| 1 | L1₹18.4 LAccepted-AOC GATE NO 454 01 TAPKIR NAGAR PUNE NASIK HIGHWAY NEAR GANDHARV NAGARI MOSHI PUNE 412 105 | PUNE | MAHARASHTRA | 412105 | L1 | Accepted-AOC ACCEPTED BEING LOWEST BIDDER | |
| 2 | L2₹20.9 L+₹2.5 L (13.4%)Rejected-Finance | L2 | Rejected-Finance REJECTED BEING NOT LOWEST BIDDER |
| Sl No | Description | Qty | Unit | Mahindra Electric Stores L2 | ONKAR ELECTRIC AND GENERAL STORE L1 |
|---|---|---|---|---|---|
| 1.00 | Supply, installing, testing and commissioning of outdoor type step down transformer of capacity 22000/415 volt (at no load), AC 3 Phase 50 Hz capacity 500KVA core type copper wound oil immersed, naturally cooled, oil natural air natural (ONAN) with external cooling tubes, Delta connected on primary side (HV) and star connected on secondary sides (LV) in accordance the vector symbol DYN - 11(Vector Group) with neutral brought on secondary side (LV) and having tapping at +5% HV side to (-)10% in steps of 2.5% for variation of HV in no. of tap position -7 be changed by means of hand operated off load tap changer gear. The maximum temp. rise shall not exceed 45 degree celcius when measured by resistance method for transformer winding and 35 degree celcius measured by thermometer for oil and 35 degree celcius HV/LV winding when measured by resistance method (necessary test certificate carried out at factory side to be produced) after continuous full load run on an ambient temperature of 45 degree celcius. The transformer shall be IS-1180 marked and shall comprise of following and having energy efficencylevel 2 latest vesion:- | 1 | Each | 18,50,000 ₹18,50,000 | 16,15,000 ₹16,15,000 Lowest |
| 1.01(a) 3 Nos porcelain bushing with MS cable box sealed for HV side suitable for 22KV complete with bushing, copper rod, Nut and Washers, bushing shall conforming to IS- 2099. (b) One cable box on LT side (secondary side) consisting of 04 Nos poreclain bushing shall confirming to IS -7421 with copper rods, complete with nuts and washers with 2 Nos cable glands suitable for reseption / taking out of XLPE insulated heavy duty armoured cable including glands, joint and jointing materials complete. (c) Oil conservator with filter type drain valve and oil level gauge. (d) Dehydrating breather with first fills dehydrating agent (silica gel). (e) Explosive vents. (f) Thermometer pocket on Tank cover. (g) One No. 100 mm dia, Dial type thermometer, vapour pressure type having range 0-120 degree celcius with metal gaurd having maximum perimeter reading temperature indicator with resistance device for transformer. (h) Two earthing terminal on tank cover to facilitate fixing of single core multi stranded copper conductor cable PVC insulated of size of 25 sq. mm earth strip for earthing of neutral and body. (j) Buchholz Relay for alarming and triping of C.B. (k) First fill transformer oil as per IS - 335-1972 up to desired level. NOTE - The quoted rates are inclusive for single core multi stranded copper cable, PVC insulated of size 25 sq mm - 40 RM for neutral and body earthing lead. | |||||
| 2.00 | Material and Labour for trolley for transformer of size 2.8 x 2.5 m made out of mild steel angle/chanels medium weight beams and MS flats with necessary welding in position drilling in hot / cold etc. for longitude and cross members of trolley made out of ISMC channel 100 and top of the member covered with 6 mm thick MS chequred plate platform and vertical support over the platform with MS angle of size 50 x 50 x 6 mm thick MS flate 50 x 5 mm thick for two runs of bracing the supports , V type towing frame with hook with spring and check nut and mounting bracket with bush for movement of two assembly. The assembly made out of ISMC chanel 100 with long and cross member , turning plate assembly for front wheel only fitted in front axle, the front and real axle are made out of medium weight beam ISMB 100 including tyre with tube F78-15 8 play rataing 4 nos. with wheel drum, mounting bracket, bearing, check nuts, locknuts, key, etc. welded with medium beam with nut bolts washers as requried for mounting the transformer and applying two coats of synthetic enamelled paint of tint as approved by GE over a coat of red oxide primer complete all as specified and as directed by Engineer -in- Charge. | 1 | Each Job | 1,42,000 ₹1,42,000 Lowest | 1,70,000 ₹1,70,000 |
| 3.00 | Supplying ,laying, jointing, testing and commissioning of XLPE insulated screened PVC bedded galvanised steel strip or wire armored electric power cable (Heavy duty ) with aluminium conductor 22000 volts grade, cross sectional area 240 sqmm 3 core suitable for 22KV earthed system including both side end termination joints with suitable size of cable lugs and testing comlete all as specified and directed. | 25 | RM | 2,500 ₹62,500 | 1,300 ₹32,500 Lowest |
| 4.00 | Supply, laying & testing cable XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor, of size 3.5 core, 300 Sq mm laid in tranches passing through pipes /ducts both side end termination joints with suitable size of cable lugs and testing complete all as specified and directed by Engr in Charge. | 18 | RM | 1,850 ₹33,300 | 1,350 ₹24,300 Lowest |
Tender Value
₹20.7 L
EMD Value
₹41,500
Closing Date
13 Dec 2025, 6:00 pmClosed
CWE Khadki Pune
Headquarters CWE Khadki, Military Engineer Services, Range Hills Road, Khadki, Pune-411003
PROVISION OF TROLLEY MOUNTED TRANSFORMER OF 500 KVA AND 3PH UNDER GE MH AND RH KHADKI
2025_MES_727702_2
CWE/KKE/TOKEN-121 OF 2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
CWE Khadki Pune
As per tender documents
6 documents required · 6 mandatory
₹500
GE MH AND RH KHADKI
₹41,500
Yes
3 Feb 2026
26 Nov 2025
15 Dec 2025
26 Nov 2025
13 Dec 2025
6 Dec 2025
26 Nov 2025 - 2 Dec 2025
Amount
Supply, installing, testing and commissioning of outdoor type step down transformer of capacity 22000/415 volt (at no load), AC 3 Phase 50 Hz capacity 500KVA core type copper wound oil immersed, naturally cooled, oil natural air natural (ONAN) with external cooling tubes, Delta connected on primary side (HV) and star connected on secondary sides (LV) in accordance the vector symbol DYN - 11(Vector Group) with neutral brought on secondary side (LV) and having tapping at +5% HV side to (-)10% in steps of 2.5% for variation of HV in no. of tap position -7 be changed by means of hand operated off load tap changer gear. The maximum temp. rise shall not exceed 45 degree celcius when measured by resistance method for transformer winding and 35 degree celcius measured by thermometer for oil and 35 degree celcius HV/LV winding when measured by resistance method (necessary test certificate carried out at factory side to be produced) after continuous full load run on an ambient temperature of 45 degree celcius. The transformer shall be IS-1180 marked and shall comprise of following and having energy efficencylevel 2 latest vesion:-
(a) 3 Nos porcelain bushing with MS cable box sealed for HV side suitable for 22KV complete with bushing, copper rod, Nut and Washers, bushing shall conforming to IS- 2099. (b) One cable box on LT side (secondary side) consisting of 04 Nos poreclain bushing shall confirming to IS -7421 with copper rods, complete with nuts and washers with 2 Nos cable glands suitable for reseption / taking out of XLPE insulated heavy duty armoured cable including glands, joint and jointing materials complete. (c) Oil conservator with filter type drain valve and oil level gauge. (d) Dehydrating breather with first fills dehydrating agent (silica gel). (e) Explosive vents. (f) Thermometer pocket on Tank cover. (g) One No. 100 mm dia, Dial type thermometer, vapour pressure type having range 0-120 degree celcius with metal gaurd having maximum perimeter reading temperature indicator with resistance device for transformer. (h) Two earthing terminal on tank cover to facilitate fixing of single core multi stranded copper conductor cable PVC insulated of size of 25 sq. mm earth strip for earthing of neutral and body. (j) Buchholz Relay for alarming and triping of C.B. (k) First fill transformer oil as per IS - 335-1972 up to desired level. NOTE - The quoted rates are inclusive for single core multi stranded copper cable, PVC insulated of size 25 sq mm - 40 RM for neutral and body earthing lead.
Material and Labour for trolley for transformer of size 2.8 x 2.5 m made out of mild steel angle/chanels medium weight beams and MS flats with necessary welding in position drilling in hot / cold etc. for longitude and cross members of trolley made out of ISMC channel 100 and top of the member covered with 6 mm thick MS chequred plate platform and vertical support over the platform with MS angle of size 50 x 50 x 6 mm thick MS flate 50 x 5 mm thick for two runs of bracing the supports , V type towing frame with hook with spring and check nut and mounting bracket with bush for movement of two assembly. The assembly made out of ISMC chanel 100 with long and cross member , turning plate assembly for front wheel only fitted in front axle, the front and real axle are made out of medium weight beam ISMB 100 including tyre with tube F78-15 8 play rataing 4 nos. with wheel drum, mounting bracket, bearing, check nuts, locknuts, key, etc. welded with medium beam with nut bolts washers as requried for mounting the transformer and applying two coats of synthetic enamelled paint of tint as approved by GE over a coat of red oxide primer complete all as specified and as directed by Engineer -in- Charge.
Supplying ,laying, jointing, testing and commissioning of XLPE insulated screened PVC bedded galvanised steel strip or wire armored electric power cable (Heavy duty ) with aluminium conductor 22000 volts grade, cross sectional area 240 sqmm 3 core suitable for 22KV earthed system including both side end termination joints with suitable size of cable lugs and testing comlete all as specified and directed.
Supply, laying & testing cable XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor, of size 3.5 core, 300 Sq mm laid in tranches passing through pipes /ducts both side end termination joints with suitable size of cable lugs and testing complete all as specified and directed by Engr in Charge.
Mahindra Electric Stores (BID ID -3496976)
Bidder Name
Mahindra Electric Stores
ONKAR ELECTRIC AND GENERAL STORE
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
Tender.pdf
Tender Documents • 0.69 MB
BOQ_830390.xls
BOQ • 3.71 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .