| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹27.3 LAccepted-Finance E3 172 ARERA COLONY NEAR 10 NO MARKET ARERA COLONY BHOPAL MADHYA PRADESH 462016 | BHOPAL | MADHYA PRADESH | 462016 | ₹27.3 L | L-1 | Accepted-Finance Lowest-1 |
| 2 | L2₹29.2 L+₹1.9 L (7.14%)Rejected-Finance 221 BISARIYA COMPLEX ZONE II M P NAGAR BHOPAL MADHYA PRADESH 462011 | BHOPAL | MADHYA PRADESH | 462011 | ₹29.2 L+₹1.9 L (7.14%) | L2 | Rejected-Finance Lowest-2 |
| 3 | Rejected-Technical 4 AND 5 DDA MARKET 4 AND 5 DDA SHOPPING COMPLEX SOUTH EXTENSION PART 1 SOUTH EXTENSION PART I | - | - | Rejected-Technical Submitted Documents are not as per NIT |
| 4 | Rejected-Technical | - | - | Rejected-Technical Submitted Documents are not as per NIT |
| 5 | Rejected-Technical | - | - | Rejected-Technical Submitted Documents are not as per NIT |
Tender Value
₹33.0 L
EMD Value
₹65,930
Closing Date
2 Jun 2022, 5:00 pmClosed
SM (E-E)
O/o Airport Director, AAI, R.B. Airport, Bhopal
Construction of Domestic Air Cargo Terminal Building and associated works at Raja Bhoj Airport, Bhopal. SH- Electrical Works - AC and Cold Storage
2022_AAI_114860_1
AAI/BPL/ENGG(E)/NIT-04/2022-23
Open Tender
Electrical Works
Works
180 days
R.B. Airport
Please refer Tender documents.
18 documents required · 18 mandatory
₹1,120
₹65,930
10 Jun 2022
5 May 2022
3 Jun 2022
5 May 2022
2 Jun 2022
13 May 2022
5 May 2022 - 12 May 2022
Amount
Design, Supply, Installation, testing and commissioning of Capacity : 15000 BTU/ Hrs X 2 Nos (01 Working + 01 standby) Refrigeration system for maintaining temperature in cold room with cooling system working on CFC free refrigerant complete in all respect for cold room of size 8.20 feet X 16.70 feet X 10 feet (H) for pharma products including Evaporative unit with matching condensing unit, Blower, Coil, Expansion valve, condensor, copressor, motor, refrigerant piping (upto 7 mtr length included)/drain piping, insulation of cold room's wall, ceiling, door with 60 mm prefab CFC free PUF panel inside PPGI & Out side PPGI and floor with 60/50 mm CFC free PUF pannels PP/GI with anti skid floor and heavy duty hinges and handles with inside & out side PPGI finish with provision for locking the door from out side with all accesseries like kick plate, light switch, Digital temperature indicator, Door Closures safety release knob, controller, safety alarm etc to achieve the required temperature of +2 to +8 degree centigrade in cold rooms with automated data logger suitable for PC Connectivity (Without PC). FLOOR - P P OUTER 6 MM MARINE PLY - 1.2 MM Aluminium. checkered plate, as per specifications i/c copper piping, cabling and starter Installation, testing and commissioning refrigeration units as required.
Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with Ecofriendly Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. 40 HP ODU
Supply, installation, testing and commissioning of following minimum capacity 4- way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (INDOOR UNIT-CASSETTE TYPE) 3.2 TR
Supply, installation, testing and commissioning of following minimum capacity 4- way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (INDOOR UNIT-CASSETTE TYPE) 2.4 TR
Supply, installation, testing and commissioning of following minimum capacity 4- way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (INDOOR UNIT-CASSETTE TYPE) 2 TR
Supply, installation, testing and commissioning of following minimum capacity 4- way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (INDOOR UNIT-CASSETTE TYPE) 1.6 TR
Supply, installation, testing and commissioning of following minimum capacity 4- way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (INDOOR UNIT-CASSETTE TYPE) 1.2 TR
Supply, installation, testing and commissioning of following minimum capacity VRV / VRF Highwall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan / dynamically balanced blower, multi speed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cordless remote control, drainpan, necessary accessories etc., suitable for operation on 230V ± 10 %, 50Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (HIGH WALL TYPE) 1.45 TR
Supply, installation, testing and commissioning of following minimum capacity VRV / VRF Highwall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan / dynamically balanced blower, multi speed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cordless remote control, drainpan, necessary accessories etc., suitable for operation on 230V ± 10 %, 50Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (HIGH WALL TYPE) 1.3 TR
Supply, installation, testing and commissioning of following minimum capacity VRV / VRF Highwall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan / dynamically balanced blower, multi speed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cordless remote control, drainpan, necessary accessories etc., suitable for operation on 230V ± 10 %, 50Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (HIGH WALL TYPE) 1 TR
SITC of Seamless heavy gauge Copper refrigerant piping of adequate size duly insulated with nitrile insulation of adequate thickness. Refrigeration piping will have to be taken in the piping rack / Cable tray Support individually connecting to all indoor units for the respective floors. Even necessary supports, fittings, valves & ref. joints where ever required will be included.(Supply + Return) with 13mm thick insulation on liquid line & 19mm thick insulation sleeves on Suction Line)
Supply, installation, testing & commissioning of ref nut / Y-joints of brass for indoor and outdoor units for suitable size as per requirement. For Outdoor Unit
Supply, installation, testing & commissioning of Ref nut / Y-joints of brass for indoor and outdoor units for suitable size as per requirement. For Indoor Unit
Supply and fixing of drain piping in hard PVC with all fittings, supports and clamps, including drilling hole in wall to route the drain pipe with 6mm thick nitrile rubber insulation.- 25mm with 9mm nitrile tubes.
Supply and drawing Control Cable between the indoor units & outdoor units. 2C x 0.75 Sq.mm Shielded Braided PVC inner sheathed, copper conductor, communication cable from indoor to outdoor units & between central controller.
Supply, fabrication and installation at proposed location of MS base frame ( for VRF machine Out Door Unit).The same shall be fabricated form 100mm wide "C" channels & shall be painted with primer and black paint.
Weartech Engineers Pvt Ltd
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .