Tender Value
Refer Docs
EMD Value
₹32,000
Closing Date
28 Sept 2020, 6:00 pmClosed
CWE MAMUN
HQ CWE MAMUN PATHANKOT 145001
PROVISION OF DG SETS UNDER GE NORTH MAMUN
2020_MES_373809_1
CWE/M-41/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE NORTH MAMUN
Class D Category b I
5 documents required · 5 mandatory
₹500
GE NORTH MAMUN
₹32,000
Yes
23 Oct 2020
1 Sept 2020
29 Sept 2020
1 Sept 2020
28 Sept 2020
16 Sept 2020
Amount
Supply, install, commissioning & testing of diesel engine driven generating set complete with acoustic enclosure approved by CPCB-II and control system for 15 KVA output at site, AC 415 volts, 50 C/S, 3 phase 4 wire directly coupled complete with self starting system including accessories, equipment control panel etc as detailed below complete all as specified & directed consisting of following ;- (A) Diesel engine :- Diesel driven engine of suitable capacity to drive alternator of cap 15 KVA, water cooled and electric start, coupled directly through flexible coupling, multi cylinder, four storke, 1500 RPM, industrial type as per ISO-1546-1 / BS5514 of DG set complete with following standard accessories as per manufacturer recommendations or all as specified and directed. (a) The gen set should have capacity to run continuously in variable load condition for unlimited hours and should also have a 110% load capacity of 01 hour in every 12 hours of operation. (b) Air System - Inlet & Exhaust comprising (i) Dry-type paper element air Cleaner (ii) Restriction Indicator / Vacuum Indicator (iii) Optimised Turbocharger (iv) Intake Manifold (v) Exhaust Manifold (vi) Silencer muffler (vii) Stainless steel Exhaust Flexible coupling (c) Cooling System comprising (i) Radiator to suit ambient conditions (ii) Cooling system piping (iii) Thermostates (iv) Pressure cap (v) Coolant Inhibitor (vi) Engine Driven Fan (d) Fuel System comprising (i) Fuel pump -Low pressure type (ii) Injectors (iii) Cartridge paper filters primary and secondary for Fuel (e) Governor :- Engine Electronic Governor for A1 governing of engine speed from No load to full load. (f) Lub Oil System :- (i) Plate Type lub oil cooler (ii) filters-lubrication oil (g) Fuel Tank :- Draw out type integral fuel tank of suitable capacity or as recommended by manufacturer with level indicator in ltrs, provided with drain plug and air vent / breather and inlet and outlet connection (h) Electric Starting system comprising (i) Electrical starter - 12 Volts (ii) Engine driven battery charging alternator (iii) Cut Out and (iv) One No of 12 volts of 88 AH or recommanded by manufacturer maintenance free battery with suitable connection terminals and leads for proper battery connection
(j) Engine Monitoring, Protection and Diagnostics relay suitable to display (i) Lub oil Pressure (ii) Coolant Temperature (iii) Engine Speed (iv) Hours Run (v) Battery Voltage, Battery charging voltage (vi) Fuel level in percentage, (vii) AC Voltage 3 phase (viii) Current RYB 3 phase (ix) Power Factor (x) Frequency (xi) KVA (xii) Kilowatt and suitable for (i) Start and Stop (ii) Common Shutdown (iii) High coolant temp warning and shutdown (iv) Low tube oil pressure warning and shutdown (v) Low fuel level shutdown (vi) Overspeed shutdown (vii) Alternator Protection including Over voltage, Under voltage, Over and under frequency and Over current lub (k) Misc Accessories i.e - (i) Flywheel Housing (ii) Flywheel (iii) Anti-vibration pads (iv) Emergency stop push button etc complete all as required for smooth operation of DG set or recommended by manufacturer. (B) ALTERNATOR :- Self excited, self regulated screen protected drip proof type with Class 'H' Insulation Salient pole revolving field and electronic Automatic Voltage Regulator for voltage regulation of + 0.5% from No load to full load, standard enclosure 415 Volt 50 HZ 4 pole 15 KVA cap complete as per IS-13364-2 and conf to IS-4722 or BS 2613-1970 complete all as required or recommended by manufacturer.
Supply, install, commissioning & testing of diesel engine driven generating set complete with acoustic enclosure approved by CPCB-II and control system for 30 KVA output at site, AC 415 volts, 50 C/S, 3 phase 4 wire directly coupled complete with self starting system including accessories, equipment control panel etc as detailed below complete all as specified & directed consisting of following ;- (A) Diesel engine :- Diesel driven engine of suitable capacity to drive alternator of cap 30 KVA, water cooled and electric start, coupled directly through flexible coupling, multi cylinder, four storke, 1500 RPM, industrial type as per ISO-1546-1 / BS5514 of DG set complete with following standard accessories as per manufacturer recommendations or all as specified and directed. (a) The gen set should have capacity to run continuously in variable load condition for unlimited hours and should also have a 110% load capacity of 01 hour in every 12 hours of operation. (b) Air System - Inlet & Exhaust comprising (i) Dry-type paper element air Cleaner (ii) Restriction Indicator / Vacuum Indicator (iii) Optimised Turbocharger (iv) Intake Manifold (v) Exhaust Manifold (vi) Silencer muffler (vii) Stainless steel Exhaust Flexible coupling (c) Cooling System comprising (i) Radiator to suit ambient conditions (ii) Cooling system piping (iii) Thermostates (iv) Pressure cap (v) Coolant Inhibitor (vi) Engine Driven Fan (d) Fuel System comprising (i) Fuel pump -Low pressure type (ii) Injectors (iii) Cartridge paper filters primary and secondary for Fuel (e) Governor :- Engine Electronic Governor for A1 governing of engine speed from No load to full load. (f) Lub Oil System :- (i) Plate Type lub oil cooler (ii) filters-lubrication oil (g) Fuel Tank :- Draw out type integral fuel tank of suitable capacity or as recommended by manufacturer with level indicator in ltrs, provided with drain plug and air vent / breather and inlet and outlet connection (h) Electric Starting system comprising (i) Electrical starter - 12 Volts (ii) Engine driven battery charging alternator (iii) Cut Out and (iv) One No of 12 volts of 88 AH or recommanded by manufacturer maintenance free battery with suitable connection terminals and leads for proper battery connection
(j) Engine Monitoring, Protection and Diagnostics relay suitable to display (i) Lub oil Pressure (ii) Coolant Temperature (iii) Engine Speed (iv) Hours Run (v) Battery Voltage, Battery charging voltage (vi) Fuel level in percentage, (vii) AC Voltage 3 phase (viii) Current RYB 3 phase (ix) Power Factor (x) Frequency (xi) KVA (xii) Kilowatt and suitable for (i) Start and Stop (ii) Common Shutdown (iii) High coolant temp warning and shutdown (iv) Low tube oil pressure warning and shutdown (v) Low fuel level shutdown (vi) Overspeed shutdown (vii) Alternator Protection including Over voltage, Under voltage, Over and under frequency and Over current lub (k) Misc Accessories i.e - (i) Flywheel Housing (ii) Flywheel (iii) Anti-vibration pads (iv) Emergency stop push button etc complete all as required for smooth operation of DG set or recommended by manufacturer. (B) ALTERNATOR :- Self excited, self regulated screen protected drip proof type with Class 'H' Insulation Salient pole revolving field and electronic Automatic Voltage Regulator for voltage regulation of + 0.5% from No load to full load, standard enclosure 415 Volt 50 HZ 4 pole 30 KVA cap complete as per IS-13364-2 and conf to IS-4722 or BS 2613-1970 complete all as required or recommended by manufacturer.
Supply, installation, commissioning and testing of LT panel outdoor type of size recommended by manufacturer cubical floor mounted type (IP-65 degree of protection ) made out of 3.15 mm thick MS sheet (internally and externally) powder coated, bus bar 300 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply ,hibling , cable entry boxes , cable gland incl 50x50x6 mm frame (bottom portion of the panel) , grouted foundation in PCC 1:2:4 type B1 with 20 mm graded stone aggregates totally tested as per IEC 61439-I , suitable for and including the following :- (i) MCCB 4 pole 415 volts 250 amp rating thermal based release with rupturing capacity 36 KA - 01 No as incomer, Make- Legrand DRX type Cat No 669187 or equivalent Model in Siemens /Schneider /ABB/L&T. (ii) MCCB 4 pole 415 volts 160 amp rating thermal based release with rupturing capacity 36 KA - 02 No for outgoing, Make- Legrand DRX type Cat No 669187 or equivalent Model in Siemens /Schneider /ABB/L&T. (iii) MCCB 3 pole 415 volts with thermal based release rupturing cap 25 KA, 100 amps - 02 Nos for outgoing , Make- Legrand DPX3 type Cat No 420043 or equivalent Model in Siemens /Schneider /ABB/L&T. (iv) Indicator set RYB -01 Set of 3 pcs only Make- L & T/AE/C&S (v) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio Make- Schneider / L & T / Legrand. (vi) MCB ,SP 10 amps -03 Nos Make- Legrand /Hager /Havells/L&T (vii) On load change over switch 160 Amps, 4 Pole, AC 415 V Manual change over open execution - 01 No. Make- C&S /Havells/L&T (viii) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed.
M&L for Earthing complete with galvanised steel earth plate electrode 600mmx600mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised earth GI strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electric plate No 3 connected to earth test point/MCB DBs all as specified and indicated compete with funnel, charcoal, dust, salt etc and GI protection pipe, medium grade 40mm bore and GI watering pipe 20mm bore light grade, 40mm thick precast RCC M-15 (nomial mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x4mm frame for cover, PCC M-15 (Nominal mix) pit, excavation and earth work in any type of soil and connected including test point, complete, all as specified & directed. Notes: 1. Earth lead & protection pipes length upto & including 7.50 metre is deemed included in the unit rate quoted by the contractor. 2. Earth filling shall be done by vegitable soil. 3. Soil should be free from stone, boulders, aggregate, gravels etc.
Supply , laying, testing and commissioning for 1100 volt grade XLPE insulated heavy duty cable, 50 sqmm 3.5 core, strip armoured with aluminium stranded conductor overall PVC sheathed laid in trenches /pole/ along wall complete all as specified and directed. Note : Excavation & Earthwork shall be measured and paid separately.
Supply , laying, testing and commissioning for 1100 volt grade XLPE insulated heavy duty cable, 16 sqmm 4 core, strip armoured with aluminium stranded conductor overall PVC sheathed laid in trenches /pole/ along wall complete all as specified and directed. Note : Excavation & Earthwork shall be measured and paid separately.
M & L for sand filling in trenches dry and and clean sand unwashed including punning around cable for protection of under ground cable complete all as specified and directed. [Note : Punned thickness shall be measured and paid]
M & L for well burnt bricks , laid flat ( old size) sub class B designation 75 for cable protection complete all as specifed and directed.
Excavation in trenches n exc 1.5m wide and n exc 1.5m in depth for foundation etc (for cable, pole stay manhole etc), in any type of soil and getting out, complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc. 25cm thick, etc complete all as specified and directed.
Removing excavation material n exc. 50m & deposited where directed at a level n exc. 1.5m above the starting point etc complete all as specified and directed.
AV ENTERPRISES
Vijay Kumar Contractor and Engineers
dinesh enterprises
KULBHUSHAN AGGARWAL
MORESHWAR ELECTRICALS CORPORATION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .