Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.9 LAccepted-AOC 138 CANNING STREET GROUND FLOOR KOLKATA | KOLKATA | WEST BENGAL | L1 | Accepted-AOC Accepted | |
| 2 | L2₹9.0 L+₹9,431.90 (1.06%)Rejected-Finance 01 BALIA BALIA SAGARDIGHI MURSHIDABAD WEST BENGAL 742237 | MURSHIDABAD | WEST BENGAL | 742237 | L2 | Rejected-Finance Rejected | |
| 3 | L3₹9.0 L+₹14,701.45 (1.65%)Rejected-Finance 344 1 SB GORAI ROAD HILL VIEW PARK NORTH ASANSOL | ASANSOL | WEST BENGAL | L3 | Rejected-Finance Rejected |
Tender Value
₹11 L
EMD Value
₹22,000
Closing Date
23 May 2025, 6:00 pmClosed
Executive Engineer, BMD, PHED
Office of the Executive Engineer. Bankura Mechanical Division. P.H.E. Dte. Ailakundi, PO Kenduadihi, Bankura 722102.
Servicing and rectification work at 250 KVA AVR, 200 KVA Transformer ,Single Panel VCB, 4 Panel VCB of 11 KV Sub-Station of Baricha Water Supply Scheme under BMD,PHE Dte.
2025_PHED_838293_13
WBPHED/EE/BMD/NIeT-2 OF 2025-2026
Open Tender
MECHANICAL
Item Rate
60 days
Bankura
Please refer Tender documents.
5 documents required · 5 mandatory
₹22,000
Yes
21 Jul 2025
2 May 2025
26 May 2025
2 May 2025
23 May 2025
2 May 2025
Amount
Attending the fault at Baricha, Bankura District with carrying different Testing, Servicing kit/machine like carrying oil filter machine, BDV testing set , Insulating Resistance Checking machine (1 KV, 2.5 KV, 5 KV) 3 Phase Variac, Current Injection machine/ kit, Voltage injection machine/kit, Blower, Multimeter, Clamp meter, Different type of tools tackles, Various Testing Wires, MCBS, Wires & Cables,Lecta Cleaner, Adhesive non Adhesive PVC Tape and items for complete servicing and testing the Transformers, VCBS with connecting HT, LT cables.
Part-A 250 KVA, 7 - 12 KV / 11 KV HT AVR :
Supply and Delivery of following items
PCB Relay Card for AVR (B Unit)
Voltage Controller Potentiometer (1K)
Transformer Oil Supply for AVR (A+C) unit
Silica Gel for AVR
1100 VA UPS Make: APC, Input: 230 V AC
Charges for Oil Filtration (B Unit – 300 Ltrs. + (A+C) Unit – 600 Ltrs.)
Charges for Di-Electric Strength Test (BDV Test)
Rectification Charges for AVR Inspection and Control Operation ,PCB Relay Card replacement,voltage controller potentiometer replacement ,Silica Gel replacement ,Charges for 50 Ltrs. Oil Top-Up and Old UPS Replacement and New UPS Installation by expert technician as per direction of EIC.
Supply and delivery of All kinds of Gaskets & Oil Seal for HT & LT Bushings, Top Cover, Inspection Cover, Valve etc. of (A+C) Unit of 250 KVA AVR
Charges for gasket changes for (A+C) Unit of 250 KVA AVR by disconnecting of all HT and LT terminals, draining transformer oil, opening of top cover, arresting of any oil leakage by changing of gasket and oil seal respectively various gasket portion like top cover, inspection cover, tap switch, conservator tank, radiators, buchholz, drain valve (as where required) and HT-LT bushing portion
Supply and Painting Charges of AVR B-Unit and (A+C) Unit.
Part-B SINGLE PANEL VCB :
8 window Announciator Supply Make: Minilec, Model: MBAS0600 Volt: 90 – 270 V AC/DC
Installation and comissioning of above supplied 8 window Announciator by replacing damaged items by expert technician.
Part-C 4 PANEL VCB :
2.5 sq. mm. S/C, 1.1 KV grade Control wire supply for control wiring rectification of 4 panel VCB
Charges for Control Wiring rectification of 4 panel VCB Incomer, O/G - 1 & O/G - 2 panel, power pack control wiring re-connection, CT secondary wiring rectification & re-connection of O/G - 2 & Spare panel
Supply , Delivery and fitting fixing of Power Pack Make: Shruti Electronics, I/P: 110 / 230 V AC, O/P: 110 V DC
Supply , Delivery and fitting fixing of O/C & E/F Relay Make: Schneider, Model: Micom P111 / Easergy P1
Supply , Delivery and fitting fixing of Auxiliary Fuse with Base Current - 6 Amp.
Supply and fitting fixing of 95 sq mm x 3 core, 33 KV grade, Indoor Type, Heat Shrinkable End Termination Kit
Supply and fitting fixing of 240 sq. mm. X 3 core, 11 KV grade, Indoor type, Heat shrinkable End Termination Kit
Charges for 11 KV HT cable disconnection, 11 KV CT primary & secondary side disconnection, 11 KV CT dismantling, and dismantaling old damaged items rubbing, cleaning done by applying CRC, WD-40. After that heating treatment done, then varnishing done by applying Red Insulation Varnish to improve the IR value, after improving the IR value finally re-fitting the 11 KV CT, reconnecting the primary and secondary connection and termination of 11 KV HT cable,and fitting fixing of above supplied new items including kit joint and power charging done of Incomer, Outgoing - 1 & Outgoing - 2 Panel .
Supply and Delivery of 11 KV grade PT Fuse Make: Bussmann, Rating: 3.15 Amps.
Charges for old defective PTs Secondary wire disconnection, dismantling the defective items from circuit and newly supplied PT fuse Installation, Fixing, Bus-Bar connection, PT secondary wire re-connection and after re-fitting the PTs at circuit testing & power re-storation
Charges for PTs Secondary wire, CT Spouts & Bus-Bar Spouts Dismantling, Rubbing, Cleaning, Heating, Varnishing by applying CRC, WD-40, Red Insulation Varnish for IR Improvement and Fixing, Bus-Bar connection, PT secondary wire re-connection,Re-fitting of Incomer,OG – 1.
Paint supply for VCB Panel inside & Bus Chamber Painting
Part-D TRANSFORMER - I (200 KVA, 11 / 0.433 KV) :
All kinds of Gaskets & Oil Seal supply for HT & LT Bushings, Top Cover, Inspection Cover, Valve Etc.of 200 KVA, 11 / 0.433 KV Transformer
Charges for repairing and rectification work by gasket changes for 200 KVA, 11 KV / 433 V Transformer by disconnecting of all HT and LT terminals, draining transformer oil, opening of top cover, arresting of any oil leakage by changing of gasket and oil seal respectively various gasket portion like top cover, inspection cover, tap switch, conservator tank, radiators, buchholz, drain valve (as where required) and HT-LT bushing portion
Charges for Oil Filtration for Transformer - 1
Charges for Di-Electric Strength Test (BDV Test)
Supply and Delivery of following items
Transparent Breather with 1/2 Kg Silica Gel
4 inch. dia. WTI Make: PTCI
4 inch. dia. OTI Make: PTCI
Charges for fitting fixing above supplied items after dismantaling of damaged parts.
Supply and fitting fixing of 95 sq mm x 3 core, 33 KV grade, Indoor Type, Heat Shrinkable End Termination Kit
Supply and delivery of 2.5 sq mm 1.1 KV, 12 Core CU Ar. Cable
Laying charges of 2.5 sq. mm. X 12 core Cu. Armd. Cable, Control cable connection in between transformer marshelling box and VCB Panel
Transformer body De-Rusting and Painting (including Paint supply)
Part-E LT PANEL :
Supply and Delivery of following items-
Ring CT for Incomer - 1 & Bus Coupler Ratio - 400/5, Bus Bar Size - 50 x 6 mm.
10 sq. mm. X S/C Copper Flexible Cable for Misc Power Connection Feeder
10 sq. mm. heavy duty Cu. ring socket for Misc Power Connection Feeder
Charges for 10 sq. mm. S/C copper cables laying, connection and cable end socketing by 10 sq. mm. cu. Sockets
Charges for cleaning of rusted portion, IR improvement etc. at LT panel by suppling 2 Nos. CRC, 2 Nos. WD-40, 1 Nos. Red insulation Varnish, 1 No. HT Tape, 4 Nos. Gas Can.
Add: 18% GST
Add: 1% Cess
DAS ENTERPRISE (BID ID -6420851)
EASTERN INDIA SALES AND SERVICE (BID ID -6402039)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .