Chief Engineer and DCE( CED, PD and EP)
Nuclear Fuel Complex, Hyderabad
Preventive Maintenance of Ventilation system at NFC-K
2026_NFC_905573_1
NFC/EP/E 689/2026-27
Open Tender
Machineries/ Mechanical Engg Items
Works
365 days
Rawatbhata
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹2.9 L
13 May 2026
20 Apr 2026
25 May 2026
20 Apr 2026
23 May 2026
20 Apr 2026
20 Apr 2026 - 2 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Preventive Maintenance(PM) of Centrifugal Blowers : Frequency : Quarterly (once in 3 months) PM works involves tbe following: a) Ensure Drive V-Belts tension (if reqd, adjust motor) b) Replace damaged V-belts c) Ensure coupling in good condition (if reqd, replace) d) Grease the Brearings e) Ensure Flexible joints in good condition (if reqd, replace) f) Ensure Belt guard in good position (if reqd, reset) g) Grease Damper bearings h) Ensure all fasteners are in complete fastened conditon (if reqd, fasten) i) Ensure the actuator connections in order (if reqd, refix) j) Report, if any abnormality in functioning Note : PM shall be performed for installed 184 qty per quater. | |||||
| 1.1 | Blowers upto 55 KW capacity | 480 | Nos | - | - |
| 1.2 | Blowers from 56 KW to 350 KW capacity | 256 | Nos | - | - |
| 2Preventive Maintenance(PM) of Horizontal coupled Centrifugal Pumps : Frequency : Quarterly (once in 3 months) PM works involves tbe following: a) Makeup oil in bearing chamber b) Ensure coupling in good condition (if reqd, replace) c) Ensure coupling guard in position (if reqd, adjust & fasten) d) Ensure NO water leakage (if reqd, rectify) e) Remove Strainer clean & re-fit f) Ensure all Nut Bolts are fastened (if reqd, fasten) g) Drain hydrocyclone till sediment is bleeded out h) Report if any abnormality is observed Note : PM shall be performed for installed 32 qty per quater. | |||||
| 2.1 | Pumps upto 20 KW capacity | 108 | Nos | - | - |
| 2.2 | Pumps from 21 KW to 60 KW capacity | 20 | Nos | - | - |
| 3 | Preventive Maintenance(PM) of Monobloc Centrifugal Pumps :
Frequency : Quarterly (once in 3 months)
PM works involves tbe following:
a) Replace gland packing
b) Ensure guard in position (if reqd, adjust & fasten)
c) Ensure NO water leakage (if reqd, rectify)
d) Remove Strainer clean & re-fit
e) Ensure all Nut Bolts are fastened (if reqd, fasten)
f) Report if any abnormality is observed
Note : PM shall be performed for installed 26 qty per quater. | 104 | Nos | - | - |
| 4 | Preventive Maintenance(PM) of Fresh Air Filters Banks:
Frequency : Quarterly (once in 3 months)
PM works involves tbe following:
a) Clean the filters using pressure pump (Pump in contractor"s scope)
b) Ensure Filters in good condition (if required, Replace)
c) Ensure the WASS/Pressurization room is clean and dry
d) Remove Strainer clean & re-fit
e) Report if any abnormality is observed
Note : PM shall be performed for installed 38 SET per quater. | 152 | SET | - | - |
| 5Preventive Maintenance(PM) of Air Washer Tanks : Frequency : Once in a year or as required PM works involves tbe following: a) Drain Water & clean the tank b) Ensure Float valve in good working condition c) Ensure spray nozzles in position & a good water spray ( if required, replace/ re-position nozzles) d) Remove Strainer clean & re-fit e) Ensure Pump discharge pressure >7 psi f) Ensure pressure guage in good condition ( if reqd, replace) f) Report if any abnormality is observed Note : PM shall be performed for installed 16 qty per year. | |||||
| 5.1 | Filter Bank up 50 filters with tank floor size less than 25 SqM. | 8 | Nos | - | - |
stage.html
html • 0.02 MB
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.24 MB
Biddoc3GCCSCC.pdf
Tender Documents • 1.14 MB
BidDoc2PreambletoNIT.pdf
Tender Documents • 0.76 MB
BOQ_951844.xls
BOQ • 0.32 MB
BidDoc5IPR_Untertaking.pdf
Tender Documents • 0.15 MB
BIdDoc6DTSPMC.pdf
Tender Documents • 0.82 MB
BidDoc7AERB_control_of_works.pdf
Tender Documents • 0.27 MB
Corrigendum2689.pdf
PDF • 1.25 MB
Corrigendum689.pdf
PDF • 1.06 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .