether HV windings are interleaved
vii) Whether windings are preshrunk
viii) Whether adjustable coil clamps are provided for HV & LV windings
ix) Whether electrostatic shields are provided to obtain uniform voltage distribution in the HV windings
x)Insulation materials used for
xi) Insulation material used between
a) HV & LV winding
b) LV winding & core
xii) Type of axial coil supports
xiii) Type of radial coil supports
xiv) Maximum allowable torque on coil clamping bolts
xv) Minimum clearance to earth(cms)
xvi) Capacitance
a) HV winding to earth when LV earthed(pF)
b) LV winding to earth when HV earthed (pF)
c) Interwinding (pF)
xvii) Insulation strength of windings(1.2/50 microsec wave)
Impulse full wave (Withstand values)
i) HV winding (KVP)
ii) LV Winding (KVP)
Impulse chopped wave (Withstand values)
i) HV winding (KVP)
ii) LV Winding (KVP)
xviii)Separate source power frequency withstand voltage
i) HV Winding (KV rms)
ii) LV Winding (KV rms)
iii) Neutral end of LV (KV rms)
xix) Induced over voltage withstand voltage (kV rms)
i) Name of manufacturer
iii) Standards applicable
iv) Type of bushing
v) a) rated voltage class (kV)
b) rated current(Amps)
vi) Lightning impulse withstand voltage (KV peak) (1.2/50 microsecs)
vii) Power frequency withstand voltage(KV rms)
a) Wet for 1 minute(kv rms)
b) Dry for 1 minute(kV rms)
viii) Visible corona discharge voltage (KV rms)
ix) Partial discharge level
x) Creepage distance in air( mm)
xi) Creepage distance (protected)
xii)Recommended gap setting
xiii) Quantity of oil in bushing (kgs) & specification of oil used
xiv) Weight of assembled bushings in Kgs
xv) Minimum clearance height for removal of bushings(mm)
0_) MINIMUM CLEARANCE(mm)
i)In air (between phases & phase to ground)
ii)In oil (between phases & phase to ground)
0_) DETAILS OF TANK
i) Type of tank
ii) Approximate thickness of sheet
d) Cooling tubes/radiators
iii) Vaccum recommended for hot oil circulation(Torr)
iv)Vaccum to be maintained during oil filling in transformer tank(TORR)
v)Vaccum to which the tank can be subjected without distortion(TORR)
vi) No. of bidirectional wheels provided
vii) Track guage required for the wheels
a) Transverse axis
b) Longitudinal axis
viii) Pressure relief device
a) State whether it is self sealing type(After release of pressure)
b) If self sealing type state the operating pressure
ix) Dia of wheels.
0_) CONSERVATOR
i. Type( with or without air cell)
ii. Total volume (ltrs)
iii. Volume between the highest and lowest levels (ltrs.)
0_) COOLING EQUIPMENT
iii) Type and No. of radiators
iv) Estimated quantity of oil in radiators (ltrs)
0_) BUCHHOLZ RELAY
ii) No.of electrical contacts
iii) Rating of electrical contacts
0_) TEMPERATURE INDICATORS
i) Oil temperature indicator
b) Permissible setting ranges for alarm & trip
c) Range of instrument
d) Number of electrical contacts
e) Rating of contacts
ii)Winding temperature indicator
b) Permissible setting ranges for alarm & trip
c) Range of instrument
d) Number of electrical contacts
e) Rating of contacts
f) Whether remote indicators provided. If so equipments required at purchaser's control room is included
iii) Make of Pressure reducing valve
0_) Details of anti earthquake device provided if any
0_) TAP CHANGING GEAR
ii) Type, designation, standard applicable
iii) Tap voltage as percent of no-load rated KV
c) % variation per step
iv) No. of steps
v) Whether padlock provided
vi) Position of taps on the HV windings
12 (a) Water proof Cable boxes (415 v side)
I) No. of cable boxes
b) Rating of each cable box
iii) Size of cables
12 (b) Water proof Cable boxes (11kV side)
I) No. of cable boxes
b) Rating of cable boxes
iii) Size of cables
i) Net Weight of core
ii)Net weight of
iii) Net weight of copper for
iv) Net weight of insulating oil
v) Net untanking weight of core frame & coils
vi)Volume of insulating oil
vii) Total weight of radiators (without oil)
viii) Transport weight of transformer package with oil but without fittings to be dismantled during transport
ix) Overall dimensions of the major packages
Transformer tank (assembly)
Spare coil tank(HV/LV)
x) Total despatching weight of anciliary equipment
xi) Total weight of transformer when completely assembled
1. Untanking height of core and coils(drawing of lifting arrangement shall be enclosed)
2 a)Dimension of transformer when finally assembled
i) Underbase to topmost point
ii) Overall breadth
iii) Overall length
b) Dimension of transformer during movement from repair bay to its final position (LxBxH)
3. Overall transporting dimensions of largest package (LxBxH)
14 Whether transformer is suitable for installation in the place of existing transformer (Yes/No)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
3 e-nit SECTION-I - GENERAL CONDITIONS.doc
Tender Document • 0.46 MB
7 Schedules 1-9.doc
Tender Document • 0.12 MB
6 SECTION -IV-UAT.doc
Tender Document • 0.35 MB
8 GTP-UAT -.xls
Tender Document • 0.07 MB
2 e-nit INSTRUCTION TO BIDDERS.doc
Tender Document • 0.26 MB
4 e-nit-SECTION II - Brief Description of the Project.doc
Tender Document • 0.10 MB
5 SECTION-III panel SPECIAL CONDITIONS Gen Tech spec.doc
Tender Document • 0.18 MB
Annexure-I.docx
Others - Annexure • 0.01 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .