| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.9 LAccepted-AOC 50 SARASWATI VIHAR SINGHAWALA AMBALA CITY | AMBALA CITY | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹39.0 L+₹95,205 (2.50%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹45.6 L+₹7.6 L (19.9%)Rejected-Finance | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹47.6 L+₹9.5 L (25.1%)Rejected-Finance | L4 | Rejected-Finance Other than lowest | |
| 5 | Rejected-Technical | - | Rejected-Technical Not enlisted b ii category |
Tender Value
₹43.6 L
EMD Value
₹87,200
Closing Date
11 Dec 2021, 6:00 pmClosed
GE (AF) Halwara
GE (AF) Halwara
PROVISIONING AUGMENTATION UPGRADATION OF INTERNAL EXTERNAL ELECTRICAL INFRASTRUCTURE OF SMQ PHASE 1 AND STP AT AF STN BARNALA UNDER GE AF HALWARA
2021_MES_488126_1
GE/HAL-53/2021-22
Open Tender
Civil Works
Item Rate
183 days
GE (AF) Halwara
MES ENLISTED CONTRACTORS CLASS D CATEGORY b ii
8 documents required · 8 mandatory
₹500
Yes
GE (AF) Halwara
₹87,200
Yes
18 Dec 2021
13 Nov 2021
13 Dec 2021
13 Nov 2021
11 Dec 2021
27 Nov 2021
Amount
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exeeding 1.5 m deep, getting out the excavated earth, bottom surface made to required gradient complete all as specified and directed. Note:-Excavation work will be done manually to avoid damage to the existing cable network.
M&L for removal of excavated material such as soils n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed.
Returning filling in, and including spreading and leveling in layers not exceeding 25 cm thick complete all as specified & directed.
M&L for dry river washed sand cushioning in cable trenches for protection of cables with two layers below and above cable and punned down to specified thickness complete all as specified and as directed. Note: Punned thickness shall only be measured for payment.
M&L for well burnt old size sub Class ‘B’ bricks, laid flat, in trenches for cable protection complete all as specified and as directed.
Supply and laying un-reinforced precast concrete cable cover , Class HV type-I, size 300mmx180mmx40mm for protection of cable complete all as specified and as directed.
M &L for GI pipe 50mm dia, light grade for road crossing / on wall / with pole for cable protection of including cutting chasing of plinth protection or wall for inserting of cable and making good disturbed surface with PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) complete all as specified and directed .
All as per Sl item No 7 above but 100mm dia light grade GI pipe
S&F Metal cald enclosure single pole and neutral enclosure with a two pin and earth plug and socket complete with one double pole, C curve, MCB 20 Amps complete all as specified and as directed.
S & F in replacement of sub-main wiring with two single core cables PVC insulated and un-sheathed 10 sqmm (Nominal Area) FRLS stranded copper conductor drawn in existing PVC conduit including 10.00 Sq mm (Nominal Area) copper cable as earth continuity conductor after chasing in wall and making good the disturbed surfaces to match with the existing surfaces , necessary junction box and covers including necessary connections, PVC flexible pipes are used in pannel board while connecting the cable complete all as specified and directed by Engineer - in - Charge.
M & L for submain wiring with two runs of 4 Sqmm single core PVC insulated but unsheathed multi stranded copper conductor FRLS 1100 volts grade cable drawn through and including surface fixing casing caping ISI marked with 20 mm width with necessary accessories and one run of 4 Sqmm single core PVC insulated but unsheathed multistranded copper conductor 1100 volts grade cable as earth conductor, cutting chasing during crossing through wall/near staircase/roof and making good to disturbed srfaces and match with existing colour complete as specified and directed.
S & F sheet metal enclosure for double door made out of CRCA mild steel sheet surface with insulated material like polyester with epoxy powder coated surface mounted SP & N 4 ways, 240 Volts, ISI marked, 200 amps rated bus bar stove enameled dust and vermin proof suitable for incorporation MCBs and isolators etc complete all as specified and directed by Engineer - in - Charge.
S & F in replacment MCB ‘C’ series type suitable for 240 volts, AC supply 63 Amps, DP with over load and short circuit protection and rupturing capacity not less than 10KA complete all as specified and directed by Engineer - in - Charge
S & F MCB ‘C’ series type suitable for 240 volts, AC supply 20 Amps, DP with over load and short circuit protection and rupturing capacity not less than 10KA complete all as specified and directed by Engineer - in - Charge
Supply and fixing in replacment of 100 amp rating 240V, 10KA TPN MCB fixed in existing MCB DB and making connection as distribution of three phase with existing DB complete all as specified and directed.
Supply, install, test and commissioning of transformer of 250 KVA, step down Outdoor type,platform mounted, complete with standard fittings, HT 11 KV 3 phase, LT 433 volts, 3 phase 4 wire corrugated off circuit tape links of rating + 7.5% to -7.5% @ 2.5% by means of hand operated off load tap changing gear all as per IS-2026, transformer copper wound, double wound, oil immersed naturaly cooled with external cooling tubes core type delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol Dy-11 (vector group) with neutral brought on secondary side (LV side), maximum temperature rises should not exceed 45 degree centigrade in oil and 55 degree centigrade in HV / LV winding ring measured by resistance after continuous full load run in ambient temp as per IS-11171 per transformer, IS-3639 for fitting & accessories, IS-2099 for high voltage porcelian bushings and confirming to IS-1180 part-1:2014 and BEE certified for energy effciency including making platforms as per manufacturer design and the transformer shall be comprised with the following standard fitting:- (a) One cable box HV side consisting of 3 Nos porcelain terminal points including nuts, bolts and washers with two Nos cable gland suitable for 3 core 95sqmm HT UG cable (b) Suitable cable box LV side for mounting two LV cable consisting of 4 Nos porcelain with brass bushing rods, complete with nuts and washers with two Nos cable gland suitable for LT UG cable providing with bimetallic NOTE : (i) Excavation & earthwork (ii) All quantity are provisional with two Nos cable gland suitable for LT UG cable providing with bimetallic lugs. (c) Oil conservator with filler type drain valve and oil level gauge (d) Dehydrating breather with fast fill of dehydrating agent. (e) Explosion vents (f) Thermometer pocket on tank cover including thermometer (g) Rating plate and terminal marking plate (h) The earthing terminal two Nos to tank to facilitate fixing of earth strips of size 32 X 6 mm (j) Oil level gauge (k) Lifting lugs/ hooks (l) Oil filling hole with cap/plug with connection plate complete (m) Air relief valve. (n) Initial filing of transformer oil. (o) Detachable rollers with locking arrangement - 4 Nos Note: (i) Any other standard protection devices as per relavent IS to connect with VCB for protection. (ii) The transformer will have its initial oil filling to appropriate level (cost of oil including testing with desired electric strength deemed to be included in quoted rate)
Supply, installation, testing and commissioning of VCB Panel with 03 VCBs and 01 Metering unit and one side extensiable 11 KV, 630 Amps, outdoor Fixed Type, totally enclosed metal clad switchgear complete with 03 Vacuum Circuit Breakers (3V+1M) [one VCB as incomer and 02 VCBs as outgoing] having rupturing capacity 250 MVA, overload and earth fault protection, ammeter, voltmeter VCB (Vacuum Circuit Breaker) manual fixed-type 400A Vacuum Circuit Breaker , inside robotically welded stainless steel 304 (Non Ferrite Non Megnetic Grade) tank having min. thickness 3+0.5 mm with IP 67 Degree of Protection and enhanced BIL of 125kVp internally to manage voltage surges. VCB should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions & complete with all accessories. The VCB shall be type tested for Internal arc test of 21kA/3 sec as per IEC62271-200. VCB shall have on-site-repairability features such as site replacable bushing/coupling/mechanism and gas refilling at site. The earthing busbar shall be provided inside each cable compartment for soilid earthing of Cable sheilds. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection and making foundation plinth as OEM sugisted and in foundation plinth provide cable trench for incomming and outgoing cables. The unit shall include the following with all necessary standard fitting as required at site. Each Incomer VCB feeder consists of: 1. Manual operated 630A Vacuum Circuit Breaker with manual spring charging arrangement and manual close & open push buttons, ON / OFF indication and series trip coil for self powered relay & shunt trip coil for external tripping.-1 No. 2. Self powered O/C & E/F relay type CSPR with CTs of 200/1- 1A 2.5VA, 5P10 (Protection core) & 2.5VA, Cl 1 (Metering core).-1 Set 3. Manually operated 630A load breaker switch with built-in earth switch with full making capacity.-1 No. 4. Mechanical position indicator. Switch ON/OFF/EARTHED. 1 No. 5. Live Cable Indication. 1 No. 6. Cable compartment cover interlocked with earth switch. 1 No. 7. Cable termination bushings suitable for 1no. 3CX300mm2 XLPE cable.-3 No. 8. Right angle boots. 1 Set. Also refer \Sch Ä'' Notes for other fittings/fixures required against this item.
Supply, laying & testing cable XLPE insulated, 11 kV, 3 core 95 sqmm screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor complete all as specified and as directed.
M&L in replacement for jointing and testing cable jointing kit for 11 KV grade cable Outdoor type end termination heat shrinkable joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 50 to 95 sqmm complete all as specified and as directed.
Supply, laying and testing 70 Sqmm 4 Core cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor complete all as specified and directed.
All as per Sl item No 20 above but 50 Sqmm 4 core
All as per Sl item No 20 above but 35 Sqmm 4 core
M&L for spreading of stone aggregate of nominal size not more than 40mm from the bay/yard manually without damaging any equipments, cable or parts of the Grid bays, spreading & levelling of finished gravel uniformaly in layers n. exc. 15 cm thick watered and rammed to true surface all as specified and directed
M&L hand-rail straight portion,dr illed and countersunk for balusters running bars, for doors, balusters, nosing to steps including embeding in concrete and screwing etc. wind ties for roof including securing bolts, posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc. flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc.and similar work conforming to Fe-290 Gde E-165 complete all as specified and directed. Note :Exposed steel surface shall be treated with two coats of aluminium paint over a coat of red oxide primer and unexposed surface of steel sections shall be applied one coat of red oxide primer.
S&F galvanised mild steel chain link fencing of 3.15 mm dia mild steel wire with mesh of size 75mm x 75 mm complete all as specified and directed by Engineer-in-Charge.
M&L for framed work such as grills, gratings, etc. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors, ladders, framed balusters; walkways, railings, framework of water tanks and similar work conforming to Fe.290.Gde-E-165 complete all as specified and directed,
M&L for pre-cast reinforced cement concrete type B-l, 1:2:4 (20 mm graded aggregate) in posts, fencing posts, struts etc. for fencing, average sectional area not exc 250 sq. cm, with or without chamfered angles and flat, splayed, rounded or mitred tops as directed and fixed complete all as specified and directed by Engr-in-Charge..
S & F MCCB 320 Amps ,four pole, conforms to IS/IEC 60947-2, IEC 60947-2 & EN 60947-2 breaking capacity Icu(KA)AC : 50kA@ 415V AC,50 Hz/60 HzDC : 10kA@ 250V DC including spreader terminals and mounting in existing panel in spare MCCB box including making connections with 10 sqmm copper cable from MCCB to bus bar of panel complete all as specified and directed.
S & F MCCB 200 Amps, four pole, conforms to IS/IEC 60947-2, IEC 60947-2 & EN 60947-2 breaking capacity Icu(KA)AC : 36kA@ 415V AC, 50 Hz/60 HzDC : 10kA@ 250V DC including spreader terminals and mounting in existing panel in spare MCCB box including making connections with 10 sqmm copper cable from MCCB to bus bar of panel complete all as specified and directed.
S & F MCCB 125 Amps, four pole,Conforms to IS/IEC 60947-2, IEC 60947-2 & EN 60947-2 breaking capacity Icu(KA)AC : 36kA@ 415V AC, 50 Hz/60 HzDC : 10kA@ 250V DC including spreader terminals and mounting in existing panel in spare MCCB box including making connections with 10 sqmm copper cable from MCCB to bus bar of panel complete all as specified and directed.
S&F in replacment 100 amp rating 240V, 10KA TPN, MCB fixed in existing MCB DB and making connection as distribution of three phase with Existing DB complete all as specified and directed.
Supply, install, testing and commissioning LT Panel-1, Outdoor type, dust and vermin proof, totally enclosed, platform mounted, factory made having front openable shutter with locking arrangement made out of CRCA steel sheet 3.15 mm thick with MS angle iron frame work of size 40 mm x 40 mm x 6 mm thick, duly painted all as specified including necessary foundation bolts, PCC (1:2:4), type B-1 platform of suitable size for mounting the panel, suitable for 415 Volts, 50 Hz, three phase, 4 wire system with suitable insulated copper busbar of capacity not less than 600 Amps and shall be complete with internal wiring with copper conductor and including the following accessories:- INCOMER:- (i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 400 Amps, 415 volts, 50 Hz, rupturing capacity 36 KA, with adjustable thermal and adjustable magnetic setting - 01 No. (ii)LED Multifucntional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iii) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set Copper Bus Bar 600Amp TPN OUTGOINGS: (i) MCCB conforming to IS:13947 (Part-II), IEC-947, 4 pole, 320 Amps, 415 volts, 50 Hz, rupturing capacity 36 KA, with adjustable thermal and adjustable magnetic setting - 01 No. (for existing FD Panel) (ii) MCCB conforming to IS:13947 (Part-II), IEC-947, 4 pole, 125 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA, with adjustable thermal and fixed magnetic setting - 01 No. (For proposed STP plant ) (iii) MCCB conforming to IS:13947 (Part-II), IEC-947, 4 pole, 100 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA, with adjustable thermal and fixed magnetic setting - 02 No. (For existing FD of JWO) (iv) MCCB conforming to IS:13947 (Part-II), IEC-947, 4 pole, 63 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA, with adjustable thermal and fixed magnetic setting - 01 No. (Spare)
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized iron strip 25×4mm (up to 7.5m in length from earth plate) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shwon in electrical plate no 3 of SSR part 1 including Charcoal, Rock salt, necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1, 40 mm thick cover with MS bar 8mm dia 150mm c/c reingorcement, watering funnel, 15 mm dia light grade for protection of earth electrode, 20 mm dia for watering all as speicified and directed and tested on completion.
S&F galvanised iron strip 25x4 mm with porcelin saddles and fixing screws for roof conductors and down conductors above ground after taking down/out strip as existing at site complete all as specified and as directed. Note :- Strip should be brazed/welded at each joint.
GILL ENTERPRISES
BEHL AND COMPANY
M/S BALWINDER SINGH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .