| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹94.8 CrAccepted-AOC BAKRON KA WADA NEAR NEELAM CINEMA JODHPUR ROAD BALOTRA BARMER RAJASTHAN 344022 | BALOTRA | BARMER | RAJASTHAN | 344022 | ₹94.8 Cr | L1 | Accepted-AOC Being Lowest |
| 2 | L2₹104.9 CrRejected-Finance | ₹104.9 Cr | L2 | Rejected-Finance Not Being Lowest |
| 3 | L3₹112.9 CrRejected-Finance L 87 STREET NO 7C MAHIPALPUR EXTENSION NEW DELHI 110037 | NEW DELHI | NEW DELHI | DELHI | 110037 | ₹112.9 Cr | L3 | Rejected-Finance Not Being Lowest |
| 4 | L4₹113.8 CrRejected-Finance | ₹113.8 Cr | L4 | Rejected-Finance Not Being Lowest |
| 5 | Rejected-Technical | - | - | Rejected-Technical Not Eligible as per NIT |
Tender Value
₹115.3 Cr
EMD Value
₹15 L
Closing Date
17 Nov 2022, 6:00 pmClosed
Chief Engineer Bathinda, Bathinda Mil Stn
HQ Chief Engineer Bathinda, Bathinda Mil Stn
PROVISION OF TECH INFRASTRUCTURE AND ALIED SERVICES UNDER GE P BIKANER ON EPC MODE
2022_MES_538640_1
CE BTZ/BKN/TOKEN-14 OF 2022-23
Open Tender
Civil Works
1095 days
Bikaner
As per NIT
10 documents required · 10 mandatory
₹3,000
GE (P) Bikaner
₹15 L
Yes
31 Dec 2022
16 Jul 2022
19 Nov 2022
16 Jul 2022
17 Nov 2022
4 Nov 2022
16 Jul 2022 - 30 Jul 2022
Amount
Sch 'A' Sec - I , (BUILDING /STRUCTURE WORKS)
Engineering procurement and construction of Tech Infrastructure work as listed in Schedule ‘A’ Section-I (Srl item No 1 and 2) complete as detailed in scope of work, DBR and other documents of the tender complete all as specified and as directed.
Engineering procurement and construction of Tech Infrastructure work as listed in Schedule ‘A’ Section-I (Srl item No 3 to 28) complete as detailed in scope of work, DBR and other documents of the tender complete all as specified and as directed.
Engineering procurement and construction of Tech Infrastructure work as listed in Schedule ‘A’ Section-I (Srl item No 29 ) complete as detailed in scope of work, DBR and other documents of the tender complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “INTERNAL ELECTRIFICATION WORKS" as listed in Schedule ‘A’ Section - II (Part-I)
Sch 'A' Sec - II (Part-II), (INTERNAL ELECTRIFICATION WORKS)
Material and labour for concealed Point wiring for one light point/fan point /bell point controlled by one switch (using red, black and green colour wires as colour coding) complete with 1.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 60mm deep, suitable size) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches/ socket / regulator etc, including provn of 1.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed. (switches/ socket / regulator shall be measured and paid separately under appropriate item of BOQ).
All as per above Srl item No. 08 but for one socket out let 5 Amps point controlled by one switch (on same board) complete all as specified and as directed by Engineer-in-charge. (switches, sockets etc. shall be measured and paid separately under appropriate item of BOQ/Sch A).
All as per above Srl item No. 08 but for one socket out let 5 Amps point controlled by one switch (on independent board and not below the any other switch board) complete all as specified and as directed by Engineer-in-charge. (switches , sockets etc. shall be measured and paid separately under appropriate item of BOQ/Sch A).
Material and labour for concealed Point wiring for one light point controlled by two Nos- two way switch (using red, black and green colour wires as colour coding) complete with 1.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 60mm deep, suitable size ) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switch, including provn of 1.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed. (switches shall be measured and paid separately under appropriate item of BOQ).
Material and labour for concealed Point wiring for one socket out let 15/16 Amps point controlled by one switch (on independant board) (using red, black and green colour wires as colour coding) complete with 2.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 60mm deep, suitable size ) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches / socket, including provn of 2.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed. (switch, socket shall be measured and paid separately under appropriate item of BOQ).
Material and labour for concealed Point wiring for one socket out let 15/16 Amps point controlled by one switch (on independant board) (using red, black and green colour wires as colour coding) complete with 4 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 25mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 60mm deep, suitable size ) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches / socket, including provn of 4 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed. (switch, socket shall be measured and paid separately under appropriate item of BOQ).
Supply and fixing LED lamp minimum 3 star rated 9W LED B-22 base complete all as specified and directed by Engr-in-Charge with following specifications (a) Lumen system efficacy of lamp should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) CRI : More than 70
Material and labour for concealed wiring for TV antenna connection complete with coaxial RG-6 heavy duty PVC insulated sheathed cable with copper conductor having single strand of 0.7 mm dia and a aluminium wire net drawn through and including PVC conduit 25mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box of size 100mm x100mmx50mm concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular TV antenna connection socket outlet, including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed. (TV antenna connection socket outlet shall be measured and paid separately under appropriate item of BOQ).
Material and labour for concealed wiring for telephone connection complete with PVC insulated sheathed cable with copper conductor having single strand of 0.4 mm dia one pair taped for telephone wiring drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box of size 100mm x100mmx50mm concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular telephone connection socket outlet, including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed. (Telephone socket shall be measured and paid separately under appropriate item of BOQ).
Supply and fixing modular type (1 module) 2 pin TV antenna connection socket outlet round flush type duly marked with symbol of TV complete all as specified and as directed by Engineer-in-charge. Note :- Inner/outer plate for fixing the socket shall be included in point wiring item of BOQ.
Supply and fixing modular type (1 module) telephone connection socket outlet flush type duly marked with symbol of telephone complete all as specified and as directed by Engineer-in-charge. Note :- Inner/outer plate for fixing the socket shall be included in point wiring item of BOQ.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 16 Sqmm single core (05 run i.e 4 runs for main 3 phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 40mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Five runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 10 Sqmm single core (05 run i.e 4 runs for main 3 phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 32mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Five runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 6 Sqmm single core (03 run i.e 2 runs for main phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 25mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Three runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 4 Sqmm single core (03 run i.e 2 runs for main phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 20mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Three runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Supply and fixing LED complete fitting including batten, T-8 Retro LED polycarbonate 1 x 20 Watt, appx 4 feet long, environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts. (c) Temp operating range : Minus 10°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP-20. (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the same make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection minimum 2.5 kV. (l) CCT : 6500K (m) CRI : Morethan 80 (n) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing LED light fitting 1 x 10 Watt, appx 2 feet long environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to light fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max 10%. (f) IP rating : IP-20. (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the same make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection minimum 2.5 kV. (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing energy efficient LED street light fitting of 25W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street/Roadway luminaire, with driver, including electric connection with using 2 core flexible copper conductor cable 1Sqmm from ceiling rose to light fitting, fixing the light fitting with new bracket made out of GI tubing light grade 25mm dia, 1.2 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron size 25x3 mm with suitable nuts and bolts for fixing of bracket including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP65. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : More than 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing in replacement energy efficient LED wide angle flood light fittings of 500 W capacity with driver, Epoxy powder coated pressure die cast aluminium alloy housing and front cover clear toughned glass, including electric connection with suitable copper cable and including fixing arrangement with suitable nut bolts or any hanging hook etc, complete fitting and all accessories with following specifications and all as directed by Engr-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP65. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : More than 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing in replacement energy efficient LED wide angle flood light fittings of 250 W capacity with driver, Epoxy powder coated pressure die cast aluminium alloy housing and front cover clear toughned glass, including electric connection with suitable copper cable and including fixing arrangement with suitable nut bolts or any hanging hook etc, complete fitting and all accessories with following specifications and all as directed by Engr-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP65. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : More than 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing in replacement energy efficient LED wide angle flood light fittings of 200 W capacity with driver, Epoxy powder coated pressure die cast aluminium alloy housing and front cover clear toughned glass, including electric connection with suitable copper cable and including fixing arrangement with suitable nut bolts or any hanging hook etc, complete fitting and all accessories with following specifications and all as directed by Engr-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP65. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : More than 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing recessed LED ceiling mounted with wide light window for maximised glare free output suitable for 600x600mm and ceiling cutout 595x595mm modular grid/POP ceiling finishes complete fitting with separate electronic driver and high brightness LED 36 Watt, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to light fitting, complete fitting and all accessories with following specifications and all as directed:- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP20. (g) CCT : 6500K (h) CRI : Morethan 80 (j) CRCA pre coated housing. (k) LED Driver of the make as of the luminaire. (l) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (m) Surge protection minimum 3 kV. (n) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily) Note for hangar lights :- All lights in hangar shall be fixed below bird proofing net.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 250 Amp rated bus bar) VTPN, 4 Way, suitable for mounting MCCB/MCB, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCCB/MCB shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) TPN, 4 Way, suitable for mounting MCB/Isolator, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB’s shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 12 Way 240V, suitable for mounting MCB/Isolator, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB’s shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 8 Way 240V, suitable for mounting MCB/Isolator, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB’s shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 4 Way 240V, suitable for mounting MCB/Isolator, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB’s shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 2 Way 240V, suitable for mounting MCB/Isolator, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB’s shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed in wall or as directed) single pole and neutral sheet metal enclosure (AC Box) with a two pin and earth plug and socket complete with one single pole MCB of capacity 20 Amps, 240 volts, AC supply complete all as specified and directed by Engineer-in-Charge.
Supply and fixing MCCB of capacity 100 Amp, FP, 415 volt, short circuit breaking capacity not less than 16KA , thermal magnetic trip, setting 80-100%, Icu-100% Ics confirming to IEC-947, IS-13947, including thimbles, nuts, bolts, washers etc , MCCB fixing in DB including making incoming, outgoing connections complete all as specified and as directed by Engineer-in-charge .
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 63 Amps, TPN with over load and short circuit protection and rupturing capacity not less than 16 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 40 Amps, TPN with over load and short circuit protection and rupturing capacity not less than 16 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 40 Amps, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 32 Amps, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 16 Amps, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 06 to 32 Amps, SP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and hanging /fixing ceiling fan 1200 mm sweep AC Supply (Input Voltage Range ; 120 to 280V), BLDC type, 5 star rated, BEE and ISI Marked super enamelled, copper winding of 'B' class insulation, single phase, minimum 30W (± 10%), Temperature rise 40 degree maximum without remote with and including capacitive regulator, 03 No blades, down rod including accessories, white colour, total harmonic less than 10%, 5 speed, hanging in position including making connection with flexible cord three core twisted copper conductor of suitable size from ceiling rose to fan complete all as specified. Note :- (i) Serial Number as issued by Engr-In-Charge of celing fan and GE Office name shall also be written on fan with red colour permanent marker and fixing of regulator on switch board, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply and fixing exhaust fan (heavy duty) steel body, AC single Phase 230V, 50 Cycle per second, size 300mm sweep with blades and frame including self closing GI louvers off mode protection against birds etc mounted in suitable opening arrangement and connecting up and including three core PVC Insulated PVC Sheathed copper conductor flexible cable1.0 Sqmm drawn in flexible PVC conduit and hanging on wall with 4 Nos steel fastners 10mm dia 100mm long and making good the disturbed surface complete all as specified and as directed by Engineer-in-charge. Note :- (i) Serial Number as issued by Engr-In-Charge of fan and GE Office name shall also be written on fan with red colour permanent marker, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply and fixing exhaust fan (heavy duty) steel body, AC single Phase 230V, 50 Cycle per second, size 450mm sweep with blades and frame including self closing GI louvers off mode protection against birds etc mounted in suitable opening arrangement and connecting up and including three core PVC Insulated PVC Sheathed copper conductor flexible cable1.0 Sqmm drawn in flexible PVC conduit and hanging on wall with 4 Nos steel fastners 10mm dia 100mm long and making good the disturbed surface complete all as specified and as directed by Engineer-in-charge. Note :- (i) Serial Number as issued by Engr-In-Charge of fan and GE Office name shall also be written on fan with red colour permanent marker, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Subtotal
Lump sum price worked out by the tenderer for “INTERNAL WATER SUPPLY WORKS" as listed in Schedule ‘A’ Section - III (Part-I)
Sch 'A' Sec - III (Part-II), (INTERNAL WATER SUPPLY WORKS)
Supply and fixing chromium plated Toilet paper/Roll Holder with Stainless Steel Flap, fixed on wall with chromium plated brass screws and PVC plug complete all as specified and as directed.
Supply and fixing 15 mm bore two way Angle stop valve with flange, cast copper alloy chromium plated, fancy type screwed down high pressure with on/off handle screwed end for iron pipe or for unions and fixed complete all as specified and as directed.
Supply and fixing central hole basin mixer valve with regular spout, 15mm bore, brass chromium plated, for mixing hot & cold water, including fixing accessories with fittings for WHB complete all as specified and as directed.
Supply and fixing wall mixer valve 15mm bore, brass chromium plated, for mixing hot & cold water with provision for overhead shower with L bend, screwed down for iron pipe suitable for fixing to wall, complete all as specified and as directed.
Supply and fixing corner Glass shelf made of 5mm thick sheet toughened glass of size 300x300mm, including chromium plated bracket and guard railing fixed along wall with chromium plated catcher brackets, brass screws and PVC plug complete all as specified and as directed.
Supply and fixing chromium plated soap dish holder, fixed on wall with chromium plated brass screws and PVC plug complete all as specified and as directed.
Supply and fixing Towel Rack 600mm Long with Lower Hangers, Stainless Steel with flange cup, fixed on wall with chromium plated brass screws and PVC plug complete all as specified and as directed.
Supply and fixing Stainless steel solid body fancy type peg set of six and fixed in position with steel screws complete all as specified and as directed by Engineer-in-Charge.
Subtotal
Lump sum price worked out by the tenderer for “RUNWAY, TAXI TRACK AND DISPERSAL WORK" as listed in Schedule ‘A’ Section -IV (Part-I)
Sch 'A' Sec - IV (Part-II), (RUNWAY, TAXI TRACK AND DISPERSAL WORK)
Material and labour for laying and compacting 150 mm (compacted thickness) Granular Sub Base (GSB) Grade V in a single layers (grading and physical requirements as per Table 400-1 and 400-2 respectively of MORTH specifications for road and bridge works) over compacted sub grade with natural sand, crushed gravel, crushed stone, crushed slag, or combination thereof as per grading required. The material shall mechanically mixed, spread and leveled on the sub grade by using motor grader of adequate capacity, and rolling with vibratory roller capacity 80-100KN static weight for achieving required compaction density of at least 98% of the minimum dry density Consolidating to required gradient and camber complete all as specified and directed. Finish surface tolerance as per table 900-2 of MORTH specification for Road and Bridge works, 2013 and all as specified and directed.
Material and labour for laying and compacting 150 mm thick (Compacted thickness) of Wet Mixed Macadam (WMM), manufactured in WMM plant (Physical requirement and grading as per Table 400-12 and 400-13 respectively of MORTH specifications for Road and Bridge works), material comprising of clean, crushed, graded aggregate and granular material premixed with water to a dense mass, spreading using sensor paver including spreading and compacting using double drum smooth wheeled vibratory rollers with 80-100 KN static weight for achieving required compaction density of atleast 98% of the maximum dry density and rolled consolidated to required gradient and camber complete as specified. If water absorption value of coarse aggregates is greater than 2%, the soundness test shall be catered on the material delivered at site as per IS : 2386 (Part-5). The finished surface tolerances as per Table 900-1 of MORTH specifications on Road and Bridge works all as specified and directed.
Material and labour for Dry Lean Concrete (DLC) of compacted thickness 150 mm in a single layer of aggregate gradation as per Table 1 of SP 49:2014 having 7 day average compressive strength not less than 7 MPa. Min cement content not less than 140 kg/cum. DLC mixed in Batching Plant, transported to site and laid by electronic sensor paver including spreading and compacting using high amplitude tamping bars on paver (initial compaction) further by double drum smooth wheeled vibratory rollers with 80-100 KN static weight to achieve minimum dry density not less than 97% of that achieved during the trial length construction, necessary finishing etc complete all as specified and directed.
Material and labour for 400 Micron HDPE sheet (Virgin Quality) water proof, wrinkle free polyethylene sheeting without puncture having minimum weight 390 gm/Sqm over tack coat/sand cushion as specified in the design with overlap between adjacent strips as minimum 300 mm and transverse joints at ends as minimum 300 mm complete all as specified and directed. Maximum standard width available and as approved by GE without joints, manufactured by multilayer technology using 100% virgin raw material, conforming to IS:10889 all as specified an directed.
Supply and laying 10mm thick sand cushion with clean sand free from residual, organic and deleterious materials spread evenly to uniform thickness laid over DLC layer. The sand cushion must not contain stones/others hard or uneven matter complete all as specified and as directed. Note :- The rate are inclusive of screening of sand at site if required to remove organic materials etc.
Supply only non circular, virgin, synthetic, monofilament polyester fibres of length 12mm to 18mm, specific gravity 1.34 to 1.39, UV stable, alkali resistant equivalent diameter 15-40 micron minimum melting temperature 250 degree centigarde and minimum tensile strength 300 Mpa be used as per manufacturer specification in design. Design mix to be prepared after incorporating fibres as specified and as directed.
Material and labour for Pavement Quality Concrete (PQC) 210 mm thick of minimum 28 days field flexural strength of 45 Kg/Sqm or 4.5 MPa, aggregate gradation as per Table 3 of IRC 15-2017, coarse aggregate of clean, hard, strong, dense, non-porous and durable pieces of crushed stone or gravel, fine aggregates of clean natural sand or crushed stone sand or combination of both, using minimum 400 kg/cum of cement content with non-circular synthetic fibre. Rate of dosage of fibers as specified by manufacturer. PQC laid, spread and compacted with slip-form paver including curing and tinning by Texturing cum Curing Machine complete all as specified and directed. Required surface texturing to be done as specified in Clause 10.1.14 and Table 9 of IRC: 15-2017 all as specified and directed. Note:- (i) Construction joints, dummy joints(contraction joints) and expansion joints shall be measured and paid separately under respective items. (ii) Deduction shall be made in computing concrete quantity for expansion joints. (iii) Polyester non-circular fiber as secondary reinforcement mixed in concrete shall be measured and paid separately as `Supply only” under relevant item of this schedule/BOQ.
Material and labour for forming 25mm wide expansion joint for 210 mm thick PQC by cutting using high RPM diamond cutter of appropriate size, straight and smooth edges, early entry saw and subsequent full depth cutting. Joint cleaned thoroughly with application of compress air. Joint shall be made dry, vacuum cleaned and free of dirt, oil, vegetation and other debris. The joint then filled with pre-molded 25 mm thick compressible polyethylene closed cell type filler board as specified, thereafter application of two coats of primer with thin brush forward and backward movement at an interval of 30 minutes before placing the backup rod and pouring the sealant. Placing of closed cell medium density, crossed linked polyethylene foam backup rod of 30 mm dia, over filler board and filled with polyurethane based sealant complying with BS-5212, BS-4254 and EN-141875-2003 with minimum movement accommodation factor (MAF) of +/- 30% having minimum 10 year performance guarantee, applying masked tape on the edges of joints to prevent accidental spill age of sealant and removing the masking tape after filling of sealant as per the method specified and directed by the manufacturer.
Material and labour for forming contraction (Dummy) joints of 8mm wide and depth 1/3 to 1/4 the thickness of slab (210mm thick PQC) using high RPM diamond cutter with an initial saw cut of 3mm soon after concrete has set, widening the first saw cut to 8mm width and 24mm deep from the top using diamond bit cutter of appropriate size, straight and smooth edges. Joint cleaned thoroughly with application of compressed air. Joint shall be made dry, vacuum cleaned and free of dirt, oil, vegetation and other debris. Application of two coats of primer with thin brush by forward and backward movement at an interval of 30 minutes before placing the backu0p rod and pouring the sealant placing of closed cell, medium density, crossed linked polyethylene foam backup rod of 10 mm dia, application of bond breaker tape on top of back up rod for complete width of the joint and filled with polyurethane based sealant complying with BS-522, BS-4254 and EN-141875-2003 with minimum movement accommodation factor (MAF) of +/- 30% having minimum 10 year performance guarantee, applying masking tape on the edges of joints to prevent accidental spill age of sealant and removing the masking tape after filling of sealant as per the method specified and directed by the manufacturer.
Material and Labour for cutting of construction joints 25mm deep and 10mm wide by early entry saw cut using diamond bit cutter of appropriate size, straight and smooth edges. Joint cleaned thoroughly with application of compressed air. Joint shall be made dry, vacuum cleaned and free of dirt, oil, vegetation and other debris. Application of two coats of primer with thin brush by forward and backward movement at an interval of 30 minutes before placing the backup rod and pouring the sealant. Placing of closed cell, medium density crossed linked polyethylene foam backup rod of 12mm dia, application of bond breaker tape on top of back up rod for complete width of the joint and filled with polyurethane based sealant complying with BS-5212, BS-4254 and EN-141875-2003 with minimum movement accommodation factor (MFA) of +/- 30% having minimum 10 year performance guarantee, applying masked tape on the edges of joints to prevent accidental spill age of sealant and removing the masking tape after filling of sealant as per the method specified and directed by the manufacturer.
M&L for soil stablisation of 500mm sub grade soil by uniform mixing at site with OPC cement @ 5% by weight of soil (5% cement to be assumed for rate estimation only, actual type of additive and percentage of blending to be executed as given in mix design, mix design to also contain recommended test with their frequency for quality control). Exact quantity of cement shall be arrived after trials on ground to achieve the required CBR/K value (4Kg/Sq cm as per pavement design). Execution will be done by mechanical means (like rotavator), automatic cement spreader streumater adding required water and rolling and compacted with power vibrating roller/vibratory soil compactor to achieve K value of not less than 4 Kg/Sq cm, complete all as specified and as directed. Rate will include pulverizing of soil, spreading of cement/ stablizer as required by design mix, sprinkling of water and compacting to achieve finish of sub grade as per Clause 902 of MoRTH specifications. Relevant provisions of IRC SP : 89-2010 will be applicable for process and quality control. Note:- (i) No extra amount paid for cement separately. (ii) Proof rolling of the stabilized sub grade to be done for confirmation of desired performance.
Subtotal
Lump sum price worked out by the tenderer for “RCC HUME PIPE DUCT ACROSS RUNWAY AND TAXI TRACK WORKS" as listed in Schedule ‘A’ Section -V
Lump sum price worked out by the tenderer for “SEWAGE DISPOSAL WORK" as listed in Schedule ‘A’ Section - VI (Part-I)
Sch 'A' Sec - VI (Part-II), (SEWAGE DISPOSAL WORK)
Supply and laying DWCPE (SN8) drain pipes 150mm inner dia (160mm OD) as per IS-16098 (Part-II), laid in trenches on and including bed 100mm thhick beding comprising of well compacted clean poorly graded gravel, gravel/sand mixture with little or no fines to required slope, including all accessories/fittings/jointing ring, jointing and testing complete all as specified and as directed by Engineer-in-Charge. Note : Excavation, earth work and pedestal /anchorage if required shall be measured & paid separately under appropriate item of BOQ/Sch A.
Supply and laying DWCPE (SN8) drain pipes 200mm inner dia (238mm OD) as per IS-16098 (Part-II), laid in trenches on and including bed 100mm thhick beding comprising of well compacted clean poorly graded gravel, gravel/sand mixture with little or no fines to required slope, including all accessories/fittings/jointing ring, jointing and testing complete all as specified and as directed by Engineer-in-Charge. Note : Excavation, earth work and pedestal /anchorage if required shall be measured & paid separately under appropriate item of BOQ/Sch A.
Supply and fixing LLDPE septic tank of capacity 5 users (minimum 2000 ltr) designed to carry sewage and sludge water, including excavation and earth work in any type of soil, installed over and including 100mm thick PCC (1:4:8) type D-2 including all necessary fittings for connecting to inlet and out let, complete all as specified and as directed.
Soakage well of size 1.20 m dia and 3.00 m effective depth for excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonry in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size for 5 users complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “ROAD, PATH & CULVERT WORK" as listed in Schedule ‘A’ Section -VII (Part-I)
Sch 'A' Sec - VII (Part-II), (ROAD, PATH & CULVERT WORK)
Material and labour for continuous edging in road work of stone kerbs (lime or sand stone) of thickness 50mm to 80mm, length not less than 450mm and depth 300mm roughly squared and dressed laid dry including earth work, compacting around and making good complete all as specified and as directed.
Providing, laying Granular Base (GSB) 150mm thick of Grade V of table 400-2 of MORTH, IRC specification of layer not exc 150mm thick by using mechanical Paver and roller necessary form work, finishing, spreading , grading leveling and rolling etc complete all as directed and as specified (Physical prosperities, procedure for spreading and compaction shall be considered and executed as mentioned in section 400 sub clause 401.7 of MORTH, IRC specification /TI 09/2018.
Providing laying 150mm thick (Compacted thickness) Wet Mix macadam (WMM) in two layers 75mm thick each compacted separately with crushed stone aggregate of specified grading spread using mechanical paver as specified rolled and consolidated as specified to required gradient and camber complete all as specified and as directed.
M&L for asphaltic semi dense concrete 40mm consolidated thickness with 5.4% VG Gde binder content by weight of total mix (actual binder content should be as per design mix) rolled & compacted to required camber and gradient complete all as specified and as directed.
Material and labour for Thermo plastic paint road marking 2mm thick painting (lines, dashes, arrows, letters etc) with road safety spikeries glass beads @ 8% by weight including preparation of new or previously treated road surfaces and applying paint by using special applicator machine with heating arrangement complete all as specified and as directed.
Supply and fixing Delineator with twin reflector made out of MS 51mm dia and mounted on oval shape in fiber plate of dimension 302mm x 167mm fitted with 02 Nos 100mm dia high reflective reflectors on both sides along with 02 Nos 70mm x 23mm rectangular reflectors on each side for excellent reflective in the night hours, alloy powder coated and rust resistant height of delineator 1000mm complete all as specified and as directed.
Supply and laying/fixing 80 mm thick (M-40 grade) precast interlocking tile/paving block factory casted (made by using PVC/ Rubber moulds on Vibrating Table Machine) using grey cement and no pigment, any shape haxagon / trigular / zigzag / I-shaped etc, as directed, confirming to relevant IS, laid over and including 25mm thick layer of sand cushining and filling the interstices etc with sand complete all as specified and as directed.
Supply and laying/fixing 80 mm thick (M-40 grade) precast interlocking tile/paving block factory casted (made by using PVC/ Rubber moulds on Vibrating Table Machine) using grey cement and with pigment, any shape haxagon / trigular / zigzag / I-shaped etc, as directed, confirming to relevant IS, laid over and including 25mm thick layer of sand cushining and filling the interstices etc with sand complete all as specified and as directed.
Material and labour for precast cement concrete M-20 type B1 using 20mm graded stone aggregate as in factory made kerb stone kerb stone as per IS 5758 : 1984, quoin blocks, apex stones, boundary pillars, bonders ( for stone walling), etc of size as directed with plain fair faces, chamfers, weatherings, slightly rounded or chamfered angles etc laying and setting in cement mortar (1:4) complete all as specified and as directed.
S&F 110mm bore PVC pipe pressure rating 4kg/cmsq (SWR) as in weep holes complete all as specified and as directed. Note :- Qty 980 RM for Road work and 350 RM for security wall, gate and fencing work.
Subtotal
Lump sum price worked out by the tenderer for “AREA DRAINAGE AND SUB SURFACE DRAIN ALONG RUNWAY BOTH SIDES WORK" as listed in Schedule ‘A’ Section - VIII (Part-I)
Sch 'A' Sec - VIII (Part-II), (AREA DRAINAGEAND SUB SURFACE DRAIN ALONG RUNWAY BOTH SIDES WORK)
M & L for providing and laying 200mm thick GSB (Granular Sub Base) Grade-V of table 400-1 of MORTH,IRC specification spreading in layers not exc. 10cm thick using graded stone aggregate of size 63mmm. Watering, ramming/rolling by tendon vibratory roller and finishing to longitudinal gradient (1:150) and transverse gradient 1.5% for achieve field compaction at least to 98% of MDD(Max Dry Density) of soil complete all as specified and as directed.
Geo fabric wrapped around perforated pipe or wrapping trench drain to hold aggregate incl overlap Geo-fabric shall be non-woven type 1.4 mm thick confirming to IRC : SP-59 (2019) and shall be suitable for sub surface dranage work complete all as specified and as directed.
S & F 160mm DN HDPE, PN-6 confirming to IS -4984 (1995) semi perforated pipe incl fitting like sockets/coupling, tees etc. laid in trenches complete all as specified and as directed.
S & F 160mm DN HDPE, PN-6) pipe confirming to IS -4984 (1995) single socketed in any length with rubber ring joints laid in trenches complete all as specified and as directed.
Supply and filling fine dry and clean sand, complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “SECURITY WALL, GATE, FENCING, BRICK STAGING FOR TRANSFORMER & DG SET AND ROAD FURNITURE WORKS" as listed in Schedule ‘A’ Section - IX (Part-I)
Sch 'A' Sec - IX (Part-II), (SECURITY WALL, GATE, FENCING, BRICK STAGING FOR TRANSFORMER & DG SET AND ROAD FURNITURE WORKS)
S & F concertina coil with punched tape of 600mm dia, centre core wire shall be minimum 2.5mm dia of mild steel conforming to IS 4454 (Part-I), galvanised coating of steel concertina coil shall confirm to requirements as laid down for medium coated wire in IS 4826 "Hot dip galvanised coating of round steel wires" concertina coil shall be fixed in diamond shape the help of dove tail two handles and spikes shall be fixed at both ends of coil, complete all as specified and as directed.
Material and labour for Forming 'V' groove of uniform size 12mm wide and 12mm deep in plasteringof walls and finishing smooth at junction of RCC framed column, beam, band and brick work complete as specified and as directed.
Material and labour for stainless steel frame for sign board / guide map with hollow pipes square/round tube, SS flat section of size and thickness as approved, SS grade-340, including necessary welding, polishing and fixing with nut and bolts complete all as specified and as directed.
Supply and fixing of 3mm thick high intensity prismatic retro reflective sheeting series 3930 of approved colour / shade fixed on solid 5mm thick plain colour PVC sheet fully covered including letter writing information / logo with same sheeting computerised cut in approved colour / shade. The letters approximately covering upto 50 % area of the board complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “RAIN WATER HARVESTING WORK" as listed in Schedule ‘A’ Section - X
Sch 'A' Sec - XI, (AIR CONDITONING WORK)
Supply & installation of voltage stabilizer of capacity 4 KVA for automatic operation, single phase naturally air cooled indoor type & Design for input voltage variation between 170V to 250 V with output voltage stabilizer at 230 v with accuracy of +/- 2.5% complete as specified and as directed.
Supply & installation of voltage stabilizer of capacity 5 KVA for automatic operation, single phase naturally air cooled indoor type & Design for input voltage variation between 170V to 250 V with output voltage stabilizer at 230 v with accuracy of +/- 2.5% complete as specified and as directed.
Supply and fixing modular socket out let 25 Amp flush type (two module) with protector and accessories for AC complete with inner plate complete with one single pole MCB of capacity 20 Amps, 240 volts, AC supply complete all as specified and as directed.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white and green colour or as directed) with 4 Sqmm single core (03 run i.e 2 runs for main phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor drawn through and including PVC conduit 20mm dia (medium quality ISI marked), on independent circuit from DB including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :-Three runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment.
Subtotal
Lump sum price worked out by the tenderer for “SUMMER APPLIANCES WORK" as listed in Schedule ‘A’ Section - XII (Part-I)
Sch 'A' Sec - XII (Part-II), (SUMMER APPLIANCES WORK)
Supply and fix frost free single door refrigerator electric driven single phase 230 volts, AC 50 Hz of Capacity 195 Ltr with BEE approved, BEE minimum 3 star rated complete all as specified and as directed.
Supply, install, testing frost free deep freezer metal glass top electric driven single phase 230 volts AC, 50 Hz of capacity 320 Ltr with BEE aproved, minimum 3 star rating complete including electric connection through voltage stabilizer complete all as specified and directed.
Supply, installation and testing of water cooler Electric driven (Single) phase having approx storage capacity of 40 ltr and nominal cooling capacity of 40 ltrs per hour including electric connection complete all as specified and as directed.
Supply, installation and testing of water cooler Electric driven (Single) phase having approx storage capacity of 80 ltr and nominal cooling capacity of 40 ltrs per hour including electric connection complete all as specified and as directed.
Supply, installation and testing of water cooler Electric driven (Single) phase having approx storage capacity of 120 ltr and nominal cooling capacity of 60 ltrs per hour including electric connection complete all as specified and as directed.
Supply and Installation of Desert cooler electric driven single phase 230 volts steel body having nominal air flow capacity of 4000 Cu M per hours with necessary inlet connection with HDPE/Flexible pipe both ends CP brass union for GI pipe complete including electric connection complete all as specified and as directed.
Supply & installation of voltage stabilizer of capacity 1 KVA for automatic operation, single phase naturally air cooled indoor type & Design for input voltage variation between 170V to 250 V with output voltage stabilizer at 230 V with accuracy of +/- 2.5% complete as specified and as directed.
Supply & installation of voltage stabilizer of capacity 2 KVA for automatic operation, single phase naturally air cooled indoor type & Design for input voltage variation between 170V to 250 V with output voltage stabilizer at 230 V with accuracy of +/- 2.5% complete as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “SOLAR WATER HEATER AND CENTRALISED HOT WATER SUPPLY WORK" as listed in Schedule ‘A’ Section - XIII (Part-I)
Sch 'A' Sec - XIII (Part-II), (SOLAR WATER HEATER AND CENTRALISED HOT WATER SUPPLY WORK)
Supply, install, testing and commissioning of Indirect transfer of heat type solar water heater system of capacity 100 ltrs per day including flat plate collector and other required accessories insulated stainless steel storage tank to be placed on building roof at a suitable height with aluminium cladding angle iron structrure cold water tank with inter connection between tank and solar panel and necessary structure & finishes work, foundation including electric back up of 2 KW and electric panel with MCBs and electric wiring upto solar panel and other safety devices such as thermostat, relays etc. complete all as specified. Note:-(i) The cost of supplying and laying of circulation pipe lines cold and hot, gun metal gate valves, non return valves, float valves and other accessories between solar panel and stainless steel hot water storage tank cold water tank and connection pipe lines from existing over head tank installed on roof of building is deemed to be included in the unit. The hot water pipe of suitable size of the solar water system will be insulated with rock wool fixed with chicken wire mesh including cladding with aluminum sheet and the cost of same shall also included in the unit rate. (ii) Cold water piping, hot water piping including its insulation beyond solar outlet supply from top to bottom (bathroom) or any other fixed point as directed and cold water tank shall be measured and paid separately.
Supply, install, testing and commissioning of Indirect transfer of heat type solar water heater system of capacity 200 ltrs per day including flat plate collector and other required accessories insulated stainless steel storage tank to be placed on building roof at a suitable height with aluminium cladding angle iron structrure cold water tank with inter connection between tank and solar panel and necessary structure & finishes work, foundation including electric back up of 3 KW and electric panel with MCBs and electric wiring upto solar panel and other safety devices such as thermostat, relays etc. complete all as specified. Note:-(i) The cost of supplying and laying of circulation pipe lines cold and hot, gun metal gate valves, non return valves, float valves and other accessories between solar panel and stainless steel hot water storage tank cold water tank and connection pipe lines from existing over head tank installed on roof of building is deemed to be included in the unit. The hot water pipe of suitable size of the solar water system will be insulated with rock wool fixed with chicken wire mesh including cladding with aluminum sheet and the cost of same shall also included in the unit rate. (ii) Cold water piping, hot water piping including its insulation beyond solar outlet supply from top to bottom (bathroom) or any other fixed point as directed and cold water tank shall be measured and paid separately.
Supply, install, testing and commissioning of Indirect transfer of heat type solar water heater system of capacity 300 ltrs per day including flat plate collector and other required accessories insulated stainless steel storage tank to be placed on building roof at a suitable height with aluminium cladding angle iron structrure cold water tank with inter connection between tank and solar panel and necessary structure & finishes work, foundation including electric back up of 3 KW and electric panel with MCBs and electric wiring upto solar panel and other safety devices such as thermostat, relays etc. complete all as specified. Note:-(i) The cost of supplying and laying of circulation pipe lines cold and hot, gun metal gate valves, non return valves, float valves and other accessories between solar panel and stainless steel hot water storage tank cold water tank and connection pipe lines from existing over head tank installed on roof of building is deemed to be included in the unit. The hot water pipe of suitable size of the solar water system will be insulated with rock wool fixed with chicken wire mesh including cladding with aluminum sheet and the cost of same shall also included in the unit rate. (ii) Cold water piping, hot water piping including its insulation beyond solar outlet supply from top to bottom (bathroom) or any other fixed point as directed and cold water tank shall be measured and paid separately.
Subtotal
Lump sum price worked out by the tenderer for “LIGHTNING PROTECTION WORK" as listed in Schedule ‘A’ Section - XIV (Part-I)
Sch 'A' Sec - XIV (Part-II), (LIGHTNING PROTECTION WORK)
Supply, installation, testing and commissioning of maintenance free earth grid (grounding) of interconnected two earth electrode of size 85 mm dia x 3 mtr long each metal conductor of electrode shall be Copper bounded MS strip of 50x6 mm Copper bounding of MS rod/ strip should be Min 250 microns. Earth electrode of 85 mm, depth 3 mtr shall be placed augured bore hole and embadding of interconnected strip shall be cast in high purity electrically conductive granuler material having ultra low resistive value 0.001Ohm-m resulting in increase of the effective surface area of the earth grid to lower the earth resistance conductive earth enhancing material shall be mix with cement in the ratio 3:1 which should not leach chemicals into the adjacent soil or underground water channels and should be in pH neutral range. Earth enhancing material should permanently proted the encased metal components of the earthing system. All hardware like nuts, bolts and washers should be of stainless steel Electrode should withstand fault current upto 35 KA for 1 second, electrodes top terminal be sealed permanently packed with conductive concrete and test link of Cu bonded MS/Copper strip of size 50x6x200 mm shall be taken out to connect the equipment. Test certificate of NABL laboratory shall be submitted by the contractor, RCC pit cover including brazzing of all the joints upto the test point complete all as specified and directed. No pre cast electrodes to be used. Make:- Elancrete/ Vasconite/ Equivalent. Note :- (i) Test certificate of earthing certified NABL laboratory shall be submitted & verified by GE. (ii) Test reports should not be more than 5 years old. (iii) Test report for fault current ohms, compliance and resistivity value from NABL certified/ CPRI lab is must and it has to be verified by GE.
Subtotal
Sch 'A' Sec - XV, (EOT CRANE WORK)
Subtotal
Lump sum price worked out by the tenderer for “DG SET WORK" as listed in Schedule ‘A’ Section - XVI (Part-I)
Sch 'A' Sec - XVI (Part-II), (DG SET WORK)
Supplying, installing, commissioning and testing diesel Generating Set 180 KVA capacity including in built retrofitting emission control device as per latest IS mounted acoustic weather proof as per CPCB (central pollution control Board) norms and noise level shall not exceed 75 decible at distance of 1 Mtr and comprising of the following (Diesel Engine :- Diesel Engine developing not less than at NTP, 1500 RPM turbo charge water cooled engine inclusive of following standard accessories :-
(i) Radiator Cooling system (ii) Direct coupled (iii) Flywheel to flexible coupling/closed coupled (iv) fly wheel housing with starter gear ring & coupling (v) Fuel houses (vi) Air cleaner (vii) Fuel and lub oil filter (viii) By pass filter (ix) Coolant inhabit (x) Fuel pump PTR type / in line mono block fuel injection pump (xi) Water pump (xii) Oil pump (xiii) Electric starter 24 volts DC (xiv) Industrial silencer (xv) Control push pull (xvi) Lub oil cooler
Alternator :- Alternator suitable for continuous operation generating 180 KVA at 1500 RPM 415 volts at NTP 0.8 power factor 3 phase 50 Hz, self-excited & regulated with ball/roller bearings conforming to IS-4722.
Fuel tank as recommended by manufacturer with inlet and outlet connection and fuel level indicator
Base frame fabricated form MS channel of suitable size and machined to ensure perfect alignment.
02 Nos maintenance free. battery of 12 volts each of 180 AH lead acid type.
Supplying fixing, testing and commissioning of AMF of DG set and shall be complete with following : (i) MCCB 4P 320A 25KA with adjustable over load (70 to 100%) adjustable short circuit - 01 No (ii) Adequate No of MCB of suitable size and rating (iii) Copper bus bar of suitable rating. (iv) Current transformer of suitable rating. (v) 4P contactor 240V AC of suitable rating. (vi) Indicating lamps (RYB) (vii) Mushroom head push butten press to lock turn to release (viii) VAF meter (ix) DC Amp meter (x) 12 V DC automatic battery charger with built in trickle boost facility. (xi) 4 point alarm annuncitar with built in hooter teast accept and reset push button. (xii) Solid state single element earth fault relay with contact. (xiii) Aux relay, coil voltage 12 V DC Note :- (a) Cost of suitable size of platform as per recommendations of manufacturer shall be provided with in over all cost quoted. (b) Any item left out for successful operation of AMF panel is deemed to be included in overall cost quoted.
Supplying, installing, commissioning and testing diesel Generating Set 200 KVA capacity including in built retrofitting emission control device as per latest IS mounted acoustic weather proof as per CPCB (central pollution control Board) norms and noise level shall not exceed 75 decible at distance of 1 Mtr and comprising of the following (Diesel Engine :- Diesel Engine developing not less than at NTP, 1500 RPM turbo charge water cooled engine inclusive of following standard accessories :-
(i) Radiator Cooling system (ii) Direct coupled (iii) Flywheel to flexible coupling/closed coupled (iv) fly wheel housing with starter gear ring & coupling (v) Fuel houses (vi) Air cleaner (vii) Fuel and lub oil filter (viii) By pass filter (ix) Coolant inhabit (x) Fuel pump PTR type / in line mono block fuel injection pump (xi) Water pump (xii) Oil pump (xiii) Electric starter 24 volts DC (xiv) Industrial silencer (xv) Control push pull (xvi) Lub oil cooler
Alternator :- Alternator suitable for continuous operation generating 200 KVA at 1500 RPM 415 volts at NTP 0.8 power factor 3 phase 50 Hz, self-excited & regulated with ball/roller bearings conforming to IS-4722.
Fuel tank as recommended by manufacturer with inlet and outlet connection and fuel level indicator.
Base frame fabricated form MS channel of suitable size and machined to ensure perfect alignment.
Two Nos. Maintenance free battery of 12 volts each of 180 AH lead acid type.
Supplying fixing, testing and commissioning of AMF of DG set and shall be complete with following : (i) MCCB 4P 400A 25KA with adjustable over load (70 to 100%) adjustable short circuit - 01 No (ii) Adequate No of MCB of suitable size and rating (iii) Copper bus bar of suitable rating. (iv) Current transformer of suitable rating. (v) 4P contactor 240V AC of suitable rating. (vi) Indicating lamps (RYB) (vii) Mushroom head push butten press to lock turn to release (viii) VAF meter (ix) DC Amp meter (x) 12 V DC automatic battery charger with built in trickle boost facility. (xi) 4 point alarm annuncitar with built in hooter teast accept and reset push button. (xii) Solid state single element earth fault relay with contact. (xiii) Aux relay, coil voltage 12 V DC Note :- (a) Cost of suitable size of platform as per recommendations of manufacturer shall be provided with in over all cost quoted. (b) Any item left out for successful operation of AMF panel is deemed to be included in overall cost quoted.
Supplying, installing, commissioning and testing diesel Generating Set 125 KVA capacity including in built retrofitting emission control device as per latest IS mounted acoustic weather proof as per CPCB (central pollution control Board) norms and noise level shall not exceed 75 decible at distance of 1 Mtr and comprising of the following (Diesel Engine :- Diesel Engine developing not less than at NTP, 1500 RPM turbo charge water cooled engine inclusive of following standard accessories :-
(i) Radiator Cooling system (ii) Direct coupled (iii) Flywheel to flexible coupling/closed coupled (iv) fly wheel housing with starter gear ring & coupling (v) Fuel houses (vi) Air cleaner (vii) Fuel and lub oil filter (viii) By pass filter (ix) Coolant inhabit (x) Fuel pump PTR type / in line mono block fuel injection pump (xi) Water pump (xii) Oil pump (xiii) Electric starter 24 volts DC (xiv) Industrial silencer (xv) Control push pull (xvi) Lub oil cooler
Alternator :- Alternator suitable for continuous operation generating 125 KVA at 1500 RPM 415 volts at NTP 0.8 power factor 3 phase 50 Hz, self-excited & regulated with ball/roller bearings conforming to IS-4722.
Fuel tank as recommended by manufacturer with inlet and outlet connection and fuel level indicator.
Base frame fabricated form MS channel of suitable size and machined to ensure perfect alignment.
Two Nos. Maintenance free battery of 12 volts each of 180 AH lead acid type.
Supplying fixing, testing and commissioning of AMF of DG set and shall be complete with following : (i) Adequate No of MCB of suitable size and rating (ii) Copper bus bar of suitable rating. (iii) Current transformer of suitable rating. (iv) 4P contactor 240V AC of suitable rating. (v) Indicating lamps (RYB) (vi) Mushroom head push butten press to lock turn to release (vii) VAF meter (viii) DC Amp meter (ix) 12 V DC automatic battery charger with built in trickle boost facility. (x) 4 point alarm annuncitar with built in hooter teast accept and reset push button. (xi) Solid state single element earth fault relay with contact. (xii) Aux relay, coil voltage 12 V DC Note :- (a) Cost of suitable size of platform as per recommendations of manufacturer shall be provided with in over all cost quoted. (b) Any item left out for successful operation of AMF panel is deemed to be included in overall cost quoted.
Supplying, installing, commission and testing diesel Generating Set (01 No installed for security lights and 01 No installed at pump house) 25 KVA capacity including in built retrofitting emission control device as per latest IS mounted acoustic weather proof as per CPCB (central pollution control Board) norms and noise level shall not exceed 75 decible at distance of 1 Mtr and comprising of the following (Diesel Engine :- Diesel Engine developing not less than at NTP, 1500 RPM turbo charge water cooled engine inclusive of following standard accessories :-
(i) Radiator Cooling system (ii) Direct coupled (iii) Flywheel to flexible coupling/closed coupled (iv) fly wheel housing with starter gear ring & coupling (v) Fuel houses (vi) Air cleaner (vii) Fuel and lub oil filter (viii) By pass filter (ix) Coolant inhabit (x) Fuel pump PTR type / in line mono block fuel injection pump (xi) Water pump (xii) Oil pump (xiii) Electric starter 12 volts DC (xiv) Industrial silencer (xv) Control push pull (xvi) Lub oil cooler
Alternator :- Alternator suitable for continuous operation generating 25 KVA at 1500 RPM 415 volts at NTP 0.8 power factor 3 phase 50 Hz, self-excited & regulated with ball/roller bearings conforming to IS-4722.
Fuel tank as recommended by manufacturer with inlet and outlet connection and fuel level indicator.
Base frame fabricated form MS channel of suitable size and machined to ensure perfect alignment.
One No. Maintenance free battery of 12 volts each of 88 AH lead acid type.
Supplying fixing, testing and commissioning of AMF of DG set and shall be complete with following : (i) MCCB 4P 63A 16KA with adjustable over load (70 to 100%) adjustable short circuit - 01 No (ii) Adequate No of MCB of suitable size and rating (iii) Copper bus bar of suitable rating. (iv) Current transformer of suitable rating. (v) 4P contactor 240V AC of suitable rating. (vi) Indicating lamps (RYB) (vii) Mushroom head push butten press to lock turn to release (viii) VAF meter (ix) DC Amp meter (x) 12 V DC automatic battery charger with built in trickle boost facility. (xi) 4 point alarm annuncitar with built in hooter teast accept and reset push button. (xii) Solid state single element earth fault relay with contact. (xiii) Aux relay, coil voltage 12 V DC Note :- (a) Cost of suitable size of platform as per recommendations of manufacturer shall be provided with in over all cost quoted. (b) Any item left out for successful operation of AMF panel is deemed to be included in overall cost quoted.
Note for item No 146 to 149 :- (a) Initial filling of lubricating oil/coolant and fuel required for testing of DG set shall be provided by the contractor without any extra cost. (b) All arrangement for testing of DG set shall be made by contractor with in overall cost quoted. (c) Pre-commissioning test shall be carried out by rep of Accepting Officer. Test for DG Set shall be carried out for duration of 12 hrs.
Subtotal
Lump sum price worked out by the tenderer for “RUNWAY LIGHTING WORK" as listed in Schedule ‘A’ Section - XVII (Part-I)
Sch 'A' Sec - XVII (Part-II), (RUNWAY LIGHTING WORK)
Supply and fixing uni directional elevated type high intensity runway light fitting suitable for use with 200W 6.6A halogen lamp complete with all accessories including and lamps and lens, lens holder, lens clamping mechanism, pre focus lamp and holder, central column assembly breakable coupling, gasket two pin secondary lead, base plate with 6 nos stainless steel nuts/bolts spring and plain washers complete all as specified and as directed. (for approch lighting)
Supply and fixing omni directional with rheostat (to control intensity ) elevated type high intensity runway light fitting suitable for use with 200 W 6.6A halogen lamp complete with all accessories including and lamps and lens, lens holder, lens clamping mechanism, pre focus lamp and holder, central column assembly breakable coupling, gasket two pin secondary lead, base plate with 6 nos stainless steel nuts/bolts spring and plain washers complete all as specified and as directed. (For Runway lightening)
Supply and fixing elevated type 45 W medium intensity runway light halogen fitting complete with lamp, omni directional blue lens, lamp holder, lens holder, clamping mechanism, pre focus lamp holder, central assembly, breakable coupling, gaskets two pin secondary lead, base plate with 6 nos stainless steel nuts/bolts spring and plain washers complete all as specified and as directed. (For taxi way lightening)
Supply and fixing elevated type 45 W medium intensity runway light halogen fitting (white colour) complete with lamp, omni directional blue lens, lamp holder, lens holder, clamping mechanism, pre focus lamp holder, central assembly, breakable coupling, gaskets two pin secondary lead, base plate with 6 nos stainless steel nuts/bolts spring and plain washers complete all as specified and as directed. (For opron lightening)
Supply and Laying AFLS primary Cable of size 6 Sqmm XLPE insulated, Sheathed multi stranded copper conductor single core airport lighting cable ISI marked confirming to latest IS complete all as specified and as directed.
M&L for DWC (Double wall corrugated) as per IS-16025 in trench/tunnel for cable protection of size OD/ID 63/50mm, with necessary connecting material snapfit couplet etc complete all as specified and as directed.
Supply and fixing 5 KV grade plug and socket receptacle of type class B connector suitable for field attachment of 6 sqmm 5 KV cable complete all as specified and as directed.
Supply and fixing 5 KV Grade 50Hz, 200W, 6.6A/6.6A rating series type isolating transformers encapsulated by polyster resin finally moulded in neoprene type rubber with primary and secondary connection complete all as specified and as directed.
Supply and fixing 5KV grade 50Hz, 45W, 6.6A/6.6A rating series type isolating transformers encapsulated by polyster resin finally moulded in neoprene type rubber with primary and secondary connection complete all as specified and as directed.
Supply, install, testing and commissioning of all the equipment required to provide airfield lighting control and monitoring system (ALCMS), type 'L 890BB' to the requirements of FAA Advisory Circular No AC 150/5345-56B (current edition) and additional circuits/ mechanisms/ interfaces for power supply equipment, and Landing -H etc. to make them campatible with ALCMS, data & power cabling earthing etc, including all hardware and software, licenses & other items are required for successful operation of the system in line with the scope of work, details of equipmens, equipments specification, performance criteria etc. Two Volt Processor will be provided both running in parallel for redundancy in operation. (Does not include the cost of Communication cable between ATC & CCR Room) complete all as specified and as directed. Make :- Nasu Systems / Honey Well / ADB Safegate
Supply and laying of Cat 6 cable and suitable size of HDPE pipe for connection of ATC panel to CCR Room control panel, item included the lenth of the HDPE pipe according to the length of the Cat 6 cable of suitable size complete all as specified and as directed.
Supply of FAA compliant indoor type microprocessor based, air cooled constant current regulator of thyristor control electronic type suitable for use on 240/415 VAC, 50/60 Hz input AC supply with below mention power at 6.6Amps with 5 steps variation of current output suitable for local and remote control operation with 24/48 VDC control supply complete with output current indicated on multifunction digital display, Over current, Over voltage earth fault protection and earth fault leakage meter, positive back indication equipment relay contactor etc as required as per specification of capacity 7.5 KW complete all as specified and as directed. Make :- Nasu Systems / Honey Well / ADB Safegate
Supply of FAA compliant indoor type microprocessor based, air cooled constant current regulator of thyristor control electronic type suitable for use on 240/415 VAC, 50/60 Hz input AC supply with below mention power at 6.6Amps with 5 steps variation of current output suitable for local and remote control operation with 24/48 VDC control supply complete with output current indicated on multifunction digital display, Over current, Over voltage earth fault protection and earth fault leakage meter, positive back indication equipment relay contactor etc as required as per specification of capacity 20 KW complete all as specified and as directed. Make :- Nasu Systems / Honey Well / ADB Safegate
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) in door type dust proof, vermin proof made out of CRCA sheet 2 mm thick powder coated, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with copper bus bar capacity 500 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on pedestal frame of angle iron of size 40 x40 x5 mm and grouted in PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate), pedestal frame duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 4Pole, 315 Amps, 415 volts 25 KA, ICS = 100% Icu -01 Nos
MCCB 40 Amps, 4 Pole, 415 volts 16 KA, Ics = 100% Icu - 05 Nos, MCCB 16 Amps, 4 Pole, 415 volts 16 KA, Ics = 100% Icu - 06 Nos
Multifunction meter electronic with suitable CTs, showing Amp, Volt, PF, Hz and other parameter rating Amp up to 200 Amp and Volt up to 500V - 01 No
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
LED indicator lamp (R,Y,B)- 01 Set
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication. (iii) Outgoing controls as discribed are for guidance. Panel to design should be based on actual load requirements for which notheing extra shall be payable.
Supplying, installing, commission and testing diesel Generating Set (installed for CCR and runway lighting) 160 KVA capacity including in built retrofitting emission control device as per latest IS mounted acoustic weather proof as per CPCB (central pollution control Board) norms and noise level shall not exceed 75 decible at distance of 1 Mtr and comprising of the following (Diesel Engine :- Diesel Engine developing not less than at NTP, 1500 RPM turbo charge water cooled engine inclusive of following standard accessories :-
(i) Radiator Cooling system (ii) Direct coupled (iii) Flywheel to flexible coupling/closed coupled (iv) fly wheel housing with starter gear ring & coupling (v) Fuel houses (vi) Air cleaner (vii) Fuel and lub oil filter (viii) By pass filter (ix) Coolant inhabit (x) Fuel pump PTR type / in line mono block fuel injection pump (xi) Water pump (xii) Oil pump (xiii) Electric starter 24 volts DC (xiv) Industrial silencer (xv) Control push pull (xvi) Lub oil cooler
Alternator :- Alternator suitable for continuous operation generating 160 KVA at 1500 RPM 415 volts at NTP 0.8 power factor 3 phase 50 Hz, self-excited & regulated with ball/roller bearings conforming to IS-4722.
Fuel tank as recommended by manufacturer with inlet and outlet connection and fuel level indicator.
Base frame fabricated form MS channel of suitable size and machined to ensure perfect alignment.
Two Nos maintenance free battery of 12 volts each of 180 AH lead acid type.
Supplying fixing, testing and commissioning of AMF of DG set and shall be complete with following : (i) MCCB 4P 250A 25KA with adjustable over load (70 to 100%) adjustable short circuit - 01 No (ii) Adequate No of MCB of suitable size and rating (iii) Copper bus bar of suitable rating. (iv) Current transformer of suitable rating. (v) 4P contactor 240V AC of suitable rating. (vi) Indicating lamps (RYB) (vii) Mushroom head push butten press to lock turn to release (viii) VAF meter (ix) DC Amp meter (x) 12 V DC automatic battery charger with built in trickle boost facility. (xi) 4 point alarm annuncitar with built in hooter teast accept and reset push button. (xii) Solid state single element earth fault relay with contact. (xiii) Aux relay, coil voltage 12 V DC Note :- (a) Cost of suitable size of platform as per recommendations of manufacturer shall be provided with in over all cost quoted. (b) Any item left out for successful operation of AMF panel is deemed to be included in overall cost quoted.
Note :- (a) Initial filling of lubricating oil/coolant and fuel required for testing of DG set shall be provided by the contractor without any extra cost. (b) All arrangement for testing of DG set shall be made by contractor with in overall cost quoted. (c) Pre-commissioning test shall be carried out by rep of Accepting Officer. Test for DG Set shall be carried out for duration of 12 hrs.
Supply, installing, commissioning & testing Energy Efficient type (Level-II) transformer (For Runway Lighting) step down 11/0.433 KV as per IS 1180-2014 Level-2), copper wound outdoor type AC, 3ph, 4 wire 50 Hz filtered & Dehydrated transformer oil and standard fittings/accessories of capacity 160 KVA naturally cooled with external cooling tubes, core type delta connected on primary (HV side) and star connected on secondary (LV side) having taping range (plus/minus) 7.5% in steps of 2.5 % each with vector group Dyn -11 to be varied by a manually operated off load tap changing gear including first filling of oil, all fitting and accessories and mounting all as specified. The transformer shall have HT bushing on high voltage side and LT bushing and LT cable end box on low voltage side with neutral brought out side for earth connection and installed on PCC plat form as per manufacturer recommended and all as specified and directed with following fitting and accessories :- (i) Name, Rating & Diagram Plant. (ii) On Load Tap Changer (OLTC) (iii) Earthing Terminal (iv) Lifting Eye Bolts (v) Air Release Plug (vi) Window for Tap Number (vii) Oil Drain cum Filtering valve with plug (viii) Oil filling cum filtering valve with plug (ix) Conservator with oil filling hole with cap (x) Silica gel Breather (xi) Removable manual crank handle to operate OLTC (xii) Removable inspection opening with cover (xiii) Oil Surge Relay
Note :- (a) Transformer shall be Pre-Commisioned by SEI after installation. (b) Cost of all necessary T&P and measuring devices shall be provided by the contractor without any extra cost. (c) Drawing of transformer shall be approved by GE before placing the order. (d) Pre-dispatch inspection at factory premises shall be carried out by rep of Accepting Officer. Contractor shall intimate the planned date of inspection well in advance. All incidental expenditure for getting the inspection/testing in the factory premises shall be borne by the contractor including transportation and administration arrangement for the rep of accepting officer without any extra cost to the department. (e) PCC foundation as per manufacturer recommendation (one metre high from ground level) shall be provided by the contractor without any extra cost.
Note for air field lighting :- The work shall be carried out by a specialized firm dealing with field runway lighting. Any item left out for functioning of system deemed to be included in rates quoted by contractor. The contractor shall submit layout plan for airfield lighting for approval of GE/User.
Subtotal
Sch 'A' Sec - XVIII (AIR COMPRESSOR WORK)
Supply installing, testing and commissioning of Air Compressor along with intake filter, flywheel mounted on given 220 Ltr tank capacity Air tank fitted with pressure switch, pressure gauge, safety valve, non return valve, drain valve, delivery valve, v- belts, and belt guard with energy efficient electric motor and starter of capacity 5 HP with max operating pressure 171 PSI, 12 kg/cm2, 3 phase, 490 LPM, 17.3 CFM capacity complete all as specified and as directed. Note:- Suitable capacity of starter and PVC insulated copper cable of suitable size from starter to motor shall be provided without any extra cost.
Supply and Fixing Stainless steel nozzle for 15 mm bore pipe complete all as specified and as directed. Make: Unitech or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and stainless steel control valve of 15 mm bore complete all as specified and as directed. Make : Zoloto or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and Fix Stainless steel pipe (AISL 304) 20 mm bore schedule-10mm wall thickness 2.11 mm in floor or in trench complete with all fitting accessories i.e. bend, socket, reducer, tee etc as required at site complete as per site requirement as specified and directed. Make :- Roopam steel or Techno commercial equivalent in make mentioned in Appx 'B'
Subtotal
Lump sum price worked out by the tenderer for “EXTERNAL WATER SUPPLY WORK" as listed in Schedule ‘A’ Section - XIX (Part-I)
Sch 'A' Sec - XIX (Part-II), (EXTERNAL WATER SUPPLY WORK)
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-9 bore 250mm confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast suitable for rubber tyton joints complete all as specified and as directed. Note : Earth work, DI specials/ fittings and tyton joint shall be measured and paid separetly.
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-9 bore 200mm confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast suitable for rubber tyton joints complete all as specified and as directed. Note : Earth work, DI specials/ fittings and tyton joint shall be measured and paid separetly.
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-9 bore 150mm confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast suitable for rubber tyton joints complete all as specified and as directed. Note : Earth work, DI specials/ fittings and tyton joint shall be measured and paid separetly.
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-9 bore 100mm confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast suitable for rubber tyton joints complete all as specified and as directed. Note : Earth work, DI specials/ fittings and tyton joint shall be measured and paid separetly.
Supply and fixing cast iron sluice valve 250 mm dia with flanged ends class I PN 1.0 (heavy duty ISI marked) confirming to IS:14846-2000, drilled type, gun metal spindle non raising type, CI gate with brass ring, iron wheel handle, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing cast iron sluice valve 200 mm dia with flanged ends class I PN 1.0 (heavy duty ISI marked) confirming to IS:14846-2000, drilled type, gun metal spindle non raising type, CI gate with brass ring, iron wheel handle, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing cast iron sluice valve 150 mm dia with flanged ends class I PN 1.0 (heavy duty ISI marked) confirming to IS:14846-2000, drilled type, gun metal spindle non raising type, CI gate with brass ring, iron wheel handle, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing cast iron sluice valve 100 mm dia with flanged ends class I PN 1.0 (heavy duty ISI marked) confirming to IS:14846-2000, drilled type, gun metal spindle non raising type, CI gate with brass ring, iron wheel handle, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing cast iron sluice valve 80 mm dia with flanged ends class I PN 1.0 (heavy duty ISI marked) confirming to IS:14846-2000, drilled type, gun metal spindle non raising type, CI gate with brass ring, iron wheel handle, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing DI fitting upto 250 mm bore pipe line for reducing/bends (any type radius and angle) tapers any type, straight, bend, increasing decreasing or double socket extra Tee pieces single branch Y 'Junction' double branch cross collers cap etc complete all as specified and as directed. Note:- Make of DI fittings shall be same make as DI pipe or as per recommendation of DI pipe manufacturer.
Material and labour for Construction of brick masonary valve pit chamber size 120 X120 X120 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:3) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Material and labour for Construction of brick masonary valve pit chamber size 90 X90 X90 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:3) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Material and labour for Construction of brick masonary valve pit chamber size 45 X45 X60 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:3) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) in door type dust proof, vermin proof made out of CRCA sheet 2 mm thick powder coated, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminium bus bar capacity 150 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on pedestal frame of angle iron of size 40 x40 x5 mm and grouted in PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate), pedestal frame duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :- (for Pump House Bldg)
Supply and fix 4 Pole MCCB 100 Amp, 50 Hz, 415 V with rupturing capacity, Thermal megnatic relay adjustable type 25 KA. – 01 Nos (In coming)
Supply and fix 4 Pole MCCB 40 Amp, 50 Hz, 415 V with rupturing capacity, Thermal megnatic relay adjustable type 16 KA. – 02 Nos (Outgoing)
Supply and fix MCB 2 Pole, 10 Amp rating suitable for 230 Volts (Out going ). – 01 Nos
Supply and fixing star delta starter suitable for 20 HP & other motor protection single phasing preventor- 02 Nos
LED Indicated Lamp (R,Y,B) one Set-01
On load Change over switch o4 pole 100 Amps 415 volts with front operated handle-01 Nos
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of pump set centrifugal type mounted on common base foundation electric motor driven complete with all accessories and comprising of the following :-
Pump centrifugal horizontal mounting type horizontal split type, cast iron body, multistage with CI impellers and stainless steel shaft 1200LPM discharge at 35 mtr head, direct coupling with electric motor Make Kirloskar/Crompton Graves/Jyoti/Mather Platter.
Squirel cage inductionn motor TEFC type Energy IE-2, 3 Phase 415 volts 50hz, AC supply, 1450 rpm suitable for above pump set but not less than 20 HP mounted on common base foundation and motor directly coupled with above pump setr Make Kirloskar/NGEF/Siemes/Bharat Bijli.
Suction pipe line using 150mm class k9, DI Flanged pipe from suction of pumping set to sump well (suitable reqd length as per site) including all DI flanged fittings and making flanged joint with nut, bolt and washer etc complete.
Delivery line of pump set using 150mm dia flanged DI pipe class K9 from pump to delivery header (approx distance between pump to delivery head upto 3 RM) including DI flanged fittings and joint with nut, bolt, washer etc complete (Sluice valve & Reflex vale in delivery line measured and paid separetaly).
Electrical cable PVC insulated, 3 core 10 sqmm flexible copper cable drawn through and including 63mm dia PVC pipe (4 kg/cm2) from motor to starter panel for star delta connections separately complete with coppers lungs cable gland etc.
Bourden's type pressure gauge of suitable size on delivery of pump set.
Common base foundation for pump set made of ISMC 100 suitable for above pump set with PCC CM 1:2:4 using 20mm graded aggregate 20cm above GL and 30 Cm below GL including grounding of eye bolts nuts etc for pump set of adequate size as per OEM recommendation.
Note :- (a) Pcc foundation as per OEM recommendation shall be provided within overall cost quoted. (b) Testing of pumping set shall be carried out by rep of Accepting Officer. (c) All T&P required for testing of pumping set shall be provided by the contractor without any extra cost.
Supply and fixing foot valve of size 150mm dia confirming to IS suitable for 150mm bore pipe flanged end complete with jointing material such as rubber gasket, nuts, bolts, washer as required at site complete all as specified and as directed.
Supply, installation, testing and commissioning of gravity feed direct cylinder mounted type gaseous chlorinator of capacity upto 1000 gr/hr with vacuum regulator incl 100 Kg cylinder duly filed with chlorine gas, integrated safety valve filter, pressure guage flow meter i.e. mearing glass or rotometer ejector, non return valve, PE tubing, ammonia bottle and spanner etc, complete conforming to IS 10553 complete all as specified and as directed.
Supply and fixing 150mm dia Non Return Valve (NRV) P.N. 1.0 ISI marked confirming to IS 5312 (Part-I) swing type gun metal flap flanged type including jointing material such as nuts, bolts, washers and rubber sheet etc complete all as specified and as directed.
Supply and fixing rubber tyton push on gasket joints for spigot and socketed DI pipe 250mm dia complete all as specified and as directed.
Supply and fixing rubber tyton push on gasket joints for spigot and socketed DI pipe 200mm dia complete all as specified and as directed.
Supply and fixing rubber tyton push on gasket joints for spigot and socketed DI pipe 150mm dia complete all as specified and as directed.
Supply and fixing rubber tyton push on gasket joints for spigot and socketed DI pipe 100mm dia complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “EXTERNAL ELECTRIFICATION WORK" as listed in Schedule ‘A’ Section - XX (Part-I)
Sch 'A' Sec - XX (Part-II), (EXTERNAL ELECTRIFICATION WORK)
Sand cushioning, with dry and clean river sand (for under ground cable) 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified and as directed. Note:- (i) Punned thickness shall be considered for payment purpose (ii) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used. (iii) Qty '2611' cum for Sch 'A' Sec -XX (Part-II), (EXTERNAL ELECTRIFICATION WORK), Qty '11' cum for Sch 'A' Sec -XVI (Part-II), (DG SET WORK), Qty '50' cum for Sch 'A' Sec - XVII (Part-II), (RUNWAY LIGHTING WORK) and Qty '34' cum for Sch 'A' Sec - XXII (Part-II), (ARBORICULTURE WORK)
Supply, installing, commissioning & testing Energy Efficient type (Level-II) transformer (installed at Tech Area) step down 11/0.433 KV as per IS 1180-2014 Level-2), copper wound outdoor type AC, 3ph, 4 wire 50 Hz filtered & Dehydrated tranformer oil and standard fittings/acccesories of capacity 630 KVA naturally cooled with external cooling tubes, core type delta connected on primary (HV side) and star connected on secondary (LV side) having taping range ±7.5% in steps of 2.5 % each with vector group Dyn -11 to be varied by a manually operated off load tap changing gear including first filling of oil, all fitting and accessories and mounting all as specified. The transformer shall have HT bushing on high voltage side and LT bushing and LT cable end box on low voltage side with neutral brough out side for earth connection and installed on PCC plat form as per manufacturer recommendation and all as specified and directed with following fitting and accessories :- (i) Name, Rating & Diagram Plant. (ii) On Load Tap Changer (OLTC) (iii) Earthing Terminal (iv) Lifting Eye Bolts (v) Air Release Plug (vi) Window for Tap Number (vii) Oil Drain cum Filtering valve with plug (viii) Oil filling cum filtering valve with plug (ix) Conservator with oil filling hole with cap (x) Silicagel Breather (xi) Removable manual crank handle to operate OLTC (xii) Removable inspection opening with cover (xiii) Oil Surge Relay
Supply, installing, commissioning & testing Energy Efficient type (Level-II) transformer (installed at Domestic Area) step down 11/0.433 KV as per IS 1180-2014 Level-2), copper wound outdoor type AC, 3ph, 4 wire 50 Hz filtered & Dehydrated tranformer oil and standard fittings/acccesories of capacity 400 KVA naturally cooled with external cooling tubes, core type delta connected on primary (HV side) and star connected on secondary (LV side) having taping range ±7.5% in steps of 2.5 % each with vector group Dyn -11 to be varied by a manually operated off load tap changing gear including first filling of oil, all fitting and accessories and mounting all as specified. The transformer shall have HT bushing on high voltage side and LT bushing and LT cable end box on low voltage side with neutral brough out side for earth connection and installed on PCC plat form as per manufacturer recommendation and all as specified and directed with following fitting and accessories :- (i) Name, Rating & Diagram Plant. (ii) On Load Tap Changer (OLTC) (iii) Earthing Terminal (iv) Lifting Eye Bolts (v) Air Release Plug (vi) Window for Tap Number (vii) Oil Drain cum Filtering valve with plug (viii) Oil filling cum filtering valve with plug (ix) Conservator with oil filling hole with cap (x) Silicagel Breather (xi) Removable manual crank handle to operate OLTC (xii) Removable inspection opening with cover (xiii) Oil Surge Relay
Supply, installing, commissioning & testing Energy Efficient type (Level-II) transformer (installed at ATC Area) transformer step down 11/0.433 KV as per IS 1180-2014 Level-2), copper wound outdoor type AC, 3ph, 4 wire 50 Hz filtered & Dehydrated tranformer oil and standard fittings/acccesories of capacity 200 KVA naturally cooled with external cooling tubes, core type delta connected on primary (HV side) and star connected on secondary (LV side) having taping range ±7.5% in steps of 2.5 % each with vector group Dyn -11 to be varied by a manually operated off load tap changing gear including first filling of oil, all fitting and accessories and mounting all as specified. The transformer shall have HT bushing on high voltage side and LT bushing and LT cable end box on low voltage side with neutral brough out side for earth connection and installed on PCC plat form as per manufacturer recommendation and all as specified and directed with following fitting and accessories :- (i) Name, Rating & Diagram Plant. (ii) On Load Tap Changer (OLTC) (iii) Earthing Terminal (iv) Lifting Eye Bolts (v) Air Release Plug (vi) Window for Tap Number (vii) Oil Drain cum Filtering valve with plug (viii) Oil filling cum filtering valve with plug (ix) Conservator with oil filling hole with cap (x) Silicagel Breather (xi) Removable manual crank handle to operate OLTC (xii) Removable inspection opening with cover (xiii) Oil Surge Relay
Note for item No 207 to 209 above :- (a) Transformer shall be Pre-Commisioned by SEI after installation. (b) Cost of all necessary T&P and measuring devices shall be provided by the contractor without any extra cost. (c) Drawing of transformer shall be approved by GE before placing the order. (d) Pre-dispatch inspection at factory premises shall be carried out by rep of Accepting Officer. Contractor shall intimate the planned date of inspection well in advance. All incidental expenditure for getting the inspection/testing in the factory premises shall be borne by the contractor including transportation and administration arrangement for the rep of accepting officer without any extra cost to the department. (e) PCC foundation as per manufacturer recommendation (one metre high from ground level) shall be provided by the contractor without any extra cost.
Supply and fixing energy efficient LED street light fitting of 45W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street/Roadway luminaire, with driver, including electric connection with suitable size of wire from junction box to street light fitting, fixing the light fitting with and including bracket made out of GI tubing light grade 32mm dia, 1.2 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron of size 25x4 mm with suitable nuts and bolts for fixing of bracket including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) CRI : Morethan 70 and CCT : 5700 K. (g) IP rating : IP65. (h) IK rating : Minimum IK07 (j) Built in potted LED Driver of the make as of the luminaire. (k) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (l) Surge protection 10 kV (inbuilt + extended) (m) Lens - High Efficiency wide angle lens. (n) BIS Approved fixtures and driver (o) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing energy efficient LED flood light fitting of 70W pressure die cast aluminum housing/body, heat resistant clear toughened glass, better optics for uniform distribution street/Roadway luminaries, with driver, including electric connection, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (for Dispersal Area) :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) CRI : Morethan 70 and CCT : 5700 K. (g) IP rating : IP65. (h) IK rating : Minimum IK07 (j) Built in potted LED Driver of the make as of the luminaire. (k) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (l) Surge protection 10 kV (inbuilt + extended) (m) Lens - High Efficiency wide angle lens. (n) BIS Approved fixtures and driver (o) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing LED Post Top light fitting of 25W decorative design, Glare-free and better uniformity compete fitting all with accessories and LED lamp, fixing on and including 50mm dia GI pipe light grade of length 2.5 mtr embeded in PCC block of size 0.3x0.3x0.5m made with PCC (1:2:4) type B-2 using 20 mm graded crushed stone aggregate, including making electric connection with suitable size of wire, complete fitting with all accessories and following specifications complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficiency of luminaire should be minimum 100 lumen per watt. (b) Input voltage range : 140 to 270 volts. (c) Temp operating range : Minus 10*C to plus 50*C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) CRI : More than 70 and CCT : 5700K (g) IP rating : IP 65 (h) IK rating : minimum IK 07 (j) Built in potted LED Driver of the make as of the luminaire. (k) LED driver should e complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (l) Surge protection 10kV (inbuilt +extended) (m) Lens - High Efficiency wide angle lens. (n) BIS approved fixtures and driver (o) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing Junction box of size 200x160x98mm/200x140X95mm or any other higher size (pole mounting) and should be insulated and made out of polycarbonate with glass fiber re-inforced material having IP65 protection in accordance with IEC 60529, fixing with and including clamp made out of SS grade 304 Flat iron size 25x3 mm including suitable size of nuts, bolts and washers also of SS grade 304 complete comprising of the following and as directed:- Note :- (a) Junction Box must meet the provision laid down in IEC 60998-1, IEC-60670-22, IEC-60670-22, IEC 60670-2 to 5 and color according to RAL 9011. (b) The manufacturer of junction box shall submit a copy of IEC certificate. (c) Junction box shall be fire retardant and self extiguishing in accordance with IEC60695-2 to 11, DIN VDE 0304 Part-3, UL94 V-2 flammability standard. It should be tested at Glove Wire test for 960°C. (d) The degree of protection of enclosure against mechanical load shall be in accordance with EN 50298 for IK08. (e) Internally embedded gasket of polyurethane/ Extruded silicon gasket. (f) Junction box shall 4 pole complete with single pole MCB 'C' curve of 6 Amp, rating.
Supply and fixing time switch astro type having longitude and latitude of phase of 32A rating with contracted fitted inside steel enclosure complete all as specified and as directed.
Earthing complete with galvanised steel earth plate electrode 60 cm × 60 cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with cap edge of the plate at a depth not less'than 1.5 metres below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides connected to galvanised iron strip 32 mm x 6 mm with including bolts, nuts, check nuts and washers of galvanised iron or steel and riveted to earth plate and one end and connecting to main switch board or metallic bodies of HT/LT equipments etc at the other ends 40 mm dia GI Pipe light grade with all fittings from electrode to body of equipment fixed with and including flat iron clamps, bolts, nuts and washers and also including providing watering pipe 20 mm dia GI light grade and including funnel, wire mesh, lugs etc from bottom of earth pit to top of electrode complete with earth pit in PCC 1:3:6 type C-2 using 40 mm grade crushed stone aggregate including CI cover and frame, frame embeded in concrete, complete all as specified and shown in electrical plate No. 3 of SSR part-I connecting electrode to test point with and including earthing lead including necessary excavation and earth work in any type of soil, returning fitting in approved soil and disposal of surplus soil to a distance not exc 50 m material and labour and testing on completion complete as specified and directed by Engr-in-charge. Note:- (i) The rate quoted shall be deemed to include for all the above provision inclusive earth lead upto 7.5 mtr length. (ii) PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge. (iv) Qty 86 Nos for Sch 'A' Sec - XX (Part-II) (EXTERNAL ELECTRIFICATION WORK), Qty 2 Nos for Sch 'A' Sec - XIV (Part-II) (LIGHTNING PROTECTION WORK), Qty 16 Nos for Sch 'A' Sec - XVI (Part-II) (DG SET WORK), Qty 12 Nos for Sch 'A' Sec - XVII (Part-II) (RUNWAY LIGHTING WORK) and Qty 10 Nos for Sch 'A' Sec - XIX (Part-II) (EXTERNAL WATER SUPPLY WORK)
Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing wire of size 4 mm dia by means of GI bolts/nuts/washers and protected by 15 mm bore GI light grade pipe upto test point or upto main switch board / electric equipment / pole / lightning arrestor / HT/LT equipments / GODO switch etc, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, including CI cover and frame, frame embeded in concrete, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and as directed by Engineer-in-charge. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing wire upto test point or upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge. (iv) Qty 68 Nos for Sch 'A' Sec - XX (Part-II) (EXTERNAL ELECTRIFICATION WORK), Qty 22 Nos for Sch 'A' Sec - XVII (Part-II) (RUNWAY LIGHTING WORK), Qty 01 Nos for Sch 'A' Sec - XXI (AVIATION OBSTRUCTION LIGHT WORK) and Qty 26 Nos for Sec - II (Part-II), (INTERNAL ELECTRIFICATION WORKS)
Note for item No 220 to 221 above :- The equipment offered shall be complete in all respects. Any material and components not specifically stated in this specification but which is necessary for trouble free operation of the equipment and accessories specified in this specification, shall be deemed to be included. The equipment shall conform in all respects to high standards of engineering design and workmanship and shall be capable of performing in continuous operation.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 1000 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 630 Amp, 4 Pole 50 Hz, 415 V, 50KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCCB 200 Amp, 4 Pole 50 Hz, 415 V, 25KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCCB 40 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 02 Nos (Out going)
MCCB 25 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 04 Nos (Out going)
MCCB 320 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Outgoing)
Space for MCCB FP - 04 Nos (Catered in PH-II)
Space for MCB SPN - 06 Nos (Catered in PH-II)
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 400 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 250 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCCB 40 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCB 20 Amp, 4 Pole rating suitable for 415 Volts – 01 No (Out going )
Space for MCCB FP - 07 Nos (Catered in PH-II)
Space for MCB SPN - 01 No (Catered in PH-II)
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 500 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 320 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, with Thermal megnatic relay adjustable type – 01 No (incoming)
MCCB 125 Amp, 4 Pole 50 Hz, 415 V, 25KA with rupturing capacity, Thermal megnatic relay adjustable type – 02 Nos (Out going)
MCCB 25 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 02 Nos (Out going)
MCB 20 Amp, 4 Pole rating suitable for 415 Volts – 01 No (Out going )
Space for MCCB FP - 04 Nos (Catered in PH-II)
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 1600 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
ACB 4 pole 1000 Amp thermal magnetic setting, capacity 60 KA - 01No (incoming)
MCCB 500 Amp, 4 Pole 50 Hz, 415 V, 50KA with rupturing capacity, Thermal megnatic relay adjustable type – 02 Nos (Out going)
MCCB 25 Amp, 4 Pole 50 Hz, 415 V, 16 KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCCB 40 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 04 Nos (Out going)
MCB 16 Amp, 4 Pole rating suitable for 415 Volts – 03 Nos (Out going )
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 1600 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
ACB 4 pole 1000 Amp thermal magnetic setting, capacity 60 KA - 01No (incoming)
MCCB 200 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCCB 160 Amp, 4 Pole 50 Hz, 415 V, 25KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCB 16 Amp, 4 Pole rating suitable for 415 Volts – 01 No (Out going )
Space for MCCB FP - 08 Nos (Catered in PH-II)
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 800 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 500 Amp, 4 Pole 50 Hz, 415 V, 50KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCCB 320 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCCB 40 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 03 Nos (Out going)
MCCB 250 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 06 Nos (Out going)
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 300 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 200 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCCB 125 Amp, 4 Pole 50 Hz, 415 V, 25KA with rupturing capacity, Thermal megnatic relay adjustable type – 02 Nos (Out going)
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 800 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 500 Amp, 4 Pole 50 Hz, 415 V, 50KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCCB 320 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCCB 250 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 06 Nos (Out going)
MCB 25 Amp, 4 Pole rating suitable for 415 Volts – 02 Nos (Out going )
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 300 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 200 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCCB 160 Amp, 4 Pole 50 Hz, 415 V, 25KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCCB 125 Amp, 4 Pole 50 Hz, 415 V, 25KA with rupturing capacity, Thermal megnatic relay adjustable type – 02 Nos (Out going)
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) in door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 2 mm thick powder coated, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminium bus bar capacity 1000 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on pedestal frame of angle iron of size 40 x40 x5 mm and grouted in PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate), pedestal frame duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :- (for Pump House Bldg)
MCCB 630 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCCB 250 Amp, 4 Pole 50 Hz, 415 V, 25KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCCB 200 Amp, 4 Pole 50 Hz, 415 V, 25KA with rupturing capacity, Thermal megnatic relay adjustable type – 02 Nos (Out going)
MCB 20 Amp, 4 Pole rating suitable for 415 Volts – 01 No (Out going )
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 30 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 16 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCB 10 Amp, 4 Pole rating suitable for 415 Volts – 02 Nos (Out going )
MCB 10 Amp, 2 Pole rating suitable for 230 Volts – 03 Nos (Out going )
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 50 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 32 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCCB 16 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (Out going)
MCB 10 Amp, 4 Pole rating suitable for 415 Volts – 02 Nos (Out going )
MCB 10 Amp, 2 Pole rating suitable for 230 Volts – 05 Nos (Out going )
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 50 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 32 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
MCB 10 Amp, 4 Pole rating suitable for 415 Volts – 02 Nos (Out going )
MCB 10 Amp, 2 Pole rating suitable for 230 Volts – 09 Nos (Out going )
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) in door type dust proof, vermin proof made out of CRCA sheet 2 mm thick powder coated, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminium bus bar capacity 600 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on pedestal frame of angle iron of size 40 x40 x5 mm and grouted in PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate), pedestal frame duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :- (for Pump House Bldg)
MCCB 400 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
Panel Mounting Socket Angled insulated water tight capacity 63 Amps, No of poles 3P+N+E, Degree of protection IP 67 - 02 Nos Make Hensel cat Part No.569
Panel Mounting Socket Angled insulated watertight capacity 32 Amps, No of poles 3P+N+E, Degree of protection IP 67 - 03 Nos Make Hensel cat Part No.539
Panel Mounting Socket Angled insulated watertight capacity 32 Amps, No of poles 2P+E, Degree of protection IP 67 - 03 Nos Make Hensel cat Part No.539306
Panel Mounting Socket Angled insulated watertight capacity 16 Amps, No of poles 2P+E, Degree of protection IP 67 - 02 Nos Make Hensel cat Part No.519306
MCB 100 Amp, TP – 02 Nos
MCB 40 Amp, TP – 03 Nos
MCB 40 Amp, SPN – 03 Nos
MCB 25 Amp, SPN – 02 Nos
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT panel Board of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 300 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
MCCB 200 Amp, 4 Pole 50 Hz, 415 V, 36KA with rupturing capacity, Thermal megnatic relay adjustable type – 01 No (incoming)
Panel Mounting Socket Angled insulated water tight capacity 63 Amps, No of poles 3P+N+E, Degree of protection IP 67 - 01 No Make Hensel cat Part No.569
Panel Mounting Socket Angled insulated watertight capacity 32 Amps, No of poles 3P+N+E, Degree of protection IP 67 - 02 Nos Make Hensel cat Part No.539
Panel Mounting Socket Angled insulated watertight capacity 16 Amps, No of poles 3P+N+E, Degree of protection IP 67 - 02 Nos Make Hensel cat Part No.519
MCB 100 Amp, TP – 01 No
MCB 40 Amp, TP – 02 Nos
MCB 20 Amp, TP – 02 Nos
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply fixing installation and testing Air circulator wall mounted type 600 mm sweep, 1440RPM single phase with 03 Nos badles Power 180 Watt and air delivery (CMM) 16200 complete with all accessories including fixing the same on wall/prefabricated structure with nut bolts etc complete all as specified and as directed.
Subtotal
Sch 'A' Sec - XXI (AVIATION OBSTRUCTION LIGHT WORK)
Supply and fixing Aviation obstruction light fitting, twin type, IP 65 protection, comprising of aluminium alloy housing with polycarbonate enclosure and accessories complete with LEDs to be fixed on the top of building/Hangar with suitable fixing accessories as shown on approved drawing and complete all as specified and as directed by Engineer-in-charge.
Subtotal
Lump sum price worked out by the tenderer for “ARBORICULTURE WORK" as listed in Schedule ‘A’ Section - XXII (Part-I)
Sch 'A' Sec - XXII (Part-II), (ARBORICULTURE WORK)
ARBORICULTURE B/R WORK
Supply and planting of Hedge and Shrubbery (Mehandi, Tikkam & Shehjan and the like) as directed by Engineer-in-Charge including creation of Beds by excavating 60 cm deep and 60cm wide trenching the excavated base to a further depth of 30 cm refilling the excavated earth after breaking clods and mixing with sludge or manure in the ratio 8:1 (8 parts of stacked volume of earth after reduction of 20% with 1 parts of stacked volume of sludge or manure after reduction by 8%) flooding with water filling with earth if necessary, watering and finally fine dressing leveling etc including stacking and disposal of material declared unserviceable and surplus earth by spreading and leveling as directed within a lead of 50 m and lift up to 1.50 m complete all as specified and as directed.
Neem (Plant height 3 to 5ft)
Gulmohar (Plant height 3 to 5ft)
Tikoma (Plant height 1 to 2ft)
Chandini (Plant height 1 to 2ft)
Gudel (Plant height 1 to 2ft)
Material and labour for stone bowl made of marble (Kumari Stone) with three steps of approximate size 4 feet dia & 1 feet depth and height of piece 2 feet fixed in position as per standard trade pattern complete all as specified & as directed.
ARBORICULTURE MAINTENANCE
ARBORICULTURE E/M WORK
Filtration plant and connected items
Supply and fixing Hydrocyclone filter with 2 solid flange size of 75mm dia and capacity of 30 m³/hr for head control unit in drip irrigation system IS 14743:1999 with all connected accessories complete all as specified and as directed. Make :- Sourabh shaktiman
Supply and fix PP manifold of size 75mm for Filter Unit of Drip and Pop-up system complete all as specified and as directed.
Supply and fixing Ventury with Ferttigation Manifold assemble size of 63 mm for head control unit IS: 14483:1997 with all acessories complete all as specified and as directed. Brand-Saurabh Shaktiman
Supply and fixing Air release valve (plastic) size of 25 mm dia for head control unit in drip irrigation system complete all as specified and as directed.
Supply and fixing Pressure gauge (glycerine) cap of 0-7 kg/cm² size of 63mm dia for head control unit in dirip irrigation system complete all as specified and as directed.
Supply and fixing Screen filter (plastic) with 2 solid flange size of 75 mm dia and capacity of 30 m³/hr for head control unit in drip irrigation system IS : 12785:1994 complete all as specified and as directed. Brand - Saurabh Shaktiman
Supply and fixing PP control valve size of 75mm for controlling water in storage tank for drip irrigation system complete all as specified and as directed.
For Drip irrigation System and POP - UP
Supply and fixing HDPE pipe (4 kg/cm²) IS ; 4984:2016, size of 90 mm dia for main distribution line in drip irrigation system and including all connected accessories (ie Socket, Bend, Elbow, Tee, Reducer, connector, Solvent, clamps etc) complete all as specified and as directed. Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing HDPE pipe (4 kg/cm²) IS ; 4984:2016, size of 75 mm for Main line in Pop-up and Drip irrigation system including all connected accessories (ie Socket, Bend, Elbow, Tee, Reducer, connector, Solvent, clamps etc) complete all as specified and as directed. Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing PVC pipe (6 kg/cm²) IS ; 4985:2000 size of 63 mm dia for sub distribution line in dirip irrigation system and including all connected accessories (ie Socket, Bend, Elbow, Tee, Reducer, connector, Solvent, clamps etc) complete all as specified and as directed. Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing Plain lateral 2.5 kg/cm², class II size of 32 mm dia, for water distribution line in dirip irrigation system and including all connected accessories (ie Socket, Bend, Elbow, Tee, Reducer, connector, suitable size Grommat Joiner 16mm take off, End cap, etc) complete all as specified and as directed. (For Trees) Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing Plain lateral 2.5 kg/cm², class II size of 16mm dia,online for water distribution line in drip irrigation system including all connected accessories (ie Grommat, Lateral cock, End cap for connection in UPVC/Plain lateral pipe etc) complete all as specified and as directed. (For Trees) Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing Emitting pipe of dia 16 mm, discharge 2 LPH, dripper spacing 30 cm. 2,5 kg/cm², IS:13488, including all connected accessories (ie Socket, Bend, Elbow, Tee, connector, suitable size Grommat, Joiner etc. complete all as specified and as directed. (For Hedges) Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing PVC Control valve size of 63 mm dia for head control unit sub distribution line in dirip irrigation system and complete all as specified and as directed. Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing HDPE/PVC Control valve size of 90 mm dia for head control unit sub distribution line in dirip irrigation system and all connected accessories complete all as specified and as directed. Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing Flush valve size of 75x63 mm dia for sub distribution line in dirip irrigation system complete all as specified and as directed. Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing service saddle of 63x32 mm dia including MT and FT for water distribution line in dirip irrigation system complete all as specified and as directed. Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing push type male threaded adopter size of 32 mm dia for water distribution line in dirip irrigation system complete all as specified and as directed. (For Hedges) Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing PP control valve (Th. End) size of 32 mm dia for sub distribution line in dirip irrigation system complete all as specified and as directed. Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing Dripper cap 8 LPH for dirip irrigation system and connected accessories complete all as specified and as directed. Make :- Finolex/supreme/Prince/ kisan/Tirupati or Techno commercial equivalent in make mentioned in Appx 'B'
Supply and fixing Pop-Up Impact sprinkler of heavy duty Plastic, adjustable to full-circle or Part circle with diffuser screw for fine drop lets and throw control, inlet size 3/4", having radious of throw up to 12 mtrs at pressure 4 kg/cm² complete all as specified and as directed. Make Aquaturf.
Supply and fixing Swing joint full three way adjustability including neight for Pop-Up Impact Sprinkler, bush with connected accessories, durable polyethylene construction for 3/4" size complete all as specified and as directed. Make Aquaturf.
Supply and fixing PVC End cap size of 63 mm dia for water distribution line in Pop-Up irrigation system and including all accessories complete all as specified and as directed.
Supply and fixing Robust top cover with nonslippery grip Plastic heavy duty extended bottom keeps the valve box stable and firmly set in the soil with Green Top and black base Size 10" rectangular shape at Pop-up distribution line and including all connected accessories complete all as specified and as directed.
Supply, install, testing and commissioning of horizontal open well submersible pump electric driven motor 7.5HP, 5.60 KW capacity, with supply voltage 415V, 3 Phase, 50Hz suitable for operation with operating head 30-45 Mtr and having capacity to discharge water 825-450 LPM with suction and discharge flanged suction 65 X 50mm with suction and delivery water line including flat Submercible copper conductor cable of size 6 Sqmm 3 Core from panel to motor as per manufacturer instructions including all connected accessories complete all as specified and as directed. (For EP) Make : CG /Kirloskar/MBH Pumps/KSB/Mather or eaquivalent).
Supply, install, testing and commissioning of horizontal open well submersible pump electric driven motor 5HP, 3.70 KW capacity, with supply voltage 415V, 3 Phase, 50Hz suitable for operation with operating head 20-30 Mtr and having capacity to discharge water 730-475 LPM with suction and discharge flanged suction 65 X 50mm with suction and delivery water line including flat Submercible copper conductor cable of size 6 Sqmm 3 Core from panel to motor as per manufacturer instructions including all connected accessories complete all as specified and as directed. (For Drip water irrigation system) (Make : CG /Kirloskar/MBH Pumps/KSB/Mather or eaquivalent).
For Fountain of Dia 7.00 Mtr
Supply, install, testing and commissioning of horizontal open well submersible pump electric driven motor 7.5HP, 5.60 KW capacity, with supply voltage 415V, 3 Phase, 50Hz suitable for operation with operating head 20-30 Mtr and having capacity to discharge water 880-825 LPM with suction and discharge flanged suction 65 X 50mm with suction and delivery water line including flat Submercible copper conductor cable of size 6 Sqmm 3 Core from panel to motor as per manufacturer instructions including all connected accessories complete all as specified and as directed. (For Fountain Outer Ring Nozzles) Make : CG /Kirloskar/MBH Pumps/KSB/Mather or eaquivalent).
Supply, install, testing and commissioning of horizontal open well submersible pump electric driven motor 5HP, 3.70 KW capacity, with supply voltage 415V, 3 Phase, 50Hz suitable for operation with operating head 20-30 Mtr and having capacity to discharge water 730-475 LPM with suction and discharge flanged suction 65 X 50mm with suction and delivery water line including flat Submercible copper conductor cable of size 6 Sqmm 3 Core from panel to motor as per manufacturer instructions including all connected accessories complete all as specified and as directed. (For Fountain Inner Ring Nozzles) (Make : CG /Kirloskar/MBH Pumps/KSB/Mather or eaquivalent).
Supply and fixing Angular jet fountain nozzel of gun metal with crome plated size inner dia 10 mm outer dia 12 mm Make: Raj, Aroma, creative or eaquivalent complete all as specified and as directed.
Supply and fixing Air jet fountain nozzel of gun metal with crome plated size inner dia 10 mm outer dia 12 mm Make: Raj, Aroma, creative or equivalent complete all as specified and as directed.
Supply and fixing heavy duty class "B" GI Pipe and Fittings of Dia 50 mm Bore including valve, Cutting connection, fabrication with all connected accessories for making arrangement for supply of water from pump to nozzles (Inner and Outer ring of foundain) suitable for fountain of 7.00 mtr dia complete all as specified and as directed.
Supply and fixing LED base water proof programmable colour changing lights as per site requirement ABS, PVC Body, RGB Colour, operating voltage 18V DC colour programmable as per Model 108R, FM-5mm or eaquivalent complete all as specified and as directed.
Supply and fixing LED base water proof programmable Green Colour lights as per site requirement ABS, PVC Body, RGB Colour, operating voltage 18V DC colour programmable as per Model 108R, FM-5mm or eaquivalent complete all as specified and as directed.
Supply and fixing DMX controller for changing colour of light, micro processing controller with 18 V transformer as per site requirement having contrast show, medium fast or fading of colour mode complete all as specified and as directed. (One for Inner ring of fontain and one for Outer ring of Fountain) Make : Creative or equivalent.
Supply and Fixing mild steel clamps made of flat iron 40 X 6 mm in two halves for tapping through 80 to 150 mm bore GI / DI Water pipe line including drilling and welding of 15/20 mm GI socket and necessary rubber insertion, nuts,bolts and washers complete all as directed.
Material and labour for Cutting/dismantling of PCC Paver Block/hardstanding/road for laying of arboriculture water distribution pipe lines and disposl of removal matrieal to a distance exc 250m but not exc 500m and making good the same as per existing complete all as specified and as directed.
Supply and fixing Rotational moulded polyethylene (HDPE) water storage tank of 5000 Ltrs capacity (Cylindrical vertical tank with closed top) hoisted on roof/ lowered underground on PCC platform and fixed in position including making necessary arrangements for fixing inlet, outlet overflow pipe and provision of washout pipe, including provision of circular platform below the tank of height 30Cm and more than the external dia of tank casted into two layer of PCC with first layer of 15cm thickness of PCC (1:2:4) type B2 using 40mm graded aggregate and second top layer 15cm thickness in PCC (1:3:6) type C1 using 20mm graded aggregate with smooth finish to exposed concrete surfaces including necessary form work etc complete all as specified and as directed. Note :- (i) The water storage tank shall be tripple layer, HDPE tank moulded to seemless perfection of rotation moulding process.The tanks shall be manufactured only from FDA approved special grade poly ethelene and shall be certified fit for portable water including necessary foundation for placing the water tank complete all as specified and directed. (ii) HDPE storage tank shall be as per IS-12701. (iii) Necessary Earth work shall be measured and paid sepaerately. (Make :- Polycon/ Modi/Ganga/Sintex or eaquivalent).
Supply and laying Best quality, locally available, sub class ‘B’ bricks (Old Size) for cable protection cover, laid flat and dry in trenches over the cable , perpendicular to the direction of cable adjacent/abutting each other complete all as specified and as directed.
Material and labour for boring of holes under main road pavement, hard standing by trenchless technology using ultra sound technique and necessary machine for accommodate 50mm bore GI tube (light grade) in the drilled holes, including returning, filling in the end working space including removal of surplus soil and making good the surface complete all as specified and as directed. Note ; (GL pipe light grade shall be measured and paid separately)
Material and labour for Construction of brick masonary valve pit chamber size 75 X75 X75 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:4:8) type D-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:6), inner plaster 12 mm thick in cm (1:4) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3mm thick (double door type) mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Material and labour for Construction of brick masonary valve pit chamber size 100 X100 X100 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:4:8) type D-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:6), inner plaster 12 mm thick in cm (1:4) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3mm thick (double door type) mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Supply, installation, commissioning and testing of factory made cubical type LT feeder pillar box of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 100 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :- (For EP)
MCCB 40 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic fixed type – 01 No (incoming)
MCCB 25 Amp, 3 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic fixed type – 03 Nos (outgoing) (Two working and one spare)
Single phase preventer suitable for 7.5 HP submersible pump set - 02 Nos
DOL Motor starter in sheet steel enclosure, suitable for 7.5 HP electric Motor, 3 phase, 415 volt, 50 Hz – 02 Nos.
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT feeder pillar box of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 100 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :- (For Fountain).
MCCB 40 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic fixed type – 01 No (incoming)
MCCB 25 Amp, 3 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic fixed type – 02 Nos (outgoing) (One working and one spare) (For 7.5 HP Pump)
MCCB 16 Amp, 3 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic fixed type – 02 Nos (outgoing) (One working and one spare) (For 5 HP Pump)
Single phase preventer suitable for 5HP and 7.5 HP submersible pump set - 02 Nos (one each)
DOL Motor starter in sheet steel enclosure, suitable for 7.5 HP electric Motor, 3 phase, 415 volt, 50 Hz – 01 Nos.
DOL Motor starter in sheet steel enclosure, suitable for 5 HP electric Motor, 3 phase, 415 volt, 50 Hz – 01 Nos.
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Space for fixing of DMX Controller with 18V transformer for changing colour of lights microprocessing controller - 02 Nos.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installation, commissioning and testing of factory made cubical type LT feeder pillar box of Suitable size (CPRI approved) out door type dust proof, vermin proof with IP 65 protection made out of CRCA sheet 3.15 mm thick powder coated with seven tank process, fully compartmentalized inside panel with 2 mm thick CRCA sheet powder coated, to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front opening with double door with hinges including locking arrangements including provision of rubber beading and mild steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, complete with aluminum bus bar capacity 100 Amps 04 Nos Three Phase and neutral (TPN) (in Separate chamber), bus bar fixed on epoxy coated insulator and provision with 1100 volt grade heat shrinkable type sleeves and housed in independent chamber having access both from front and back side, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel board door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :- (For Drip Water irrigation system)
MCCB 25 Amp, 4 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic fixed type – 01 No (incoming)
MCCB 16 Amp, 3 Pole 50 Hz, 415 V, 16KA with rupturing capacity, Thermal megnatic fixed type – 03 Nos (outgoing) (Two working and one spare)
Single phase preventer suitable for 5HP submersible pump set - 02 Nos
DOL Motor starter in sheet steel enclosure, suitable for 5 HP electric Motor, 3 phase, 415 volt, 50 Hz – 02 Nos.
LED Indicated Lamp (R,Y,B) one Set-01
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Earthing complete with galvanised steel earth plate electrode 60 cm × 60 cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with cap edge of the plate at a depth not less'than 1.5 metres below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides connected to galvanised iron strip 25 mm x 4 mm with including bolts, nuts, check nuts and washers of galvanised iron or steel and riveted to earth plate and one end and connecting to main switch board or metallic bodies of equipments etc at the other ends 40 mm dia GI Pipe light grade with all fittings from electrode to body of equipment fixed with and including flat iron clamps, bolts, nuts and washers and also including providing watering pipe 20 mm dia GI light grade and including funnel, wire mesh, lugs etc from bottom of earth pit to top of electrode complete with earth pit in PCC 1:3:6 type C-2 using 40 mm grade crushed stone aggregate including CI cover and frame, frame embeded in concrete, complete all as specified and shown in electrical plate No. 3 of SSR part-I connecting electrode to test point with and including earthing lead including necessary excavation and earth work in any type of soil, returning fitting in approved soil and disposal of surplus soil to a distance not exc 50 m material and labour and testing on completion complete all as specified and as directed. Note:- (i) The rate quoted shall be deemed to include for all the above provision inclusive earth lead upto 7.5 mtr length. (ii) PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
Subtotal
Lump sum price worked out by the tenderer for “EXCAVATION, EARTHWORK AND SITE DEVELOPMENT WORK" as listed in Schedule ‘A’ Section - XXIII
ENGINEER CONSTRUCTION PVT. LTD.
NSC Projects Pvt. Ltd.
Som Projects Pvt. Ltd.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid