Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.6 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹24.9 L+₹3.1 L (13.9%)Rejected-AOC 1 128 A SECOND FLOOR MOHAMMADPUR NEAR BHIKAJCAMA PLACE NEW DELHI 110066 | NEW DELHI | NEW DELHI | DELHI | 110066 | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | Rejected-Technical | - | Rejected-Technical Not recommended being not enlisted in category C (ii) |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
18 Jan 2022, 6:00 pmClosed
CWE Jammu
HQ CWE Jammu Pin 900172 C/o 56 APO
REPAIR MAINT OF MECHANICAL LAUNDARY OIL FIRE INCINERATOR FIRE FIGHTING SYSTEM AND COMPREHENSIVE ANNUAL MAINT OF LIFT UNDER GE SATWARI
2021_MES_496229_1
CWE/JP-64/2021-22
Open Tender
Support/Maintenance Service
Item Rate
365 days
AOR G E Satwari
Class E, cat b (i) and c (ii)
9 documents required · 9 mandatory
₹500
G E Satwari
₹50,000
Yes
23 Mar 2022
20 Dec 2021
25 Jan 2022
20 Dec 2021
18 Jan 2022
4 Jan 2022
Amount
Supply and Fix in replacement of hydrant valve double headed all as specified and directed.
Supply and Fix in replacement of RRL hose pipe -A 15 mtr long 63 mm dia all as specified and directed.
Supply and Fix in replacement of Butter fly valve of size 150 mm all as specified and directed.
Supply and Fix in replacement of Butter fly valve of size 100 mm all as specified and directed.
Supply and Fix in replacement of Butter fly valve of size 80 mm all as specified and directed.
Hose box made of 18 gauge MS sheet 800mm X 600mm X 250mm with double door with 4 mm thick glass and door frame made of 16 gauge MS sheet painted fire red oxide and brilliant white inside yard all as specified and directed.
Material and labour for replacenent of online pressure pump of cap 0.5 HP including its necessary connection in existing water pipe line all as specifed and directed with fwg specifiecation:- Single-phase Water Pump In-built Thermal Over Load Protector Power Rating: 0.37 kW Power Supply: 180-240V Motor Power: 0.5 HP
Material and labour for replacement of branch pipe gun metal 63 mm instantaneous inlet, made threaded outlet, with 15 mm bore nozzle long all as specified and directed.
Material and labour for carrying out annual maintenance contract for one year of UV based water purifier make Aqua guard classic model by replacement of pre filter candle sleek and carbon block twice in a year and servicing twice after regular intervals, including the replacement of circuit board and any other part as required at site to make the Aqua guard functional throughout the year. Note: Servicing and replacement of parts will be carried out by authorised service representative of Eureka Forbes.
Strip opening of the Primary Chamber and removal of the ashes or any dust material from inside with restoring of all calicum silicate insulation and welding of steel plates and its bracing and stiffening , complete repair to the refractory lining of the chamber and providing of ceramic wool for flanges and expansion joints, settings of dismantled insulation bricks and providing heat resistant aluminium painting complete all as specified and directed.
Strip opening of Secondary Chamber and removal of the ashes or any dust material from inside with restoring of all calicum silicate insulation and welding of complete steel plates and its bracing and stiffening , complete repair to the refractory lining of the chamber and providing of ceramic wool for flanges and expansion joints, settings of dismantled insulation bricks and providing heat resistant aluminium painting complete all as specified and directed.
Material and labour for repair to chamber of oil fired incineretor made of MS plate of adequate thickness by replacement of rusted MS plate welding with existing plate incl painting and matching with existing colour externally all as specified and directed.
Material and labour for complete servicing of air fan blower with fan Motor-02 Nos of capacity 1.0 KW
Supply and fixing in replacement of V Belt No B-102.
Supply and fixing in replacement of V Belt No B-64.
Supply and fix in repair of Burner for Oil fired incinerator by replacement of fwg accessories complete all as specified and directed.
Sequence controller (LMO24)
Ignition Transformer (FIDA)
Ignition Electrode
Ignition Cable
Photocell (SEIMENS)
Fuel Pump
Thermocouple (1 to 1200 Deg) Inconel
Material and Labour for repair of washing machine cap 15 kgs by replacement of Door Gas kit, Glen dori, belt etc all as specified and directed.
Supply and fix in repair of steam boiler control panel board by replacement of its accessories like: safety switches, control cable, fire alarm, steam pressure switch, Digital temperature Display, lit switches with high quality lamps, atmospheric economiser, burner safty valve, sensor complete all as specified and directed.
Material and Labour for repair and servicing of Washing Machine of cap 60 kgs front loading incl replacement of defective parts (if needed) all as specified and directed. Note: Cost for replacement of defective parts has been measured and paid under relevent items.
3 " Motor pulley
16" motor bush pulley
Bearing-22210
Bearing slip-22310
Bearing-22215
Bearing slip-22315
Glen dori, oil seal
Door gaskit
Inner basket repair
Material and Labour for repair and servicing of of hydro 25kgs capacity incl replacement of defective parts (if needed) all as specified and directed. Note: Cost for replacement of defective parts has been measured and paid under relevent items.
Rubber Buffer
Hydro spring
Hydro Bolt set SS,
Limit switch
Push botton with NC 0-15 Min timer
Brake plate
1 KVA Transformer
Delay off timer
SS Lock
Supply and fix in replacement of Sealed lead acid battery of capacity 12V 7Ah for lift (15 person) and control panel of fire fighting complete all as specified and directed.
Supply and fix in replacement of solar Li-ion battery 14.8V/5.2 AH with BMS system for solar street light complete all as specified and directed.
Material and labour for replacement of door handle with lock suitable for washing machine 50 Kg all as specified and directed.
Supply and fixing in replacement of Tension Spring as per existing suitable for hydro extractor all as specified and directed.
Material and labour for replacement of DC brake complete suitable for hydro extractor of existing make all as specified and directed.
Material and Labour for repair of UPS of capacity 10-20 KVA by repair/ replacement of insulated gate bipolar transistor (IGBT), DC capacitor, SCR module, logic board, diaod transisters, protection board or DC converter circuit board 3 phase of suitable rating complete all as specified and directed.
Material and Labour for repair of UPS of capacity 2-5 KVA by repair/ replacement of insulated gate bipolar transistor (IGBT), DC capacitor, SCR module, logic board, diaod transisters, protection board or DC converter circuit board 3 phase of suitable rating complete all as specified and directed.
Material and labour for pressure testing of cylinder and refilling of fire extinguisher CO2 type of capacity 6.5 Kg alongwith replacement of nozzle and hose as existing all as specified.
Material and labour for pressure testing of cylinder and refilling of fire extinguisher CO2 type of capacity 4.5 Kgs alongwith replacement of nozzle and hose as existing all as specified.
Material and labour for pressure testing of cylinder and refilling of fire extinguisher CO2 type of capacity 9 Kg alongwith replacement of nozzle and hose as existing all as specified.
Material and labour for pressure testing of cylinder and refilling of fire extinguisher ABC type of capacity 5 Kg alongwith replacement of nozzle and hose as existing all as specified.
Supply & fix in replacement of pressure release valve of size 25 mm dia as existing all as specified.
Supply & fix in replacement of detectors complying with and type certified to EN-45 addressebale type multisensor detectors with heat and smoke combination photoelectric/optical with base with self built intelligenceas per IS-11360 all as specified and directed.
Supply & fix in replacement of fire alarm sounders/ Sirens Electronic type horizontal single stage continious normal opeartion for atleast 50 minutes with sound level 65 DB to 120 DB measured al 1.5 mtr with sound output variation of +5 DB of range 500 mtr all as specified and directed.
Comprehensive maintenance including preventive and periodical maintenance of installed lift -06 Nos of capacity 15 passengers (1020 kgs) with speed of 0.40 m/s to 0.5 m/s in reliable, safe, efficient operating condition through authorised OEM or their accredited/ authorised agencies by regularly examining, lubricating and adjusting the eqpt and carrying out planned maintenance in a systematic and controlled manner using technician and expertise and replacement of all unserviceable as per OEM term & condition and schedule of maintenece provided by the OEM including machine and belt. Equipment covered such as Renew all wire ropes and chains (where fitted) as often required an adequate factor of saftey, to equalise the tension on all hoisting ropes, repair or replace conductor cables and hoistway and machine room elevetor wiring, machine, worn gear, thrust bearings, drive sheves, drive sheaves bearing, break contact, lining and components, Motor, motor generator, motor winding, rotating elements, commutator, ---Contd to Srl Item No 54.01---
over load warning indicator and digital group indicator panel with micro-processer complete and automatic rescue device incl maintenance free battery and cost of material & qualified technician to attend the complaint on requirement basis including sunday and holiday.
Supply & fix in replacement of addresseble manual call point resetteable type all as specified and directed.
Repairs to door shutters of out door/indoor LT switch board Panel,MCCB,s covers,Bus bar chamber covers etc fabricated with MS sheet 3.15mm thick complete including cutting to required size and shape fixing in position by bending, welding all as required for proper functioning of LT panel shutters including two coats of synthetic enamel paint over a coat of red oxide all as specified and directed.
Material and Labour for descaling of steam boiler of cap 600 Kg by descaling media SRI-S2 Liquid Boiler Descaling Chemical, standard grade or by Liquid Sulfamic Descalant all as specified and directed.
Supply and fix in replacement Air termination, single pointed rod 12 mm dia and 300 mm long in existing GI pipe of 20-25 mm dia all as specified and directed.
Supply and fix in replacement test point terminal block made of gun metal or phasphorus bronze size 75X75X25 mm drilled and screwed including 3 Nos. 8 mm dia 25mm long hex. head screw all as specified and directed.
Supply and fix in replacement Aluminium strip 25 X 3.15 mm with saddles and fixing screws etc for roof conductors above ground all as specified and directed.
Material and Labour for PCC block of size 30 x 30 x 30 cm type B-1, 1:2:4 (20 mm graded aggregate) with and including embedded 25 mm dia GI pipe medium grade 1.00 m long for fixing air termination including all necessary fixing arrangement all as directed.
Material and Labour for detecting water leakage from Over head tank of cap 50000 Gln/ 100000 Gln with 30 m staging and necessary repair to make leakage prooof all as directed by Engineer -in- Charge.
M/s Dhapola Elevator and Engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .