Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹12.2 LAccepted-AOC 708 PREM NAGAR KARNAL HARYANA 132001 | KARNAL | KARNAL | HARYANA | 132001 | 1 | Accepted-AOC Lowest price | |
| 2 | 2₹17.6 L+₹5.4 L (44.1%)Rejected-AOC AMAR NIWAS RA 288 GANDHI CHOWK SADAR BAZAR KARNAL | KARNAL | KARNAL | HARYANA | 2 | Rejected-AOC Higher price | |
| 3 | Rejected-Technical | - | Rejected-Technical Technical Disqualiified |
Tender Value
₹15.3 L
EMD Value
₹30,660
Closing Date
1 Mar 2024, 2:00 pmClosed
Executive Engineer
Construction Branch, Kurukshetra University Kurukshetra
Supply, Erection, Testing, Commissioning of 400 KVA Capacity Transformer with allied items near Faculty Lounge Building to feed the power supply to Faculty Lounge Building, Old Arts Faculty Building and Education Department Building at KUK.
2024_HRY_352255_1
KUK/Constn/2024/1
Open Tender
Electrical Works
Works
90 days
Kurukshetra University
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
₹30,660
Yes
7 Oct 2024
9 Feb 2024
4 Mar 2024
9 Feb 2024
1 Mar 2024
9 Feb 2024
Amount
Laying and Jointing PVC Pipe. Heading
Design, Supply & erection of transformer (Copper Wound out door type) of standard make Required 11/0.433 KVA rating outdoor type 11 KVA, G.O. switch, H. Pole, battery charges, earthing, safety equipment, fenceed enclousure for transformer, and any other contingent thereto complete in all respect as per approved make and directions of Engineer-in-charge as per respective capacity Make: Kirloskar/ Crompton Greaves/ Amsons/ Jay-Bee/ Alstom 20.76.11 400 KVA
MCCB ,DISTRIBUTION BOARDS, MCB's, RCCB's, CHANGE OVER etc. 23.22.1 Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. Make: Havells/L&T/ABB/GE 23.22.1.3 TRIPLE POLE MCCB 16 to 100 Amp, 25 KA
TRIPLE POLE MCCB 300 Amp, 25 KA
TRIPLE POLE MCCB 400 Amp, 50 KA
TRIPLE POLE MCCB 600 to 800 Amp, 50 KA
EARTHING AND LIGHTENING ARRESTOR 24.1.1 Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required.
Extra for using salt and char coal/coke for pipe earth electrode as required.
Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required
Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode.
Supplying and laying 25mm x 3mm G.I. strip at 0.5 metre below ground as strip earth electrode including soldering etc. as required.
Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required.
L.T. CABLE Laying of underground cable 0.75 metre below ground level covered with sand and bricks including excavation and refilling of trenches.:- 24.2.2.5 300 sqmm to 400 sqmm 3 to 3½ Core
Laying of underground cable 0.75 metre below ground level covered without sand and bricks including excavation and refilling of trenches.:- 24.2.3.5 300 sqmm to 400 sqmm 3 to 3½ Core (Armourd)
Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 24.2.8.13 240 sqmm
HT CABLE Laying and erection of XLPE (E)II kv HT aluminium conductor armoured cable 1 metre below ground level with sand & bricks with all labour and material including digging and refilling of trench as required. 24.3.1.1 up to 120 sqmm 3 core XLPE Cable
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: 24.3.4.1 70 to 120 sqmm
MISCELLANEOUS ITEMS S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work 24.5.2.6 DWC/HDPE pipe 145/123 mm outer dia/ inner dia
Supply & Erection of L.T. outdoor type floor mounted Panel fabricated with 14 gauge CRCA sheet with Powder coating sheet steel pedestal floor mounting type mounted on M.S. Channel 75 x 40 x 6 mm totally enclosed dust and vermin proof front opening cubical type consisting of wiring and aluminiam bus bar of required capacity covered with heat shrinkable sleeves in different colour 415 volt 50 Hz A.C. supply with allied item for connection comprising of the following: - a) Main Incomer :- (i) Space for MCCB 800 Amp. 415 V T.P. three phase 50 K.A. breaking capacity with rotary handle (include the cost of the rotary handle) = 01 No. Make of MCCB /L&T/ABB/GE/Havells. (ii) RYB three phase indicator lamp = 03 No. (iii) Digital Ampere meter 0-800 amp and Digital Voltmeter 0-500V= 01Set. b) Outgoing:- (i) Space for MCCB 600A 415 V TP three phase 50KA breaking capacity with rotary handle = 01 Nos. Make of MCCB /L&T/ABB/ GE/ Havells (ii) Space for MCCB 400A 415 V TP three phase 50KA breaking capacity with rotary handle = 01 Nos. Make of MCCB /L&T/ABB/ GE/ Havells (iii) Space for MCCB 300A 415 V TP three phase 50KA breaking capacity with rotary handle = 02 Nos. Make of MCCB /L&T/ABB/ GE/ Havells (iv) Space for MCCB 100A 415 V TP three phase 25KA breaking capacity with rotary handle = 01 Nos. Make of MCCB /L&T/ABB/ GE/ Havells The panel should be nicely powder coated after degreasing phosphate treatment. The panel should be marked with incoming and outgoing feeder. The job includes interconnection (duly tape) with solid bus bars of required cross-section capable of taking full load current between each MCCB and bus bar. The cubical panel should have removable glands plates for incoming and outgoing cables and the panel should be supported on four legs of required strength. The bus bar should be supported on epoxy insulator of suitable length confirming to relevant Indian standard. The Job should be completed up to the entire satisfaction of the Engineer-in-charge of the work.
Supply & Erection of L.T. outdoor type floor mounted Panel fabricated with 14 gauge CRCA sheet with Powder coating sheet steel pedestal floor mounting type mounted on M.S. Channel 75 x 40 x 6 mm totally enclosed dust and vermin proof front opening cubical type consisting of wiring and aluminiam bus bar of required capacity covered with heat shrinkable sleeves in different colour 415 volt 50 Hz A.C. supply with allied item for connection comprising of the following: - a) Main Incomer :- (i) Space for MCCB 600 Amp. 415 V T.P. three phase 50 K.A. breaking capacity with rotary handle (include the cost of the rotary handle) = 01 No. Make of MCCB /L&T/ABB/GE/Havells. (ii) RYB three phase indicator lamp = 03 No. (iii) Digital Ampere meter 0-800 amp and Digital Voltmeter 0-500V= 01 Set. b) Outgoing:- (i) Space for MCCB 400A 415 V TP three phase 50KA breaking capacity with rotary handle = 02 Nos. Make of MCCB /L&T/ABB/ GE/ Havells (iii) Space for MCCB 300A 415 V TP three phase 50KA breaking capacity with rotary handle = 01 No. Make of MCCB /L&T/ABB/ GE/ Havells The panel should be nicely powder coated after degreasing phosphate treatment. The panel should be marked with incoming and outgoing feeder. The job includes interconnection (duly tape) with solid bus bars of required cross-section capable of taking full load current between each MCCB and bus bar. The cubical panel should have removable glands plates for incoming and outgoing cables and the panel should be supported on four legs of required strength. The bus bar should be supported on epoxy insulator of suitable length confirming to relevant Indian standard. The Job should be completed up to the entire satisfaction of the Engineer-in-charge of the work.
Supply & Erection of L.T. outdoor type floor mounted Panel fabricated with 14 gauge CRCA sheet with Powder coating sheet steel pedestal floor mounting type mounted on M.S. Channel 75 x 40 x 6 mm totally enclosed dust and vermin proof front opening cubical type consisting of wiring and aluminiam bus bar of required capacity covered with heat shrinkable sleeves in different colour 415 volt 50 Hz A.C. supply with allied item for connection comprising of the following: - a) Main Incomer :- (i) Space for MCCB 400 Amp. 415 V T.P. three phase 50 K.A. breaking capacity with rotary handle (include the cost of the rotary handle) = 01 No. Make of MCCB /L&T/ABB/GE/Havells. (ii) MCCB Changeover switch 400 Amp 415 V = 01 No. (iii) RYB three phase indicator lamp = 03 No. (iv) Digital Ampere meter 0-800 amp and Digital Voltmeter 0-500V= 01 Set. b) Outgoing:- (i) Space for MCCB 300A 415 V TP three phase 50KA breaking capacity with rotary handle = 02 No. Make of MCCB /L&T/ABB/ GE/ Havells The panel should be nicely powder coated after degreasing phosphate treatment. The panel should be marked with incoming and outgoing feeder. The job includes interconnection (duly tape) with solid bus bars of required cross-section capable of taking full load current between each MCCB and bus bar. The cubical panel should have removable glands plates for incoming and outgoing cables and the panel should be supported on four legs of required strength. The bus bar should be supported on epoxy insulator of suitable length confirming to relevant Indian standard. The Job should be completed up to the entire satisfaction of the Engineer-in-charge of the work.
Supply of 11 KV XLPE H.T. Cable size 70 sqmm X 3 core Make: Havells/Plaza/Polycab
PVC underground L.T. Cable size 400 Sqmm 3.5 Core armoured. Make: Havells/Plaza/Polycab
Som Nath Contractor
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .