Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | FIRST₹37.3 LAccepted-AOC | FIRST | Accepted-AOC BEING LOWEST | |
| 2 | SECOND₹43.7 LRejected-Finance | SECOND | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹43 L
EMD Value
₹86,000
Closing Date
3 Dec 2021, 6:00 pmClosed
GE (AF) MARATHAHALLI
GE AF MARATHAHALLI WIND TUNNEL ROAD, KEMPAPURA, YEMALUR POST, BANGALORE. PIN- 560037
SPECIAL REPAIR REPLACEMENT OF EARTHING PITS AT 26 ED AND GV AND SPECIAL REPAIR REPLACEMENT OF LT PANELS BER COOLING APPLIANCES AND MISC ELECTRICAL INFRASTRUCTURE AT 26 ED PHASE I AND CERTAIN MAJOR REVENUE WORKS AT GV CAMP UNDER GE AF MARATHAHALLI
2021_MES_486381_1
8915/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) MARATHAHALLI
AS PER ENIT
10 documents required · 10 mandatory
₹500
GE (AF) MARATHAHALLI
₹86,000
Yes
5 Mar 2022
5 Nov 2021
9 Dec 2021
5 Nov 2021
3 Dec 2021
20 Nov 2021
Amount
Material and labour for earthing complete with galvanized steel earth plate electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to GI 32x6 strip through 40 mm GI pipe as earthing lead protection and 20mm GI pipe is connected water pouring funnel up to earth plate as earthing lead means of nuts, bolts, check nuts and washer of GI steel and connecting to testing point including provision of test point and all as shown in electrical plate No. 3 of SSR Pt I. The work is inclusive of necessary earth work and PCC chamber in type C-1 (1:2:4) with 8 CTD bar reinforcement both ways at 140 mm bents to centre complete all as specified and as directed (for lightening arrester) including name plate of size 150mmx250mmx2mm thick MS plate welded with supporting angle 20x20x4mm thick 900mm long and painted and marked on plate or yellow colour sticker stick on plate complete all as specified and necessary earth work and PCC work complete. 1. EARTH PIT NO : ________________ 2.DATE OF MEASUREMENT : _________________ 3. NEXT DUE DATE : _________________ 4.STANDARD VALUE : _______________ 5. VALUE OBTAINED :_______________ Note:- GI earth strip beyond 7.5M shall be measured and paid separately
Material and labour for earthing complete with galvanized steel earth plate electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to 4.0 mm GI wire through 15 mm GI pipe as earthing lead protection and 20mm GI pipe is connected water pouring funnel up to earth plate means of nuts, bolts, check nuts and washer of GI steel and connecting to testing point including provision of test point and all as shown in electrical plate No. 3 of SSR Pt- I. The work is inclusive of necessary earth work and PCC chamber in type C-1 (1:2:4) with 8 CTD bar reinforcement both ways at 140 mm bents to centre including name plate of size 150mmx250mmx2mm thick MS plate welded with supporting angle 20x20x4mm thick 900mm long and painted and marked on plate or yellow colour sticker stick on plate complete all as specified and necessary earth work and PCC work complete. 1. EARTH PIT NO : ________________ 2.DATE OF MEASUREMENT : _________________ 3. NEXT DUE DATE : _________________ 4.STANDARD VALUE : _______________ 5. VALUE OBTAINED :_______________ Note:- GI earth strip beyond 7.5M shall be measured and paid separately
Material and labour for earthing complete with galvanized steel earth plate electrode 600X600X6 mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to GI earth lead 25x4mm thick earth strip drawn through 40mm GI tube light grade by means of nuts, bolts, check nuts and washer of GI steel and connecting to testing point including provision of test point and all as shown in electrical plate No. 3 of SSR Pt -I. The work is inclusive of necessary earth work and PCC chamber in type C-1 (1:2:4) with 8 CTD bar reinforcement both ways at 140 mm bents to centre including testing complete all as specified and as directed including name plate of size 150mmx250mmx2mm thick MS plate welded with supporting angle 20x20x4mm thick 900mm long and painted and marked on plate or yellow colour sticker stick on plate complete all as specified and necessary earth work and PCC work complete. 1. EARTH PIT NO : ________________ 2.DATE OF MEASUREMENT : _________________ 3. NEXT DUE DATE : _________________ 4.STANDARD VALUE : _______________ 5. VALUE OBTAINED :_______________
Material and Labour for Maintenance free Earthing, each pit consisting of copper coated steel rod of size 17.2mm dia 3 mtrs long 250 Microns molecularly bonded, joined with connecting clamps filled with maintenance free earth enhancing compounds Curec+ 6 kgs & Curecon 10 kgs, compounds strictly be a Eco friendly and must comply to IEEE 80:2000 clause 14.5 (d), IEEE 80:2000 clause 14.5 (b) and this compound should be Electrically & Thermally conductive, must be tested for Long term in CPRI for at least 2 year to display its stability & compound must be ISO certified and the earth pit should be closed with high density polymer HDPE inspection pit of 308 X 308 X 214 mm depth Complete all as specified and as directed including name plate of size 150mmx250mmx2mm thick MS plate welded with supporting angle 20x20x4mm thick 900mm long and painted and marked on plate or yellow colour sticker stick on plate complete all as specified and necessary earth work and PCC work complete. 1. EARTH PIT NO : ________________ 2.DATE OF MEASUREMENT : _________________ 3. NEXT DUE DATE : _________________ 4.STANDARD VALUE : _______________ 5. VALUE OBTAINED :_______________ Note: (i)Earth pit is required to be identified by the specific marker, colour codes (a) Maint free earthing pits- Red colour and write proper earthing details all as directed. (ii) The ring main earth resistance value shall be 1.0 Ohms. (iii) Rate deemed to be inclusive of one PCC inspection chamber of size 30cm x 30 cm x 30 cm depth and CI cover placed on main pit. (iv) 25 mm x 5 mm x300 mm copper bus bar - 1 No. (v) 25 mmx 25 mm x 150 mm bus bar - 1No (vi) Earth conductor beyond 7.5 Mts shall be measured and paid separately under relevant items of this schedule.
Material and labour for repairs to exisisting damaged earth chamber pits and chamber covers provision of new earth chamber pits covers made out of MS 5.0 mm thick chequered plate welded on angle iron frames 30 x 30 x 4 mm made out to size as per site requirement single door type with hinges and locking arrangement duly painted with 2 coat of synthetic enamel black paint over a coat of red oxide primer all as specified and as directed. Note:-Earth work ,brick work, removing u/s chamber cover, replacing rusted bolts and nuts complete all as specified.
Material and labour for repairs to exisisting earth chamber covers provision of new earth chamber cover made out of PCC chamber type C-1 (1:2:4) with 8 CTD bar reinforcement both ways at 140 mm bents to centre inclusive of necessary earth work, bricks work and replace rusted bolts and nuts testing complete all specified and as directed.
Supply and fixing earth strip in exisisting earth strips and provision addition earth strips of size 25x4 mm thick GI strip where ever required. incl porceline insulator spacer for every one meter with saddles and fixing screws etc. for roof conductor sand down conductors above ground complete all specified and as directed.
Supply and fixing Air termination single pointed Aluminium rod 12 mm dia 300 mm long complete all specified and as directed.
Supply and fixing earth strip in exisisting earth strips and provision addition earth strips of size 32 x 6 mm thick GI strip where ever required incl porceline spacer for every one meter with saddles and fixing screws etc. for roof conductor sand down conductors above ground complete all specified and as directed.
Material and labour for conventional earth pits replacing of old rusted (copper) bolts and nuts,washers replacing with new where ever required complete all specified and as directed.
Supply and fixing test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos of 8mm dia 25mm long hex. head screw complete all specified and as directed.
Supply and fixing earth name plate of size 150 mm x 250 mm 2 mm thick MS plate welded with supporting angle 20 x 20 mm 900mm long and painted and marked on plate or yellow colour sticker stick on plate complete all as speciied. a) Earth Pit No...... b) Earth resistance value.... c) Date on tested..... d) Due date next test.....
Supply, install,testing & commissioning LT panel board, factory made cubical totally enclosed Out door type, CPRI approved, IP-42, fabricated out of 3 mm thick CRCA sheet with angle iron base frame made of 50x50x6 mm thick angle iron 1 mtr long with PCC 1:4:8 type D2 at legs operated front side and rear side cover incl provision of cable glands of suitable sizes for incoming/outgoing cables, two coats of synthetic enamell paint over a coat of red oxide, inside and outside, Aluminium bus bar of rating 400 Amps for phase and half for neutral, mounted on epoxy insulator in parallel, covered with super quality PVC insulator tube of red, yellow, blue and black, pre-wired with suitable size of PVC insulated 1100 volts FR HR grade copper conductor, single core, multi stranded, comprising of the following (Near HQ 26 ED, MT Sec) (a) MCCB 200 amps 3 pole, 36 KA, 415 V-01 Bno (incoming) (b) Switch connector fuse unit -200 amps type FNX range 125-250 A-01 No (incoming) (c) MCCB 100 amps, Adjustable type 3 pole, 36 KA, 415 V - 04 No (Out going) (d) MCCB 63 amps, Adjustable type 3 Pole, 36 KA, 415V -02 No (Out going) (e) Digital Panel meter, VAF+PF meter 3ph class 1-5A (f) Neutral link (g) Push button -ON/OF : 3 set (h) RYB indicators -01 set (i) Bus bar 200 Amp 4 way assembly-01 nos (j) Stud terminal 4 pole (k) Rotary switch for 3 phase RYB -01 No (l) CT and PT coil for suitable - 01 No
2 Supply, install, testing & commissioning LT panel board, factory made cubical totally enclosed Out door type, CPRI approved, IP-42, fabricated out of 3 mm thick CRCA sheet with angle iron base frame made of 50 x50x6 mm thick angle iron 1 mtr long with PCC 1:4:8 type D2 at legs operated front side and rear side cover incl provision of cable glands of suitable sizes for incoming/outgoing cables, two coats of synthetic enamell paint over a coat of red oxide, inside and outside, Aluminium bus bar of rating 400 Amps for phase and half for neutral, mounted on epoxy insulator in parallel, covered with super quality PVC insulator tube of red, yellow, blue and black, pre-wired with suitable size of PVC insulated 1100 volts FR HR grade copper conductor, single core, multi stranded, comprising of the following (Near P/H, HQ 26 ED) (a) MCCB 200 amps 3 pole, 36 KA, 415 V-01 No (incoming) (b) Switch connector fuse unit -250 amps type FNX range 125-250 A-01 No (incoming) (c) MCCB 100 amps, Adjustable type 3 pole, 36 KA, 415 V - 05 No (Out going) (d) MCCB 63 amps, Adjustable type 3 Pole, 36 KA, 415V -01 No (Out going) (e) Digital Panel meter, VAF+PF meter 3ph class 1-5A (f) Push button-ON/OF : 3 set (g) RYB indicators - 01 set (h) Bus Bar 200 Amps 4 Way, Assembly-01 no (j) Stud terminal 4pole (k) Rotary switch for 3 phase RYB -01 No (l) CT and PT coil for suitable - 01 no
Supply, install, testing & commissioning LT panel board, factory made cubiclal totally enclosed Out door type, CPRI approved, IP-42, fabricated out of 3 mm thick CRCA sheet with angle iron base frame made of 50 x50x6 mm thick angle iron 1 mtr long with PCC 1:4:8 type D2 at legs operated front side and rear side cover incl provision of cable glands of suitable sizes for incoming/outgoing cables, two coats of synthetic enamel paint over a coat of red oxide, inside and outside, Aluminium bus bar of rating 400 Amps for phase and half for neutral, mounted on epoxy insulator in parallel, covered with super quality PVC insulator tube of red, yellow, blue and black, pre-wired with suitable size of PVC insulated 1100 volts FR HR grade copper conductor, single core, multi stranded, comprising of the following (Affnet) (a) Switch connector fuse unit -200 amps type FNX range 125-250 A-01 No (incoming) (b) MCCB 200 amps, Adjustable type 3 pole, 36 KA, 415 V - 01 No (incoming) (c) MCCB 100 amps, Adjustable type 3 pole, 36 KA, 415 V - 03 No (Out going) (d) MCCB 63 amps, Adjustable type 3 Pole, 36 KA, 415V -01 No (Out going) (e) Digital Panel meter, VAF+PF meter 3ph class 1-5A (f) Push button-ON/OF : 3 set (g) RYB indicators - 01 set (h) Bus Bar 200 Amps 4 Way, Assembly-01 nos (j) Stud terminal 4pole (k) Rotary switch for 3 phase RYB -01 No (l) CT and PT coil for suitable - 01 no
Supply, install, testing & commissioning LT panel board, factory made cubical totally enclosed Out door type, CPRI approved, IP-42, fabricated out of 3 mm thick CRCA sheet with angle iron base frame made of 50 x50x6 mm thick angle iron 1 mtr long with PCC 1:4:8 type D2 at legs operated front side and rear side cover incl provision of cable glands of suitable sizes for incoming/outgoing cables, two coats of synthetic enamell paint over a coat of red oxide, inside and outside, Aluminium bus bar of rating 400 Amps for phase and half for neutral, mounted on epoxy insulator in parallel, covered with super quality PVC insulator tube of red, yellow, blue and black, pre-wired with suitable size of PVC insulated 1100 volts FR HR grade copper conductor, single core, multi stranded, comprising of the following (TRF yard) (a) Switch connector fuse unit -250 amps type FNX range 125-250 A-01 No (incoming) (b) MCCB 400 amps, Adjustable type 3 pole, 36 KA, 415 V - 01 No (Out going) (c) Digital Panel meter, VAF+PF meter 3ph class 1-5A (d) Push button-ON/OF : 3 set (e) RYB indicators - 01 set (f) Bus Bar 400 Amps 4 Way, Assembly-01 no (g) Stud terminal 4pole (h) Rotary switch for 3 phase RYB -01 No (j) CT and PT coil for suitable - 01 no
Supply, install, testing & commissioning LT panel board, factory made cubicle totally enclosed Out door type, CPRI approved, IP-42, fabricated out of 3 mm thick CRCA sheet with angle iron base frame made of 50 x50x6 mm thick angle iron 1 mtr long with PCC 1:4:8 type D2 at legs operated front side and rear side cover incl provision of cable glands of suitable sizes for incoming/outgoing cables, two coats of synthetic enamel paint over a coat of red oxide, inside and outside, Aluminium bus bar of rating 400 Amps for phase and half for neutral, mounted on epoxy insulator in parallel, covered with super quality PVC insulator tube of red, yellow, blue and black, pre-wired with suitable size of PVC insulated 1100 volts FR HR grade copper conductor, single core, multi stranded, comprising of the following (Near fire Hydrent) (a) Switch connector fuse unit -100 amps type FNX range 125-250 A-01 No (incoming) (b) MCCB 100 amps, Adjustable type 3 pole, 36 KA, 415 V - 01 No (Incoming) (c) MCCB 63 amps, Adjustable type 3 pole, 36 KA, 415 V - 03 No (Incoming) (d) MCB 40 amps adjustable type 36 KA-02 No (e) Automatic star delta starter 10-20 amps 415 vots 3 ph -01 No (Borewell) L&T (f) Digital panel meter, VAF+PF meter 3ph class 1-5A (g) Push button -ON/OF : 3 set (h) RYB indicators - 01 set (j) Bus Bar 100 Amps 4 Way. Assembly -01 no (k) Stud terminal 4pole (l) Rotary switch for 3 phase RYB-01 No (m) CT and PT coil for suitable -01 No
Taking down old MCCB and Supply and fixing MCCB, 3 pole 25 to 63 Amps rating, fixed thermal and magnetic setting, 25 KA breaking capacity, 415 V,50 Hz AC supply including making all connections complete all as specified and as directed.
Taking down old MCCB and Supply and fixing MCCB, 4 pole 63 Amps rating, fixed thermal and magnetic setting, 25 KA breaking capacity, 415 V, 50 Hz AC supply including making all connections complete all as specified and as directed.
Taking down old MCCB and Supply and fixing MCCB, 3 pole 63 to 100 Amps rating, fixed thermal and magnetic setting, 25 KA breaking capacity, 415 V, 50 Hz AC supply including making all connections complete all as specified and as directed.
Taking down old MCCB and Supply and fixing MCCB, 4 pole 100 Amps rating, fixed thermal and magnetic setting, 25 KA breaking capacity, 415 V, 50 Hz AC supply including making all connections complete all as specified and as directed.
Taking down old MCCB and Supply and fixing MCCB, 3 pole 160 Amps rating, fixed thermal and magnetic setting, 36 KA breaking capacity, 415 V, 50 Hz AC supply including making all connections complete all as specified and a directed.
Taking down old MCCB and Supply and fixing MCCB, 3 pole 200 Amps rating, fixed thermal and magnetic setting, 36 KA breaking capacity, 415 V, 50 Hz AC supply including making all connections complete all as specified and as directed.
Taking down old MCCB and Supply and fixing MCCB, 3 pole 400 Amps rating, fixed thermal and magnetic setting, 36 KA breaking capacity, 415 V, 50 Hz AC supply including making all connections complete all as specified and as directed.
Taking down old changeover switch and Supply and fixing in replacement on load changeover switch 415 V, 4 pole, 63 Amps complete all as specified and as directed.
Taking down old on load change over switch and Supply and fixing in replacement on load changeover switch 415 V, 4 pole, 100 Amps complete all as specified and as directed.
Taking down old on load change over switch and S & F in replacement on load changeover switch 415 V, 4 pole, 200 Amps with sheet enclosure complete all as specified and as directed to be matched with existing type/size & to be fixed in the existing panel.
S&F in repair of LT Panel board indoor type/ outdoor type repair/replacement of rusted, damged door hinges, door handles front and back side , supporting legs 40x40x6mm MS angle and necessary cutting, welding, drilling where ever required at site and burnt out cables lugs by trimming of loose wires replacement of new cable lugs, rusted bolts & nuts cleaning, inside/outside of the panel. One coat of red oxide and two coat of enamel paint over on it including damaged pcc foundation repair work front/ back side of panel and pcc platform be provide complete all as specified and as directed
S&F in repair/replacement of Aluminium cables lugs silver coated upto 16 sqmm to 70 sqmm including necessary crimping tool complete all as specified and directed.
Material and labour for repair/replacement of Aluminium cables lugs silver coated upto 95 sqmm to 185 sqmm including necessary crimping with crimping tool complete all as specified and as directed.
Material and labour for cement concrete 1:3:6 type C1 using 20mm graded stone aggregate as in coping, bases of electric poles including necessary from work and finishing the exposed concrete surfaces of concrete even and fair complete all as specified and as directed.
Material and labour for cement concrete 1:2:4 type B-2 using 40mm graded stone aggregate as in mass concrate/foundation/ supporting (encasing) bases of electric poles including necessary from work and finishing the exposed concrete surfaces of concrete even and fair complete all as specified and as directed.
Material and labour for Cutting PCC/road 150mm thick for laying of LT UG cable and making good the disturbed surfaces with cement concrete 1:2:4 type B-1, using 20mm graded stone aggregate complete all as specified and directed.
Material and labour for G.I. tubing light grade of size 50mm bore for protection of cables to be laid under roads, crossings/culverts including taking down/up old unserviceable GI tubing complete all as specified and as directed.
Material and labour for G.I. tubing light grade of size 80mm bore for protection of cables to be laid under roads, crossings/culverts including taking down/up old unserviceable GI tubing complete all as specified and as directed.
Supply and fixing in repairs busbar panels for distribution system of cable looping optema series the panel of size 600x600x600mm double door with locking arrangement of 200 amps busbar supporting with insulator including panel supporting stand of hieght 600mm grounting in ground with pcc work 1:2:4 B-1 concrete and cables to connect with cable lugs, fixing bolts nuts and washers HSN code 8536 4way 63 amps capacity wall mounted complete all as specified and as directed.
Supply and fixing in repairs busbar panels for distribution system of cable looping optema series the panel of size 600x600x600mm double door with locking arrangement of 200 amps busbar supporting with insulator including panel supporting stand of hieght 600mm grouting in ground with pcc work 1:2:4 B-1 concrete and cables to connect with cable lugs, fixing bolts ,nuts and washers HSN code 8536 4way 100 amps capacity wall mounted complete all as specified and as directed.
Supply and fixing street light panel 6 KW contactor 32/TP and 40/TP MCB Analog time switch with battery back up of 24 hours, having current capacity 40A, 3Phase 240 volts with 1 changeover for controlling of security light fitting with proper connection and testing schedule operation complete all as specified and as directed.
Taking down old MCB TP and Supply and fixing MCB TP 25 to 63 Amps rating, 'C' series 10 KA breaking capacity, 415 V, 50 Hz AC supply including making all connections complete all as specified complete all as specified and as directed.
Supply & fixing and connecting up complete MCCB DB VTPN 4 way (Vertical), double door, 415 V, AC, 50 Hz, IP-43 protection conforming to IS-13032 universal mounting with copper bus bar neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides complete all as specified and as directed.
Taking down old MCB SP and Supply and fixing MCB SP 6-32 Amps rating 'C' series 10 KA breaking capacity 240 V 50 Hz AC supply including making all connections complete all as specified and as directed.
Taking down old MCB SPN and Supply and fixing MCB SPN 6-32 Amps rating, 'C' series 10 KA breaking capacity 240 V, 50 Hz AC supply including making all connections complete all as specified complete all as specified and as directed.
Taking down old MCB DB and Supply and fixing MCB DB 32 Amps rating, 'C' series 10 KA breaking capacity 240 V 50 Hz AC supply including making all connections complete all as specified and as directed.
Taking down old MCB TPN and Supply and fixing MCB TPN 63 Amps rating, 'C' series 10 KA breaking capacity 415 V, 50 Hz AC supply including making all connections complete all as specified and as directed.
Taking down old MCB TPN and Supply and fixing MCB TPN 40 Amps rating, 'C' series 10 KA breaking capacity 415 V 50 Hz, AC supply including making all connections complete all as specified and as directed.
Supply and fixing in repairs DOL starter suitable for 7.5 Hp pumpsets complete all as specified and as directed.
Supply and fixing in repairs fully Automatic star delta startersuitable for 20 Hp pumpsets complete all as specified and as directed.
Supply and fix steel tubular swaged poles type 410 SP-31 (9 meter long) complete with CI base plate final taper plug bolts nuts & screws as specified including foundation and coping complete all as specified and as directed. Note :- Excavation and foundation will be paid separately of relevent items.
Supply and fix LED street light 60 watt AC 230 Volts complete 230 V AC outdoor type with high pressure diecast aluminum hosing and heat resistant complete with driver, lamp bracket with fixing accessories impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed.
Supply and fixing moulded PVC /SMC Junction boxes out door type, weather proof of size 240 x 130 x 95 mm to be fixed at the bottom of street light pole 3 ph RYB busbar 200 Amps capacity complete with suitable clamp, nutS, bolts, washers and suitable glands to accommodate 01 No MCB SP 5 Amps 10 KA, with suitable connectors for incoming and outgoing connections complete all as specified and directed .
Material and labour for pole wiring drawn through 20 mm PVC conduit rigid pipe including copper wiring multistranded two runs of 1.5 sqmm and one run of 1.5 sqmm earth wire as earth dolly wiring sintex box to light fitting and internal connections for light fittings complete all as specified and as directed.
Supply and fixing in repairs/ replacement old water level indicator mechanical type and provision of new digital water level indicator device operating on single phase supply direct display in 6" size (letter display) digital system in meter / centimeter of water level of over head tank ensuring alarm while water fall or rise over pre-determined limit with the following description complete all as specified and directied by Engr-in-charge. (a) The entire unit must operate through a compact electronic circuit which must reliable operation at 230 volts+_10% at 50 Hz with reliable in display and alarm at low and high level of over head tank. (b) One circuit must be housed in high impact polystryrene moulded box with nylon moulded connection strips. The level system must resistance transducer (c) The whole unit system electronically control and the upper level and lower level indication must be in two part ie sensor and display board Each part must be fitted in MS CRCA sheet box separately. One must be installed at OHT 26 ED and Second at pump house to UG sump and OHT tank at MP Camp the inter connections with multi core copper conductor with locking arrangement. Note :PVC insulated multi core copper conductor cable 0.5 sqmm frm water level indicator to over head tank, Sensor shall be connected with pvc insulated copper conductor cable so as to indicate the water level empty 25%, 50%, 75%, & 100% tank full including testing Commencining with smooth functioning.
S&F in repairs single phase preventer for monoblock and submersible pumps over load, earth fault Model MPR 200nx.
S & F Mild Steel work as in framed work such as Grills, Gratings, Ladders etc with ends of bars shouldered and/or riveted or forged into spikes framed Guard Bars, Barred Iron Doors, Ladders, framed Balusters, Walk Ways, Railings, frame wok of Water Tanks and similar work confirming to Fe-290, Grade E-165, including preparation of new steel surfaces n.exc. 10cm width or girth and applying two coat of synthetic enamel paint over one coat of red oxide zinc chrome primer complete all as specified and as directed.
Supply laying and testing UG cable 10 sqmmx 4 core XLPE Insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes including taking down. Note :- Rate of UG cable includes earth work, sand cushioning, brick or PCC covering medium grade GI tubing where necessary testing etc complete all as specified and as directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep for laying of cables etc, getting out and forming bottom surface to required gradient complete all as specified and directed.
Excavation in trenches in soft/loose soil exceeding 1.5 meter wide and not exceeding 3.0 meter deep for laying of cables etc, getting out and forming bottom surface to requied gradient complete all as specified and directed.
Returning filling including spreading levelling watering and well ramming to excavated soil in layers not exc 25 cm thick complete all as specified and as directed
Removing excavated material not exc 50m and depositing where directed at a level not exc 1.5m above the starting point in soils complete all as specified and as directed.
Material and labour for Sand cushionng to cable with a layer of sand before and after laying the cable complete all as specified and as directed. Note : Sand shall be measured after punned down.
Material and labour for Brick protection cover on cable with sub class 'B' bricks across in trenches laid dry and flat adjacent to each other complete all as specified and as directed
Supply and fixing of sign board, box type fabricated with MS sheet 2mm thick for outer cover and front display side 3 mm thick hylam white colour sheet and blue colour letters on it for installations pump house/power house/STP plant/Fire Hydrant plant requirement including inside board LED Tube light arrangement for display Letters height 6" and board supporting by 50mm dia GI pipe meadium grade of size (0.75 x 1.5 m) and height 1.75 mtr from floor level incl errection commissioning testing complete. Note :- PCC 1:2:4 class 'B' concrete using 20 mm aggregate for supporting pipes.
M&L for point wiring complete with 1.5 Sqmm single core FRLS PVC insulated unsheathed cable 1100 volts grade multi stranded with copper conductor conforming to IS 694 drtawn through and incl non-metalic rigid PVC conduit incl accessories run surface on walls/ceiling incl MS terminal boxes fabricated with 1.6 mm thick MS sheet concealed where feasable on walls with modular cover plate with frame for housing the moduler swithes,socket, regulator incl provision of 1.5 Sqmm FRLS PVC insulated single core multi stranded copper conductor cable as earth continuity conductor and connecting to common earth dolly, complete all as specified and as directed. (a) One llight point controlled by one switch.
All as per item no 63 above, but, One 5A 2pin/3pin switch socket out let multipurpose on independent Board.
All as per item No.63 above, but , wiring complete with 2.5 Sqmm for 5 pin 5/15A socket on point independent board with 2.5 sqmm copper for earth continuity complete all as specified and as directed.
S&F Modular Socket,6 Amps-2/3 pin combined 2 Module complete all as specified and as directed.
S&F Modular Switch 1 way 16 Amps 1 Module complete all as specified and as directed.
S&F Modular Socket, 6A/16A,2 Module complete all as specified and as directed.
S&F Modular Switch 1 way 6 Amps 1 Module complete all as specified and as directed.
Fixing only in repair Modular type Fan step regulator, 2 module/1 module complete all as specified and as directed.
M&L wall mounting fan 400mm sweep,230V,AC complete all as specified and as directed.
Supply and fixing 15 Amp top plug 230 volts AC complete all as specified and as directed.
Supply and fixing 5 Amp top plug 230 volts AC complete all as specified and as directed.
Supply and Fixing in repairs LED Tube light fitting 1x20W,220V CRCA housing with Pc diffuser box type with drive,holder including LED tube light connecting up with 3 core 0.5 sqmm copper wire between celing rose and fitting terminal all as specified and as directed.
S & F in repair PVC ceiling rose two to three terminals complete all as specified and as directed.
S & F in repair Angle holder PVC/polycarbonate type complete all as specified and as directed.
S&F in repair step type electronic fan regulator -2 module complete all as specified and as directed.
S&F MS terminal boxes on walls with modular cover plate with frame for housing the moduler switches regulator up to 5 to 8 Nos complete all as specified and as directed.
Supply and fixing in repairs MCB DB SPN 4way, Double door,240V, AC,50HZ, with 200 Amp rated bus bar complete all as specified and as directed.
Supply and fixing in repairs MCB SP 5 to 32 Amps rating, 10 KA 'C' curve 240V, 50 Hz AC complete all as specified and as directed.
Supply and fixing in repairs MCB SPN 32 Amps rating, 10 KA 'C' curve 240V, 50 Hz AC complete all as specified and as directed.
Material and labour for sub main wiring 1100 volts grade PVC insulated FRLS multistranded copper conductors, two runs of single core 4 Sqmm along with one run 4 Sqmm PVC insulated single core FRLS multistranded copper conductor cable as earth continuity conductor along with one run of PVC medium grade coundit complete all as specified and as directed.
Supply and install 1.5 Ton 5 Star split inverter AC Indoor /Out door unit complete with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality including writing MES No with unit Name on equipment using of paint or stencil with paint complete all as specified and directed. Note :- Dismantiling and Taking down care fully with out damaging exisiting system and handed over to MES store.
Supply and install 2 Ton 5 star split inverter AC indoor/outdoor unit complete with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality including wirting MES No with unit Name on equipment using of paint or stencil with paint complete all as specified and directed. Note : Dismantiling and Taking down care fully with out damaging exisiting system and handed over to MES store.
Supply and fix Ductable Air conditioner electric driven single phase of capacity of 2.0 TR , 5 star rated complete including aligning evaporator coil and canvas joint to ductable unit to exisisting duct and indoor . Note : - Dismantiling and Taking down care fully with out damaging existing system and handed over to MES store.
Supply and fix single pole and neutral sheet metal enclosure wit a two pin and earth plug and socket complete with one 20 Amps SPN MCB complete all as specified and directed
Supply and fix suitable size copper refrigerant pipe of 1.5 Ton/2Ton split AC including necessary insulation and thermo rexine tape etc complete all as specified
Supply and fix rigid non-metallic PVC fixible pipe of dia 20mm for drain out the water from indoor unit and fixing accessories such as saddles, pipe hook etc complete all as specified and directed.
Supply and mounting on wall /sunshade of outdoor unit stand for split air conditioner including civil work complete all as specified and directed.
Taking down ceiling fan any size , any make fixed/ hanged in different location in MP camp ,dismantling the fan complete cleaning and re assembling the same including replacing Anti suicide down rods, split pins flexible copper cable of size 23/.0078 twin core 70 cm long and re fixing the ceiling fan on the same location in orginal position testing and commissioning of fan for smooth running as per entire satisfaction complete all as specified and directed.
Supply and fix 10" Gold life Smart MS down rod (Anti suicide fan rod) white colour ceiling fan of any size complete all as specified and directed.
Vishwas Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .