| 1 | L1₹10.6 LAccepted-Finance 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA | MEERUT | UTTAR PRADESH | 250103 | L1 | Accepted-Finance ok | |
| 2 | L2₹10.8 L+₹17,383.76 (1.64%)Accepted-Finance | L2 | Accepted-Finance ok |
| Sl No | Description | Qty | Unit | STANDARD CAPACITORS L2 | Premier Engineering Company L1 |
|---|---|---|---|---|---|
| 1.00 | REPAIR/ RENOVATION OF APFC Panel 200 kVAr: 02 Nos. Dismantling of defective capacitor units from the APFC panel after suitably discharging the left-over charge on capacitors to ensure safety of the working persons along with dismantling of APFC relay, indications lights, meters, A/M switches, MCBs including dismantling of terminations and existing hardware and rusted parts and various other items requiring change in the panel as required at site. | 2 | Jobs | 25,000 ₹29,500 Lowest | 27,000 ₹31,860 |
| 2.00 | Replacement of defective Super Heavy-Duty Capacitor units of various capacities with new capacitor units, rated at 440 V, 3 phase, 50 Hz system complete with terminal cover, cable end entry, mounting structure and hardware etc. Make – Standard. | 300 | KVAR | 1,34,400 ₹1,58,592 Lowest | 1,36,500 ₹1,61,070 |
| 3.00 | Banking of capacitors of various capacities with multistrand copper wires & lugs/ aluminium bus bars and mounting arrangement for parallel connection to form suitable rating capacitor bank. | 300 | KVAR | 43,500 ₹51,330 Lowest | 45,000 ₹53,100 |
| 4.00 | Replacement of defective APFC relay, with new microprocessor based APFC Relay having digital display of power factor and other parameters to sense power factor through control CT and give phased impulses to contactor coils for switching ON-OFF required number of capacitors as per requirement to achieve target power factor. Make – Standard. | 2 | Nos. | 46,720 ₹55,129.6 Lowest | 46,800 ₹55,224 |
| 5.00 | Programming of APFC relay for target power factor including setting of various parameters and keeping updated indications of the efficiency of electrical power usage, and improving it for reducing the power losses and avoid penalties from utility companies. | 2 | Jobs | 19,000 ₹22,420 | 17,000 ₹20,060 Lowest |
| 6.00 | Replacement of defective capacitor duty contactors suitable for 25 kVAr capacitor with new capacitor duty contactor. Make - Standard/ EPCOS. | 4 | Nos. | 21,648 ₹25,544.64 | 21,600 ₹25,488 Lowest |
| 7.00 | Replacement of defective triple pole MCB of 32 A capacity with new MCB for operation and safety of individual capacitor bank. Make - Standard/ L&T. | 4 | Nos. | 5,280 ₹6,230.4 | 5,200 ₹6,136 Lowest |
| 8.00 | Replacement Cooling Fan 4" for cooling of capacitor banks. | 2 | Nos. | 2,000 ₹2,360 | 1,900 ₹2,242 Lowest |
| 9.00 | Replacement Filter 6" for prevention of ingress of dust in the panel. | 1 | No. | 550 ₹649 Lowest | 600 ₹708 |
| 10.00 | Supply of 0-500V digital Voltmeter with selector switch.
Make–AE/ HPL/ Standard. | 2 | Nos. | 2,550 ₹3,009 Lowest | 2,600 ₹3,068 |
Tender Value
Refer Docs
EMD Value
₹22,500
Closing Date
4 Sept 2025, 2:30 pmClosed
Executive Engineer (EnM)HP-II
OFFICE OF THE EXECUTIVE ENGINEER (EnM) HP-II DELHI JAL BOARD GOVT OF NCT OF DELHI HAIDER PUR WATER WORKS, DELHI 110085
Renovation of Standard make APFC Panel at Delhi Cantonment BPS.
2025_DJB_277284_2
NIT-07/(2025-26)/HP-II
Open Tender
Miscellaneous Works
Works
30 days
EE(EnM)HP-II
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
DJB
₹22,500
17 Sept 2025
26 Aug 2025
4 Sept 2025
26 Aug 2025
4 Sept 2025
26 Aug 2025
REPAIR/ RENOVATION OF APFC Panel 200 kVAr: 02 Nos. Dismantling of defective capacitor units from the APFC panel after suitably discharging the left-over charge on capacitors to ensure safety of the working persons along with dismantling of APFC relay, indications lights, meters, A/M switches, MCBs including dismantling of terminations and existing hardware and rusted parts and various other items requiring change in the panel as required at site.
Replacement of defective Super Heavy-Duty Capacitor units of various capacities with new capacitor units, rated at 440 V, 3 phase, 50 Hz system complete with terminal cover, cable end entry, mounting structure and hardware etc. Make – Standard.
Banking of capacitors of various capacities with multistrand copper wires & lugs/ aluminium bus bars and mounting arrangement for parallel connection to form suitable rating capacitor bank.
Replacement of defective APFC relay, with new microprocessor based APFC Relay having digital display of power factor and other parameters to sense power factor through control CT and give phased impulses to contactor coils for switching ON-OFF required number of capacitors as per requirement to achieve target power factor. Make – Standard.
Programming of APFC relay for target power factor including setting of various parameters and keeping updated indications of the efficiency of electrical power usage, and improving it for reducing the power losses and avoid penalties from utility companies.
Replacement of defective capacitor duty contactors suitable for 25 kVAr capacitor with new capacitor duty contactor. Make - Standard/ EPCOS.
Replacement of defective triple pole MCB of 32 A capacity with new MCB for operation and safety of individual capacitor bank. Make - Standard/ L&T.
Replacement Cooling Fan 4" for cooling of capacitor banks.
Replacement Filter 6" for prevention of ingress of dust in the panel.
Replacement of defective/burnt out LED indication lights of various colours with new indication lights. Make – Standard.
Power wiring with 10 sq. mm multistrand copper wires for connection between capacitors and bus bar using copper lugs and necessary hardware etc. as required at site.
Installation of all above components in the existing capacitor banks with suitable fabrication work to accommodate new items in the existing enclosure / structure for alignment of components and ease of termination, complete with hardware on the mounting structure and termination of existing cables with lugs, tapes etc. complete with earthing of the capacitor banks, touching the rusted parts of the panel structure with paint for protection from moisture etc. as required at site.
Servicing of APFC panels including complete dusting of the panel, cleaning of contact points, Decarbonizing of joints, alignment of doors, checking of all nuts & bolts, control circuit and power circuit wiring dressing and renovation of control and power terminations etc. as required at site.
Testing & Commissioning of complete APFC Panel installation including following: 01. Meggering of complete capacitor installation using 500 V Megger. 02. Continuity test for checking continuity of all circuits to ensure that all circuits are properly wired. 03. Checking function and efficiency of various components of APFC panel.
REPAIR/ RENOVATION OF 85 kVAr STATIC CAPACITOR PANEL - 1 & 2 Dismantling of defective capacitor units from the APFC panel after suitably discharging the left-over charge on capacitors to ensure safety of the working persons along with dismantling of APFC relay, indications lights, meters, A/M switches, MCBs including dismantling of terminations and existing hardware and rusted parts and various other items requiring change in the panel as required at site.
Replacement of defective Heavy-Duty Capacitor units of various capacities with new capacitor units, rated at 440 V, 3 phase, 50 Hz system complete with terminal cover, cable end entry, mounting structure and hardware etc. Make – Standard.
Banking of capacitors of various capacities with multistrand copper wires & lugs/ aluminium bus bars and mounting arrangement for parallel connection to form suitable rating capacitor bank.
Replacement of defective triple pole MCCB of 250A capacity with new MCCB for operation and safety of capacitor bank. Make - L&T.
Replacement of defective triple pole MCCB of 125A capacity with new MCCB for operation and safety of capacitor bank. Make - L&T.
Replacement of defective triple pole MCB of 63 A capacity with new MCB for operation and safety of individual capacitor bank. Make - L&T.
Replacement of defective/burnt out LED indication lights of various colours with new indication lights, Make – Standard.
REPAIR/ RENOVATION OF 100 kVAr STATIC CAPACITOR PANEL- 3 & MOTOR SET , Dismantling of defective capacitor units from the APFC panel after suitably discharging the left-over charge on capacitors to ensure safety of the working persons along with dismantling of APFC relay, indications lights, meters, A/M switches, MCBs including dismantling of terminations and existing hardware and rusted parts and various other items requiring change in the panel as required at site.
Replacement of defective super Heavy-Duty Capacitor units of various capacities with new capacitor units, rated at 440 V, 3 phase, 50 Hz system complete with terminal cover, cable end entry, mounting structure and hardware etc. Make – Standard.
Banking of capacitors of various capacities with multistrand copper wires & lugs/ aluminium bus bars and mounting arrangement for parallel connection to form suitable rating capacitor bank.
Replacement of defective triple pole MCCB of 160A capacity with new MCCB for operation and safety of capacitor bank. Make – Standard.
STANDARD CAPACITORS (BID ID -1617106)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .