Provision of 2.5 MVA Capacity, 33/11 KV Power Transformer for Technical Area at Site 2P
2021_DRDO_618538_1
CCE(R AND D)E/ENQ-69/EM/2P/2020-21
Limited
Electrical Works
Item Rate
90 days
Site 2P Panagarh
Please refer Tender documents
7 documents required · 7 mandatory
₹500
Yes
CCE(R and D) East
Exempted
27 Apr 2021
4 Mar 2021
25 Mar 2021
4 Mar 2021
24 Mar 2021
15 Mar 2021
5 Mar 2021 - 9 Mar 2021
Amount
33/11 kV 2.5 MVA Transformer Supply,installation,testing and commissioning of 33KV/11KV 2.5MVA outdoor ONAN Copper wound Power Transformer with On load Tap changer +5 to-10% in steps of 2.5% with RTCC Panel Consisting of Automatic Voltage regulator as per detailed Technical Specifications consisting of Buchholtz'sTechnical Specifications consisting of Buchholtz's relay with Alarm and trip contacts, winding temp and Oil temp alarm contacts, lifting lugs, earthing stud and marshalling box as per manufacturing drawings. Oil level Indication with alarm circuit, Pressure Relief Valve, etc. as complete in all respect as required. Secondary side suitable to 3Cx300 Sq.mm XLPE HT Cable box and Primary side suitable cable Terminal box for 33 KV XLPE 3 core 185 Sqmm cable. The transformer shall be as per latest BIS standard (Make :- Kirloskar/Volt Amps / ABB / Schneider)
33 kV VCB Panel Supply Installation Testing and commissioning of 36KV,1250A Floor Mounted Indoor Vacuum Circuit Breaker Panels. The SF6/VCB (26KA/3 sec) Panel Horizontal withdrawals made of 14Swg CRCA Sheet Steel Clad, Synthetic Eporxy powder coated finish painted, totally enclosed free standing cubicle type, suitable for operation on 33KV 3Ph, 50Hz, AC earthed system. full set complete with bus bar inter connections contol wiring designation labels, caution notice, including pad locking facilities.VCB Shall be motorised spring Charging (230V healthy and shall be as per detailed specifications.dual core CTs (100-50/1A+1A) are to be Provided for Protection and Metering of Burden and class of Accuracy as specified in Specifications, 33KV/110V PT with Voltmeter,Ammeter,PF meter, KWH Meter, Relays type MICOM 127 Numerical with Hi-Set current & Voltage, Over load and Earth fault, Buchholtz's relay with Alarm and trip contacts, winding temp and Oil temp alarm contacts, Oil level Indication with alarm circuit etc Phase Indicating lamps,Breaker On/Off/Trip and Spring Charge and trip circuit Healthy indications with Local & Remote operation. Make : ABB / Kirloskar / Schneider / L&T
HT Cables: Supply, Laying and commissioning of following size 33/11KV grade XLPE Insulated armoured Aluminium Conductor underground cable in ground at a depth of 1000mm below ground level including excavation and refilling of earth after cables are laid,providing protection with sand and bricks at sides and RCC slab on top and cable route markers at every 15m interval and also at the turnings.The cable shall confirm to IS 7098/Part-II a) 3CX185Sq.mm, 33KV XLPE Armoured cable Make: Havells / Finolex / KEI / Polycab
b) 3CX185Sq.mm, 11KV XLPE Armoured cable Make: Havells / Finolex / KEI / Polycab
Providing Indoor/Outdoor Heat Shrinkable end terminations for the cable specified above with all materials,Bi-metallic Lugs using Crimping tool, 33/11KV Insulation tape,Identification tags etc.,including end termination and earthing of termination kit a) 3CX185Sq.mm 33KV Indoor type terminations. Make : Raychem / CCI
b) 3CX185Sq.mm 11KV Indoor type terminations. Make : Raychem / CCI
Supply, installation, testing and commissioning of over current, earth fault relay MICOM P-122 for 11kV existing VCB
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Dismantling / Shifting / Removal of All external fittings of the Transformer / HT VCB
Credit for Old 2.0 MVA 33/11 KV Transformer
Credit for Old 33kV HT VCB
Santosh & Associates
CHARAN ELECTRICALS
MCC MECHANICAL AND ENGINEERING CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .