| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.8 LAccepted-Finance 4 1 SECTOR B INDUSTRIAL AREA GOVINDPURA BHOPAL BHOPAL MADHYA PRADESH 462023 | BHOPAL | MADHYA PRADESH | 462023 | L1 | Accepted-Finance L1 | |
| 2 | L2Accepted-Finance | L2 | Accepted-Finance L2 | |
| 3 | L3Rejected-Finance A 246 2ND FLOOR ATLANTIS K 10 TOWER A SARABHAI MAIN ROAD ALKAPURI VADODARA GUJARAT 390007 INDIA UDYAM GJ 24 0003367 24AAACC7616D1Z4 R M MII STATUS AS VERIFIED | VADODARA | GUJARAT | 390007 | L3 | Rejected-Finance L3 | |
| 4 | Rejected-Technical | - | Rejected-Technical Disqualified due to nonsubmission of documents as per Annexure III, IV, IX and XI. | |
| 5 | Rejected-Technical 301 3RD FLOOR VAISHNAVI KRISHNA GRANDEUR OPP ISPAT BHAVAN DISTILERY ROAD HYDERBASTI 500003 SECUNDERABAD HYDERABAD TELANGANA 500003 | HYDERABAD | TELANGANA | 500003 | - | Rejected-Technical Disqualified due to nonsubmission of documents as per Annexure III, IV, and IX. |
| Sl No | Description | Qty | Unit | NIDHI ENGINEERING INDUSTRIES | ARUN ENTERPRISES | COMP AIR TREATMENT SYSTEM PVT LTD |
|---|---|---|---|---|---|---|
| 1.00Tube bundle of Air compressor Model: TBTDPM Make: Kirloskar | ||||||
| 1.01 | Tube bundle for inter cooler
• Number of Tube : 64
• MOC of tubes : Cu (BS-2871) in TA condition
• MOC of baffle plates : SA 285
• Total length of cooler : 3145 mm
• Dimensions of tube : OD 15mm x 1.35mm thick
• C to C distance : 2460 mm Integrated fined type x 2800 L
• Number of Spacers : 72
• Position : Horizontal
• Number of tie rods : 04
• Number of baffle plates: 14
• Tube plates(front & rear): Steel (IS-2026)
• Baffles : SS-304
Parameters:-
• Tube side design pressure : 6.5 kg/cm2
• Tube side hydraulic test Pr. : 10.25 kg/cm2
• Shell side design pr. : 2.3 kg/cm2
• Shell side hydraulic test pr. : 3.5 kg/cm2
Performance: 17.1 M3/min free air is to be cooled from 162 oC to 45 oC
by 100 LPM clarified water its temp. rise from 6 to 12 oC | 3 | Nos. | 5,50,800 ₹6,49,944 Lowest | 7,44,000 ₹8,77,920 | 6,48,058.32 ₹7,64,708.82 |
| 1.02 | Tube bundle for after cooler
• Number of Tube : 48
• MOC of tubes : Cu (BS-2871) in TA condition
• Dimensions of tube : OD 15mm x 1.35mm thick integrated fine type 2170 L fine type 2170 L
• Tube plate(front & rear) : Steel (IS-2062)
• Number of spacers : 78
• Number of tie rods : 04
• Number of baffle plates : 14
• Total length of cooler : 2665 mm
• Position : Vertical
• Baffles : SS-304
Parameters:-
• Tube side design pressure : 6.5 kg/cm2
• Tube side hydraulic test Pr. : 10.25 kg/cm2
• Shell side design pr. : 9.6 kg/cm2
• Shell side hydraulic test pr. : 14.5 kg/cm2
Performance: 18 M3/min free air is to be cooled from 162 oC to 45 oC by 140 LPM clarified water its temp. rise from 6 to 12 oC | 3 | Nos. | 3,21,300 ₹3,79,134 Lowest | 4,98,000 ₹5,87,640 | 5,25,773.99 ₹6,20,413.3 |
Tender Value
₹7.5 L
EMD Value
₹15,000
Closing Date
11 Aug 2025, 3:00 pmClosed
SE P and W
SE P and W, Office of ED GEN, SGTPS, MPPGCL, BRS
Procurement of Tube bundles for inter cooler and after coolers of Kirloskar make Air Compressor Model TB-TD-PM for TMD-I unit 1 and 2 , SGTPS, MPPGCL, Birsinghpur.
2025_MPPGC_400731_1
400731
Open Tender
Miscellaneous Goods
Item Wise
90 days
SGTPS, MPPGCL, Birsinghpur
As per NIT
15 documents required · 15 mandatory
₹500
Yes
₹15,000
Yes
17 Mar 2026
8 Jul 2025
13 Aug 2025
8 Jul 2025
11 Aug 2025
8 Jul 2025
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .