Tender Value
₹2.9 L
EMD Value
₹5,740
Closing Date
15 Mar 2022, 5:00 pmClosed
Project Engineer BPL-3
Project Engineer BPL-3
External Electrification Work Semi Urban Thana Mohda Dit.Betul 11/0.4 KV Line 1x25 KVA Transformers.
2022_MPPHC_189117_1
17/2021-2022
Open Tender
Electrical Works
Item Rate
30 days
Bhopal-3
As Per NIT
4 documents required · 4 mandatory
₹2,000
₹5,740
13 Jun 2022
8 Mar 2022
17 Mar 2022
8 Mar 2022
15 Mar 2022
8 Mar 2022
Amount
Supplying and erection of HT/LT overhead line single length supporting complete with aligning and keeping it in truly vertical position including digging pit of required size filling with 1:3:6 cement concrete of 0.60 meter. dia of required length around the pole including muffing of 0.50 meter. from ground level as per specifications with 20 cm. thick. complete as per specification. The depth of foundation shall be 1/6th of the length of pole.(a) Pcc Pole 8 Meter Long
Supplying and errection of stay set completed with stay rod, anchor plate, thimble, stay clamp, turn buckle etc. with stay wire strain insulator nut bolts as per specifications including concreting in required size and excavation in all type of soil Rocks and also foundations in cement concrete 1:3:6 complete of required size and other necessary materials complete as per specification. (A) Stay rod 16 mm with 7/3.15 mm stay wire
Supplying and fixing of Angle/ channel/flat iron, V cross Arms reinforcement of RS joist/ flat iron fittings for overhead lines and poles such as cross arms/ bracket/ clamps/ stiffness for poles etc. all required steel work including' cutting to size making proper shapes drilling scan welding etc. including nuts & bolts plan & spring wisher and other necessary material including one coat of red oxide and two coat of aluminum paint etc. as required.
Supplying and fixing Polymer type 11 K.V. pin insulator with G.I. pin of approved make on existing pole or bracket with necessary materials and hardware complete as required.
Supplying and fixing polymer type 11 K.V. disc (strain) insulator of approved make on existing pole or bracket with necessary materials and hardware complete as required.
Supplying and drawing AAAC conductor of approved make with stringing, making off complete with binding at existing insulator, jointing , jump ring, billing off connecting, making 'D' loops connections etc. complete and clearing of obstacles (if any) as specified and directed. (A) AAAC Rabbit Conductor 0.05 Sq. Inch (55 sq.mm) aluminum or Equivalent .
Supplying and fixing of danger/ caution Board as per specification with necessary materials complete for H.T. lines and other equipments as required.
Supplying and fixing 12x16 gauge barbed wire antidumping device (900 mm and3.5kg wire on pole) around the existing H.T. pole and sub station poles for safety measures as per IE rules including all staples and all other necessary materials complete as per mpseb specification.
Supplying, installing, connecting, testing and commissioning of 11/0.4 K.V. 3 Phase 50 Cycle Oil Immersed,Naturally Cooled,Out door Type transformer Connected Delta on H.T. Side and star on L.T. Side hand Operated Off Load Tap Changer Switch above 25 KVA Oil Conservertor with drain valve Plug 25 KVA and above Dehydrating Sillica Gel Breather on Eye Level,rating and diagram plate two Eathing terminal,Lifting lugs,Oil level Gauge drain valve with plug temperature not Exeeding 500C on load,Oil Filling Hole with plug,four Unidirectional roller Arcing Horns,Explosion vent ,terminal arrangement bushing on H.V. side and Cable Box on LV side first fillling of oil upto desired level and transformer installing on existing Structure with all required materials Arrangement as Required as Per IS Specification Marked ISI & 5 Star Rating. (A) 25 KVA 11 / 0.4,Level III
Providing and fixing outdoor type pole mounting weather, dust and vermin proof L.T. distribution box made of 14/16 gauge, M.S. sheet with clamping arrangements, lockable hinged door duly painted on all sides with red oxide antirust and corrosion treatment two coats of synthetic enamel paints of approved make and shade, consisting of following fittings. L.T. Distribution box suitable for 25.KVA.transformer with required Amp MCCB on incoming side and PF HRC units on outgoing side. For 25KVA Transformer (63 Amp. 25 KA MCCB ,80 Amp HRC Fuse 9no.& Busbar) Complete as required as per MP SEB latest Specification.
Commissioning of D P structure over existing support with panting in an approved manner consisting of following :- (A) D. C. cross arm with clamp, nuts & bolts (100 x 50 mm only ) - 1 set (B) 11 KV D. O. fuse unit, lightings arrangement and AB swich mounting channel with nuts and bolts (75 x 40 mm channel) of require - 1 set (C) 11 KV Polymer AB swich as required ( set of 3 Nos.) - 1 set (D) Transformer mounting cross arms / channels with clamps nuts and bolts (100 x 50 mm channel ) - 1 set (E) 11KV Polymer Do fuse unit ( set of 3 no.) - 1 set (F) Transformer clamping set (50x50x6 mm angle ) with nuts and bolts etc. complete - 1 set (G) Transformer belting set (50x50x6 mm angle) with nuts and bolts etc. complete - 1 set (H) 11 kv polymer lightning arrestor ( 9 kv gapless type ( 5 kA ) for DTR ) ( set of 3 No.) - 1 set (I) supplying , fixing, testing and connecting of complete earling set of 7 No. as per MPMKVVC.Ltd. circular No DS CO M/EZ/ WS/1516/DT 17-03-2008 and approved drawing for transformer sub - station including all materials GI Strips, GI wires, Charcoal power salt excavation of pits in all types of soils/rocks etc. as required complete .( 1 set of 5Nos.) -1 set (J) Distribution panel mounting channel and clamp with nuts & bolts etc. (75 x 40 mm channel ) 1 – set(K) Supplying , fixing, testing and Commissioning of DTR Meter LT. 3 phase 4 wire 3X240 volts 3 A. LTCT operated 3 phase 4 wire 3x63, 5 volts , LB = 5 amps lmax 10 amp trivector meter glass of accuracy 0.5s DLMS complaint category a meter along with GSM ( GPRS compactable ) modems with box i/c all accessories and formalities as per MPMKVVCL as required. or 3P 4w - 5A LTCT class 5s DLMS compliant type c. rs - 232. Port box MRI LTCT 100/5A i/c meter box with TTB etc as required.(L) SF & T and HT tape for covering LT bushing i/c windings and blower fitting complete minimum 30 meter or as required. D.P. Structure Complete as above (A to L)
Supplying ,laying ,testing, and commissioning of P V C insulated PVC heavy duty power cable confirming to lS 15541964,1100 volt grade cable Of approved make in trench ,G I pipe Air (laying on pole) trench, i/c cost of excavation in any type of soil/rock etc. including connection through lugs by cramping method glands etc as required as per specification.Supplying laying testing and commissioning.UnArmoured single core XLPE insulated aluminum conductor cable. 35 sq mm.
OMSAN ELECTRICALS
NEERAJ KUMAR JAIN
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .