| 1 | H3₹47.0 L−₹2.0 L (3.98%)Accepted-AOC 19 1A BOSE PUKAR ROAD KASBA GROUND FLOOR KOLKATA 700042 | KOLKATA | KOLKATA | WEST BENGAL | 700042 | H3 | Accepted-AOC Contract awarded to M/s Intime Commotrade Pvt Ltd being lowest bidder | |
| 2 | H1₹49.5 LRejected-Finance 2A 40 1 DHARMATALA ROAD KASBA KOLKATA WEST BENGAL 700042 | KOLKATA | KOLKATA | WEST BENGAL | 700042 | H1 | Rejected-Finance higher rate quoted then H3 | |
| 3 | H2₹47.8 L−₹1.7 L (3.49%)Rejected-Finance DINBAZAR 131 339 S 1 WARD NO 4 JALPAIGURI WEST BENGAL 735101 | JALPAIGURI | JALPAIGURI | WEST BENGAL | 735101 | H2 | Rejected-Finance higher rate quoted then H3 |
| Sl No | Description | Qty | Unit | Intime Commotrade Pvt Ltd H3 | MIDSCOPE SUPPLIERS H2 | SPS TRADING H1 |
|---|---|---|---|---|---|---|
| 1.00 | M & L for excavating over areas, n exc 1.5 m deep and getting out in soft/loose soil complete all as specified and as directed. | 26 | Cum | 299 ₹7,774 Lowest | 300 ₹7,800 | 500 ₹13,000 |
| 2.00 | Removing surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed. | 26 | Cum | 80 ₹2,080 Lowest | 80 ₹2,080 Lowest | 100 ₹2,600 |
| 3.00 | M&L for Kankar or laterite,with mix of fly ash ,clinker & stone dust in the proportion of 1:3:6 ( i.e. 10% fly ash,30% clinker & 60% stone dust ) laying in layers n.exc 100mm thick ,spread, rolled and consolidated to gradient and camber required, watering ,ramming and compacted complete all as directed by Engg-in-charge . | 15 | Cum | 2,289 ₹34,335 Lowest | 2,300 ₹34,500 | 2,500 ₹37,500 |
| 4.00 | M&L for Hardcore using broken stone or boulders of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface complete all as specified. | 15 | Cum | 2,090 ₹31,350 Lowest | 2,100 ₹31,500 | 2,200 ₹33,000 |
| 5.00 | M & L for PCC (1:3:6) Type C2 using 40 mm graded crushed stone aggregates as in foundations, fillings and mass concrete complete all as specified. | 26.75 | Cum | 6,169 ₹1,65,020.75 Lowest | 6,200 ₹1,65,850 | 6,300 ₹1,68,525 |
| 6.00 | M & L for Sand filling under floors or in foundation including watering and consolidation complete all as specified. | 18.96 | Cum | 1,791 ₹33,957.36 Lowest | 1,800 ₹34,128 | 2,000 ₹37,920 |
| 7.00 | M & L for Machine pressed precast concrete prepolished interlocking paver block any shape and size confirming to IS 15658-2006 of 60 mm thickness, M- 35 Grade complete all as specified and as directed. | 150 | Sqm | 1,443 ₹2,16,450 Lowest | 1,450 ₹2,17,500 | 1,500 ₹2,25,000 |
| 8.00 | M & L for Machine pressed precast concrete interlocking prepolished paver block any shape and size confirming to IS 15658-2006 of 100 mm thickness, M-50 Grade complete all as specified. | 80 | Sqm | 1,791 ₹1,43,280 Lowest | 1,800 ₹1,44,000 | 2,000 ₹1,60,000 |
| 9.00 | Taking out existing precast concrete interlocking paver block of any shape and size, of 60 mm thickness carefully and fixing the same in same position complete all as specified and directed | 244 | Sqm | 120 ₹29,280 Lowest | 120 ₹29,280 Lowest | 150 ₹36,600 |
| 10.00 | M&L for providing and laying at or near ground level factory made kerb stone of M- 25 grade cement concrete in position to the required line, level and curvature , jointed with cement mortar 1:3 , including making joints with or without grooves , including making drainage opening wherever required complete all as specified and as directed. | 24.43 | Cum | 15,323 ₹3,74,417.51 Lowest | 15,400 ₹3,76,299 | 15,500 ₹3,78,742.5 |
Tender Value
₹48.8 L
EMD Value
₹97,600
Closing Date
30 Jan 2026, 9:00 amClosed
GE PANNGARH
GARRISON ENGINEER PANAGARH, MILITARY ENGINEER SERVICES, PO-PANAGARH, DISTT- BURDWAN, STATE-WEST BENGAL PIN-713420
All as per BOQ
2026_MES_747957_1
8500-499/E8
Open Tender
Civil Works
Works
180 days
PANNGARH
All as per tender documents
6 documents required · 6 mandatory
₹500
GE Panagarh
₹97,600
20 Feb 2026
10 Jan 2026
31 Jan 2026
10 Jan 2026
30 Jan 2026
24 Jan 2026
M & L for excavating over areas, n exc 1.5 m deep and getting out in soft/loose soil complete all as specified and as directed.
Removing surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed.
M&L for Kankar or laterite,with mix of fly ash ,clinker & stone dust in the proportion of 1:3:6 ( i.e. 10% fly ash,30% clinker & 60% stone dust ) laying in layers n.exc 100mm thick ,spread, rolled and consolidated to gradient and camber required, watering ,ramming and compacted complete all as directed by Engg-in-charge .
M&L for Hardcore using broken stone or boulders of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface complete all as specified.
M & L for PCC (1:3:6) Type C2 using 40 mm graded crushed stone aggregates as in foundations, fillings and mass concrete complete all as specified.
M & L for Sand filling under floors or in foundation including watering and consolidation complete all as specified.
M & L for Machine pressed precast concrete prepolished interlocking paver block any shape and size confirming to IS 15658-2006 of 60 mm thickness, M- 35 Grade complete all as specified and as directed.
M & L for Machine pressed precast concrete interlocking prepolished paver block any shape and size confirming to IS 15658-2006 of 100 mm thickness, M-50 Grade complete all as specified.
Taking out existing precast concrete interlocking paver block of any shape and size, of 60 mm thickness carefully and fixing the same in same position complete all as specified and directed
M&L for providing and laying at or near ground level factory made kerb stone of M- 25 grade cement concrete in position to the required line, level and curvature , jointed with cement mortar 1:3 , including making joints with or without grooves , including making drainage opening wherever required complete all as specified and as directed.
Supplying and laying of PVC underground drainage sewer system pipe bearing 160 mm dia SN 4 including jointing with couplar, bend tee as per site requirement complete laid in trenches or floors complete all as specified and directed.
M&L for providing precast cement concrete Type B1 1:2:4 (20 mm graded crushed stone aggregates) in landings, cover slabs (for man holes etc.) in chullah hoods, chajjas, water troughs, mangers, shelves and similar articles with plain faces complete all as specified
M&L for prepration of new plastered surfaces of kerb stones of any description applying Two or more coats of 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives @ 1.43 litre/ 10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/ 10 sqm over new surfaces complete all as specified.
Taking down/dismantling of unserviceable LT panels complete including Earth Work,dismantling of brick works,PCC etc all as specified and directed by Engineer-in-Charge.
Supply,designing ,install, testing & commission 3 phase and neutral, 415 volts outdoor type, CPRI type tested having certification of IEC-61439 , factory made , dust and vermin proof, cubical type LT panel of size 1.50m x 0.45m x 1.50m, with canopy fabricated from 3.00 mm thick CRCA sheet for outer shell and 2 mm thick for non load bearing with angle iron frame of 50 x 50 x 6 mm, double door, front and back openable type, double door system, hinged opening, rubber lining, locking arrangement, with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade, protection class IP-66 fully compartmentalize design with 4 Nos of bus bar made of aluminium, 800 Amps rated (electrical grade aluminium complying with the requirements of latest BIS, colour coded), busbar extensions for cable connections of electrolytic grade . The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated pre-wired with suitable size of copper strip/copper wire with colour code for connecting out going MCCB/MCB's, including suitable aluminium earth strips conforming to IS with danger notice plate, necessary cable glands, cable connection with proper lugs, making electrical connection and circuit wiring for street light auto ON/OFF control timer by using desired electrical parameters PCC foundation and pedestal for fixing pillar feeder box/LT Panel with PCC 1:3:6, 15 cm thick in foundation, brick (Fly ash) / PCC block work in CM 1:6, rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grounting bolts etc for panel. The platform shall be of 450 mm height above ground level all as specified with supply and fixing the following accessories including taking out the existing one :
Dismantling existing LT panels of any type, any size carefully for reuse including necessary excavation demolition of concrete,disconnecting of earthing,cable, taking out burn out lugs,MCCBs,bus bars,insulators and other connected works ,surface levelling etc. and reinstall the LT panels after repair/replacement of burn out lugs,MCCBs,bus bars,insulators, wiring etc including re-connection of earthing,cables with new foundation of panels, brick works,PCC works etc complete including testing all as specified and as directed by Engr-in-charge.(NOTE : Earth Work,brick works, foundation work, PCC, lugs, switch gear, metering devices, bus bar,insulators, cable for wiring etc will be Measured and Paid separately under relevant Items as supply only).
S&F Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, Fe 410-W (GdeE- 250) qualityAdrilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging, also fastening and fixing complete.
M & L for cross arms , bracing, supports , clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as directed inclusive of 2 coats of aluminium paint over a coat of red oxide primer, complete all as specified and as directed.
M&L PCC (1:3:6) type C2 using 40mm graded aggregate as in foundation for stay set /Pole/ Panels etc including fair finish even and fir to exposed surfaces without using extra cement complete all as specified and as directed.
M & L PCC (1:2:4) type B-1 (with using 20 mm graded stone aggregate) as in coping of pole/panel including necessary form work as required complete as directed
M&L Brick work with flyash bricks old size bricks, straight or curved on plan exc. 6m mean radius built in cement mortar 1:6 complete all as directed.
M & L for 15mm thick rendering in cm (1:4) on fair face of brick work finished even & fair complete all as specified & directed.
M & L for Hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface as specified and directed.
Supply only the followings ( to be incorporated against Item No 43.00 and 44.00 only)
MCCB 63 Amps rating, 4 pole , 415 V, AC, 50 HZ, adjustable thermal & adjustable magnetic setting setting, Ics-100 % Icu , service breaking capacity 16 KA.
MCCB 100 Amps rating, 4 pole , 415 V, AC, 50 HZ, adjustable thermal & adjustable magnetic setting setting, Ics-100 % Icu , service breaking capacity 16 KA.
MCCB 125 Amps rating, 4 pole , 415 V, AC, 50 HZ, adjustable thermal & adjustable magnetic setting setting, Ics-100 % Icu , service breaking capacity 16 KA.
MCCB 160 Amps rating, 4 pole , 415 V, AC, 50 HZ, adjustable thermal & adjustable magnetic setting setting, Ics-100 % Icu , service breaking capacity 16 KA.
MCCB 200 Amps rating, 4 pole , 415 V, AC, 50 HZ, adjustable thermal & adjustable magnetic setting setting, Ics-100 % Icu , service breaking capacity 36 KA.
MCCB 250 Amps rating, 4 pole , 415 V, AC, 50 HZ, adjustable thermal & adjustable magnetic setting setting, Ics-100 % Icu , service breaking capacity 36 KA.
MCCB 350 Amps rating, 4 pole , 415 V, AC, 50 HZ, adjustable thermal & adjustable magnetic setting setting, Ics-100 % Icu , service breaking capacity 36 KA.
MCCB 400 Amps rating, 4 pole , 415 V, AC, 50 HZ, adjustable thermal & adjustable magnetic setting setting, Ics-100 % Icu , service breaking capacity 36 KA.
Taking down/out unserviceable or serviceable UG Cables of any Cross Sectional Area and Connections including Bricks, GI Pipes, etc. of any descriptions, laid in Trenches and/or fixing with Walls/Poles including Segregating of Serviceable Materials viz Bricks, Cables, GI Pipes, etc. and keep in Safe custody for re-use, complete all as specified and as directed. (NOTE : Earth Work shall be Measured and Paid for separately under relevant Items).
Laying only in trenches or passing through pipe, XLPE insulated, heavy duty, galvanised steel strip armoured electric LT cable with solid aluminium conductor for 1100 volts grade cross sectional area 10 sqmm 4 core ncluding providing Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed Note : Cable will be issued under Sch B free for laying only
Laying only in trenches or passing through pipe, XLPE insulated, heavy duty, galvanised steel strip armoured electric LT cable with stranded aluminium conductor for 1100 volts grade cross sectional area 16 sqmm 4 core ncluding providing Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed Note : Cable will be issued under Sch B free for laying only
Laying only in trenches or passing through pipe, XLPE insulated, heavy duty, galvanised steel strip armoured electric LT cable with stranded aluminium conductor for 1100 volts grade cross sectional area 25 sqmm 3.5 core ncluding providing Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed Note : Cable will be issued under Sch B free for laying only
Laying only in trenches or passing through pipe, XLPE insulated, heavy duty, galvanised steel strip armoured electric LT cable with stranded aluminium conductor for 1100 volts grade cross sectional area 50 sqmm 3.5 core ncluding providing Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed Note : Cable will be issued under Sch B free for laying only
Laying only in trenches or passing through pipe, XLPE insulated, heavy duty, galvanised steel strip armoured electric LT cable with stranded aluminium conductor for 1100 volts grade cross sectional area 70 sqmm 3.5 core ncluding providing Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed Note : Cable will be issued under Sch B free for laying only
Laying only in trenches or passing through pipe, XLPE insulated, heavy duty, galvanised steel strip armoured electric LT cable with stranded aluminium conductor for 1100 volts grade cross sectional area 95 sqmm 3.5 core ncluding providing Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed Note : Cable will be issued under Sch B free for laying only
Laying only in trenches or passing through pipe, XLPE insulated, heavy duty, galvanised steel strip armoured electric LT cable with stranded aluminium conductor for 1100 volts grade cross sectional area 120 sqmm 3.5 core ncluding providing Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed Note : Cable will be issued under Sch B free for laying only
Laying only in trenches or passing through pipe, XLPE insulated, heavy duty, galvanised steel strip armoured electric LT cable with stranded aluminium conductor for 1100 volts grade cross sectional area 150 sqmm 3.5 core ncluding providing Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed Note : Cable will be issued under Sch B free for laying only
Laying only in trenches or passing through pipe, XLPE insulated, heavy duty, galvanised steel strip armoured electric LT cable with stranded aluminium conductor for 1100 volts grade cross sectional area 185 sqmm 3.5 core ncluding providing Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed Note : Cable will be issued under Sch B free for laying only
Re-Laying/Fixing or Passing through Pipe, XLPE insulated, Armoured, Electric Power UG Cable (Heavy Duty) with Aluminium Conductor, 1100 Volt Grade, Nominal Cross-Sectional Area 10 Sqmm 4 Core including Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed.
Re-Laying/Fixing or Passing through Pipe, XLPE insulated, Armoured, Electric Power UG Cable (Heavy Duty) with Aluminium Conductor, 1100 Volt Grade, Nominal Cross-Sectional Area 16 Sqmm 4 Core including Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed.
Re-Laying/Fixing or Passing through Pipe, XLPE insulated, Armoured, Electric Power UG Cable (Heavy Duty) with Aluminium Conductor, 1100 Volt Grade, Nominal Cross-Sectional Area 25 Sqmm 3.5 Core including Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed.
Re-Laying/Fixing or Passing through Pipe, XLPE insulated, Armoured, Electric Power UG Cable (Heavy Duty) with Aluminium Conductor, 1100 Volt Grade, Nominal Cross-Sectional Area 50 Sqmm 3.5 Core including Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed.
Re-Laying/Fixing or Passing through Pipe, XLPE insulated, Armoured, Electric Power UG Cable (Heavy Duty) with Aluminium Conductor, 1100 Volt Grade, Nominal Cross-Sectional Area 70 Sqmm 3.5 Core including Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed.
Excavating in trenches , n.exc 1.5 m wide and n.exc 1.5 m depth for foundation etc or for shafts, wells, cesspits ,manhole pier hole etc n.exc 10 sqm on plan and n.exc 1.5m in depth and getting out in any kind of soil Note : Manual excavation to be done. During excavation if any damage occured to existing cable any type/ water pipe line, it will be contractor responsibilty to get it repair and make functional by providing jointing kit etc without any extra cost. Contractor has to repair it within 24 hrs so that essential service can not be effected due to such damage.If contractor fails to repair it within 24 hrs penalty @ Rs 500/- will be charged to contractor. In this GE decision will be final, conclusive and binding.
Returning, Filling in, including Spreading, Levelling, Watering and Well Ramming in Layers not exc. 250mm in Soft/Loose Soil, complete all as specified and as directed.
Removing excavated Materials (Soils) not exc. 50.00 mtr and depositing where directed at a level not exc. 1.50 mtr above the Starting Point in Soil, complete all as specified and as directed.
M&L Sand Cushioning (dry) in trenches for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 230mm Spread thickness and consolidated (punned) upto 180mm thickness, complete all as specified and as directed. (NOTE : For the purpose of Payment, Punned thick-ness of Sand Cushioning only shall be Measured and Paid )
Supply and laying well burnt Bricks , locally available best quality (sub class "B" bricks) laid in trenches perpandicular to U/G cable for cable protection complete all as specified.
S & F 50 mm High density polyethylene pipe (HDPE) of pressure rating 6 kgf/cm2 fixed complete to walls, ceilings or in floors etc. complete all as specified and directed .
S&F Galvanised Iron Pipe 80mm Bore (dia) ‘Light Grade’ for protection of UG Cable, laid in Floors/ Road Crossing, fixing to Pole with Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed.
S&F Galvanised Iron Pipe 50mm Bore (dia) ‘Light Grade’ for protection of UG Cable, laid in Floors/ Road Crossing, fixing to Pole with Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed.
S&F Galvanised Iron Pipe 100mm Bore (dia) ‘Light Grade’ for protection of UG Cable, laid in Floors/ Road Crossing, fixing to Pole with Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed.
Labour only for Horizontal Boring for Passing Protection Pipe up to 80mm Bore (dia), under Road /Foot Path, not exc. 10.00 mtr in a Single Length, complete all as specified and as directed. Note : Pipe to be measured separately.
M&L for straight through joint (heat shrinkable) complete suitable for LT 1100 Volt aluminium conductor cable of size 3.5/4 x 10-16 sqmm and testing after jointing of following sizes of cables. Note Payment will be released only after submission of PV and test certificate
M&L for straight through joint (heat shrinkable) complete suitable for LT 1100 Volt aluminium conductor cable of size3.5/4 x 25-50 sqmm and testing after jointing of following sizes of cables, Note Payment will be released only after submission of PV and test certificate
M&L for straight through joint (heat shrinkable) complete suitable for LT 1100 Volt aluminium conductor cable of size3.5 x 70-150 sqmm and testing after jointing of following sizes of cables. Note Payment will be released only after submission of PV and test certificate
M&L for straight through joint (heat shrinkable) complete suitable for LT 1100 Volt aluminium conductor cable of size3.5 x 185-240 sqmm and testing after jointing of following sizes of cables. Note Payment will be released only after submission of PV and test certificate
S & F HDPE DWC (Double Walled Corrugated) of Diameter 40 mm including disconnection and connection of cable near panel/OH for pipe fixing including joints complete all as directed.
S & F HDPE DWC (Double Walled Corrugated) of Diameter 50 mm including disconnection and connection of cable near panel/OH for pipe fixing including joints complete all as directed.
S & F HDPE DWC (Double Walled Corrugated) of Diameter 100 mm including disconnection and connection of cable near panel/OH for pipe fixing including joints complete all as directed.
Material and labour for earthing complete with Galvanised steel earth plate electrode 600x600x6 mm mm buried directly in ground (Earth pit not less than 2.25m below ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to GI strip 32x6 mm as earth lead by means of bolt, nuts, check nuts and washers of galvanised iron or steel, upto 7.5m length, earth strip protected by and including 40 mm dia GI pipe (light grade) and connected to main test point or body of pole/pannel or lightening arrester of main controlling switch as directed including concrete pit in PCC (1:3:6) type C1 , Precast RCC (1:2:4) Type B1 cover slab of size 54x54x5 cm reinforced with 8 mm dia TMT bars @ 100 mm C/C both ways with one handle for lifting made out of 10 mm dia TMT bar embedded in precast cover slab, funnel, wire mesh, 20 mm bore GI Pipe (Medium Grade) for watering, Charcoal and salt in alternate layers of 15 cm (Compacted Thickness) around the earth electrode including necessary excavation, earth work in any type of soil and disposal of spoil to a distance n.exc 50 m and necessary testing complete all as shown in Electrical Plate No 3 of SSR Part-I. NOTE : 1. The unit rare includes for protectionh GI pipe of 40mm and watering pipe of 20mm bore including excavation for earth pit in any type of soil/disintegrate rock. 2. Contractor has to bring agriculture soil from outside of defence land and fill in earth pit to acheive desired result as the soil resisitivity is very high. 3. The cost of GI strip of 32x6mm including protection pipe, from top of earth plate upto 7.5 meter above/below ground level is deemed to be included in the unit rate. 4. All the joints in GI strip and connectgion with earth plate to be welded through brazing and in addition by providing double brass nut bolt and washer. 5.Costing of welding and nut bolts are deemed to be included in the unit rate
M&L for preparation of existing surface of LT Panel by srapping down peeled off old paint, cleaning etc and applying Two coat of Siemens Grey Paint by using spray machine and Black paint on Angle Iron over a coat of red oxide primer complete all as specified and directed by Engr in Charge.
Supply and Fix Metal cable route indicator of height 750 mm MS Flat of 40 mm x 4 mm with Circular 100 mm diameter MS Sheet of minimun thickness 3 mm duly engraved " LT CABLE" including Aluminium paint over it and to be fixed 150 mm below ground level with PCC (1:3:6) (40 mm aggregate) of size 250x250x300 mm all as directed by Engr-in-Charge.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
PS499.pdf
Tender Documents • 1.30 MB
BOQ_837605.xls
BOQ • 0.49 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .