| 1 | L1₹29.3 LAccepted-AOC E 84 OF HQ CWE NW MUMBAI AGE 87 1 3 GEETA NAGAR NAVY NAGAR COLABA MUMBAI 400 005 | MUMBAI | MAHARASHTRA | 400005 | L1 | Accepted-AOC L1 | |
| 2 | L2₹43.9 L+₹12.7 L (40.8%)Rejected-Finance | L2 | Rejected-Finance Not Reasonable |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
28 Jul 2022, 6:00 pmClosed
Saurabh Gupta, EE
GE (W) Colaba, Mumbai
REPAIR/MAINT OF BLDG SECURITY LIGHTS, CABLE DUCTING, METER ROOM PANELS OF MD ACCN/OTM AND REPAIRS/REPLACEMENT TO INTERNAL ELECTRIFICATION, LED FITTING AND FIXTURES CONNECTED ITEMS IN OFFRS MD ACCN AND DEF CIV QTR AT COLABA UNDER GE (W) COLABA
2022_MES_533446_1
8655/E8
Open Tender
Civil Works
Item Rate
180 days
GE (W) Colaba
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (W) Colaba, Mumbai
₹80,000
Yes
26 Aug 2022
24 Jun 2022
30 Jul 2022
24 Jun 2022
28 Jul 2022
7 Jul 2022
Amount
Taking down old cable tray of any type by disconnecting and removing (sub main wiring PVC pipes for refixing) and supply & fixing in repair of GI hot dip/ powder coated perforated type cable tray of sheet thickness not less than 2.0 mm and 50 mm height of tray and width not less than 200mm to be fixed on any wall (brick/stone) vertically/horizontally elbow & Tee, including tray cover of thickness not less than 2.00mm, and connected all accessories complete bending, shaping, drilling, welding, cutting alongwith all fixing arrangement such as suitable size of nuts, bolts, coupler plates, iron bars, fastners etc. complete all as specified and directed.
All as per Item No 1 above but of width not less than 300 mm
All as per Item No 1 above but of width not less than 450 mm Notes for item No 1 to 3 :- (a) Taking down and refixing of service connections/submain wiring will measure and paid separatly (b) Rate quoted must be inclusive of frame work for fixing cable trays on to walls/ ceiling.
Supply & fixing in repairs MS plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment in repair and similar work conforming to Fe 410-W (Gde-E- 250) quality A all as specified and directed.
Taking down exisitng LT Cable aluminium/copper any size laid on wall/floor/trenches, submain wiring, and lan/telephone wires and refixing on cable trays/ walls including all accessories all as specified and directed.
M&L PCC 1:2:4, type B1 (using 20mm graded crushed stone aggregate) as in foundation filling /road filling including including rafts, footings, foundation beams plinth beams, bases for columns and mass concrete all as specified and directed.
Material and labor for fabrication work with Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint all as specifeid and diredted.
Supply, install, testing and commissioning of LT building panel board mounted on angle iron frame 40mm x 40mm x 5 mm grouted on floor, double door cubical indoor type for 415V, 3 phase, made of 2 mm thick CRCA sheet weather, vermin proof factory fabricated, powder coated, CPRI approved, front open hinged door with locking arrangement with individual compartment / Chambers for incoming MCCBs, outgoing SPN's, single phase meter boxes and 200 Amps rated bus bar, rear top and bottom cable entry including disconnecting cable connections, electronic meters from old meter cabin panel and fixing/connecting in new installed panel with provisions of thimble/lugs and necessary farme work and PCC foundation including shifting of existing panel to store if any making arrengement for fixing of panel and making good to disturbed surfaces all as directed comprising the following : INCOMING :- (Busbar Chamber & Incoming MCCB) (a) Copper strip busbar 100 amps rated, wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including insulators with nuts & bolts at both ends = 04 nos. (b) MCCB, FP, 100 Amps 16 kA including all fixing accessories - 01 Nos. Make-Legrand / Schneider / L&T (c) 3 Phase LED voltmeter Cl 0.5 - 1 Nos, 3 Ph LED Ammeter of Cl 0.5-1 Nos Make : Legrand/Schneider/L&T), CT 100/5 A-3 Nos (d) LED Neon indicator light (RYB) 230/250 volts, AC -01 set (set of three) Make :- AE/L&T OUTGOING :- (MCB Chamber and Meter box Chambers) (a) MCB, Single pole & neutral, 40 amps, 240 volts, ‘C’ curve, 10 KA all complete as specified and as directed - 09 Nos with qtr numbers over each spn block. (b) Fixing only serviceable existing electric meter - 09 Nos with provision of glass over meter chamber for meter reading. Location : P-80, P-83, P-84, P-94, P-91
Supply, install, testing and commissioning of LT building panel board mounted on angle iron frame 40mm x 40mm x 5 mm grouted on floor, double door cubical indoor type for 415V, 3 phase, made of 2 mm thick CRCA sheet weather, vermin proof factory fabricated, powder coated, CPRI approved, front open hinged door with locking arrangement with individual compartment / Chambers for incoming MCCBs, outgoing SPN's, single phase meter boxes and 200 Amps rated bus bar, rear top and bottom cable entry including disconnecting cable connections, electronic meters from old meter cabin panel and fixing/connecting in new installed panel with provisions of thimble/lugs and necessary farmwork and PCC foundation including shifting of existing panel to store if any making arrengement for fixing of panel and making good to disturbed surface as directed comprising of the following : INCOMING :- (Busbar Chamber & Incoming MCCB) (a) Copper strip busbar 200 amps rated, wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including insulators with nuts & bolts at both ends = 04 nos. (b) MCCB, FP, 160 Amps 25 kA- 01 Nos. Make-Legrand / Schneider / L&TMCCB including all fixing accessories -01 Nos. (c) 3Ph LED voltmeter Cl 0.5- 1 Nos, 3Ph LED Ammeter of Cl 0.5-1 Nos(Make : Legrand/Schneider/L&T) (d) LED Neon indicator light (RYB) 230/250 volts, AC -01 set (set of three) Make :- AE/L&T OUTGOING :- (MCB Chamber and Meter box Chambers) (a) MCB, Single pole & neutral, 40 amps, 240 volts, ‘C’ curve, 10 KA all complete as specified and as directed - 14 Nos with qtr numbers over each spn block. (b) Fixing only serviceable existing electric meter - 13 Nos with provision of glass over meter chamber for meter reading. (c) MCCB FP, 80 Amps 16 KA -01 Nos. Make-Legrand / Schneider / L&TMCCB Location : P-96
Supply, install, testing and commissioning of LT building Panel board mounted on angle iron frame 40mm x 40mm x 5 mm grouted on floor, double door cubical indoor type for 415V, 3 phase, made of 2 mm thick CRCA sheet weather, vermin proof factory fabricated, powder coated, CPRI approved, front open hinged door with locking arrangement with individual compartment / Chambers for incoming MCCBs, outgoing SPN's, single phase meter boxes and 200 Amps rated bus bar, rear top and bottom cable entry including disconnecting cable connections, electronic meters from old meter cabin panel and fixing/connecting in new insalled panel with provisions of thimble/lugs and necessary farmwork and PCC foundation including shifting of existing panel if any making arrengement for fixing of panel and making good to disturbed surface as directed comprising of the following : INCOMING :- (Busbar Chamber & Incoming MCCB) (a) Copper strip busbar 200 amps rated, wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including insulators with nuts & bolts at both ends = 04 nos. (b) MCCB, FP, 160 Amps 25 kA- 01 Nos. Make-Legrand / Schneider / L&TMCCB including all fixing accessories -01 Nos. (c) 3Ph LED voltmeter Cl 0.5- 1 Nos, 3Ph LED Ammeter of Cl 0.5-1 Nos(Make : Legrand/Schneider/L&T), CT 200/5 amp-3 Nos (d) LED Neon indicator light (RYB) 230/250 volts,AC -01 set (set of three) Make :- AE/L&T OUTGOING :- (MCB Chamber and Meter box Chambers) (a) MCB, Single pole & neutral, 40 amps, 240 volts, ‘C’ curve, 10 KA all complete as specified and as directed - 15 Nos with qtr numbers over each spn block. (b) Fixing only serviceable existing electric meter - 15 Nos with provision of glass over meter chamber for meter reading. Location : P-107
Supply, install, testing and commissioning of LT building Panel board mounted on angle iron frame 40mm x 40mm x 5 mm grouted on floor, double door cubical indoor type for 415V, 3 phase, made of 2 mm thick CRCA sheet weather, vermin proof factory fabricated, powder coated, CPRI approved, front open hinged door with locking arrangement with individual compartment / Chambers for incoming MCCBs, outgoing SPN's, single phase meter boxes and 200 Amps rated bus bar, rear top and bottom cable entry including disconnecting cable connections, electronic meters from old meter cabin panel and fixing/connecting in new insalled panel with provisions of thimble/lugs and necessary farmwork and PCC foundation including shifting of existing panel to store if any making arrengement for fixing of panel and making good to disturbed surface as directed comprising of the following : INCOMING :- (Busbar Chamber & Incoming MCCB) (a) Copper strip busbar 200 amps rated, wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including insulators with nuts & bolts at both ends = 04 nos. (b) MCCB, FP, 160 Amps 25 kA- 01 Nos. Make-Legrand / Schneider / L&TMCCB including all fixing accessories -01 Nos. (c) 3Ph LED voltmeter Cl 0.5- 1 Nos, 3Ph LED Ammeter of Cl 0.5-1 Nos(Make : Legrand/Schneider/L&T) , CT 200/5 -3 Nos (d) LED Neon indicator light (RYB) 230/250 volts,AC -01 set (set of three) Make :- AE/L&T OUTGOING :- (MCB Chamber and Meter box Chambers) (a) MCB, Single pole & neutral, 40 amps, 240 volts, ‘C’ curve, 10 KA all complete as specified and as directed - 18 Nos with qtr numbers over each spn block. (b) Fixing only serviceable existing electric meter - 15 Nos with provision of glass over meter chamber for meter reading. Location : P-112
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting out in soft loose soil for removing of cable including returning filling, spreading, levelling and well ramming in layers not exc 25 cm all as specified and directed.
Supply and fix in replacement cable LT XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable heavy duty with copper conductor LT 1100 volts grade, 3.5 core of size 50 Sqmm including disconnecting /getting out old unserviceable cable piece all as specified and directed. Make: Polycab/Havells/CCI
Supply, install, testing and commissioning of LT building Panel board mounted on angle iron frame 40mm x 40mm x 5 mm grouted on floor, double door cubical indoor type for 415V, 3 phase, made of 2 mm thick CRCA sheet weather, vermin proof factory fabricated, powder coated, CPRI approved, front open hinged door with locking arrangement with individual compartment / Chambers for incoming MCCBs, outgoing SPN's, single phase meter boxes and 400 Amps rated bus bar, rear top and bottom cable entry including disconnecting cable connections, electronic meters from old meter cabin panel and fixing/connecting in new insalled panel with provisions of thimble/lugs and necessary farmwork and PCC foundation including shifting of existing panel to store if any making arrengement for fixing of panel and making good to disturbed surface as directed comprising of the following : INCOMING :- (Busbar Chamber & Incoming MCCB) (a) Copper strip busbar 400 amps rated, wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including insulators with nuts & bolts at both ends = 04 nos. (b) MCCB, FP, 320 Amps 36 kA- 01 Nos. Make-Legrand / Schneider / L&TMCCB including all fixing accessories -01 Nos. (c) MCCB, FP, 160 Amps 25 kA- 01 Nos. Make-Legrand / Schneider / L&TMCCB including all fixing accessories -02 Nos. (d) 3Ph LED voltmeter Cl 0.5- 1 Nos, 3Ph LED Ammeter of Cl 0.5-1 Nos(Make : Legrand/Schneider/L&T) , CT 400/5 -3 Nos (e) LED Neon indicator light (RYB) 230/250 volts,AC -01 set (set of three) Make :- AE/L&T OUTGOING :- (MCB Chamber and Meter box Chambers) (a) MCB, Single pole & neutral, 40 amps, 240 volts, ‘C’ curve, 10 KA all complete as specified and as directed - 18 Nos with qtr numbers over each spn block. (b) Fixing only serviceable existing electric meter - 15 Nos with provision of glass over meter chamber for meter reading. Location : 112
Supply and fixing in repair LED building security light fitting 45 Watt, luminaire fixture in IP 66 protection level output of LED lamp efficiency minium 100 luman per watt after all losses , pressure die-cast aluminium housing LED Street light complete with GI clamp including connected accessories and bracket made of GI Pipe 50mm dia light grade 1.25 m long, bend to shape with two sets of MS flat iron clamps, nuts, bolts, washers etc. complete all as directed by Engineer-in-Charge. Make Philips : cat pat No BRP409 LED060HENRPC S1PSU GR or equivalent in Wipro cat part No LR02-501-XXX-57-XX / Havells cat part No ENDURACITYLINERNEXGENSL45WLED757 SASYBOPC. Note : The rate quoted must be inclusive of 3 core 1.5sqmm cable for connecting the light to supply.
M&L for earthing complete using GI Plate electrode 60 cm X 60 cm X 6 mm thick, burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.50 mtr below normal ground level but using galvanised iron wire 4 mm as earthing lead by means of GI bolts, nuts, check nuts, washers made out of GI/steel, all as shown on electrical plate No 3 of MES schedule part-I, earth lead wire connected to indicated position including concrete pit in PCC (1:3:6, C1), Precast RCC cover slab 55 cm x 55 cm x 5 cm with reinforcement of 8 mm dia bar 100 mm c/c bothways including one handle made of 12 mm dia MS bar embedded in pre cast slab and 20 mm bore galvanised iron pipe"medium grade" for watering with GI funnel and wire mess including 15 mm dia GI pipe light grade for protection pipe including charcoal and salt in alternate layers of 15 cm including necessary excavation and earth work in any type of soil all as specified and as directed and testing on completion.
S&F in repair earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire all as specified and directed.
Material & Labour for Sub main wiring in repair, with two run of 16 sq mm stranded copper conductor PVC unseathed FRLSH wire along with 16 sq mm green colour wire as earth contuinity conductor connected to common earth dolly including PVC FR heavy duty conduit of adequate size (not less than 32 mm dia) for housing the wires for from Pannel / Main DB to house SPN DB including taking down old unserviceable submain with all associated fixtures complete all as specified & as directed by engr-in-charge Make : Finecab / Havells / Finolex as approved by GE Note: (a) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. (b) Note: Mode of measurement two runs of 16 sqmm cable and one run of 16 sqmm cable with PVC conduit shall be measured as one length.
Material & Labour for Sub main wiring in repair, with two run of 10 sq mm stranded copper conductor PVC unseathed FRLSH wire along with 10 sq mm green colour wire as earth contuinity conductor connected to common earth dolly including PVC FR heavy duty conduit of adequate size (not less than 32 mm dia) for housing the wires for from Pannel / Main DB to house SPN DB including taking down old unserviceable submain with all associated fixtures complete all as specified & as directed by engr-in-charge Make : Finecab / Havells / Finolex as approved by GE Note: (a) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. (b) Mode of measurement two runs of 10 sqmm cable and one run of 10 sqmm cable with PVC conduit shall be measured as one length.
Material & Labour for Sub main wiring in repair, with two run of 4 sq mm stranded copper conductor PVC unseathed FRLSH wire along with 4 sq mm green colour wire as earth contuinity conductor connected to common earth dolly including PVC FR heavy duty conduit of adequate size (not less than 32 mm dia) for housing the wires for from house SPN DB to servant Qtr SPN DB including taking down old unserviceable submain with all associated fixtures all as specified & as directed by engr-in-charge Make : Finecab / Havells / Finolex as approved by GE Note: (a) Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. (b) Mode of measurement two runs of 4 sqmm cable and one run of 4 sqmm cable with PVC conduit shall be measured as one length.
Material & Labour for point wiring with PVC insulated unsheathed single core multi stranded copper conductor 1.5 sqmm, 1100 volts grade cable, FRLSH, passing through PVC casing caping including modular PVC Gang box of suitable module for mounting of modular Switchs & Sockets as required at site along with one run of PVC insulated unsheathed multistranded copper conductor cable 1.5 sqmm (green colour) FRLSH as earth wire connected to earth dolly complete all as specified & as directed by engr-in-charge for one light point/ Exhaust fan/ Wall Fan controlled by one switch including taking down old unserveceable point wiring. Make of Wire : Anchor / Havells / Finolex of ISI mark as approved by GE
All as per item No.21 above but One bell point controlled by one bell push.
All as per item No.21 above but One ceiling fan controlled by one switch & regulator
All as per serial no.21 above but for one light point controlled by two, two way switches (two way switch point wiring)
All as per item No.21 above but One 3 pin socket point 5 Amps on independent board
All as per item No.21 but One 3 pin socket point 5 Amps on same board
All as per srl item No 21 here-in-before but for one socket point 15 Amp with 2.5 sq mm PVC unseathed FRLSH wire along with 2.5 sq mm green colour wire as earth contuinity conductor connected to common earth dolly all as specified and as directed.
All as per srl item No 21 here-in-before but for AC point 20 Amp with 4 sq mm PVC unseathed FRLSH wire along with 4 sq mm green colour wire as earth contuinity conductor connected to common earth dolly all as specified & as directed.
Material & Labour for Point wiring (concealed type) with 1.5 sq mm, PVC insulated unsheathed (FRLSH), 1100 volts grade, multi-stranded copper conductor, in and including rigid non-metallic PVC heavy duty conduit (ISI mark), 19/ 20 mm dia suitable size including cutting chases for conduits, sinking for boxes for concealed conduit wiring with all fittings and accessories including with and fix concealed 1.2 mm thick pressed steel sunken box, suitable for fixing moduler switch socket and unsheathed (FRLSH) single core multi-stranded copper conductor cable of size 1.5 sq mm green in colour as earth continuity conductor connected to common earth dolly and making good to the disturbed surfaces to match the existing surfaces complete (fill up cement in gaps, finishing with putti and apply two coats of paint, match with existing colour in disturbed surface area), as per IS specification and as specified in SSR Part-I complete for one light point / Ex Fan / wall fan controlled by one modular switch, 1 way 6/10 amps, 1 module including taking down old unserveceable point wiring all as specified and directed. Make of Cable : Anchor / Havells / Finolex / Polycab Make of Conduit : Precision/ Prestoplast/ Polycab
All as per serial no.29 here-in before but for bell point controlled by one switch.
All as per serial no.29 here-in before but for but one light point controlled by two, two way switches (two way switch point wiring)
All as per serial no.29 here-in before but for One ceiling fan by one switch & regulator
All as per serial no.29 here-in before but for One 3 pin socket point 5 Amps on independent board
All as per serial no.29 here-in before but for One 3 pin socket point 5 Amps on same board
All as per srl item no.29 here-in-before but for one socket point 15 Amp with 2.5 sq mm PVC unseathed FRLS wire along with 2.5 sq mm green colour wire as earth contuinity conductor connected to common earth dolly all as specified & as directed.
All as per srl item No 29 here-in-before but for AC point 20 Amp with 4 sq mm PVC unsheathed FRLSH wire along with 4 sq mm green colour wire as earth contuinity conductor connected to common earth dolly all as specified & as directed.
S&F in repair Moduler Switch , flush type single pole, one way 6/10 Amp all as specified & as directed.
S&F in repair Moduler Switch , flush type single pole, one way 16 Amp all as specified & as directed.
S&F in repair Moduler socket 2/3 pin 6 Amp all as specified & as directed.
S&F in repair Moduler socket 6/16 A 2/3 pin all as specified & as directed.
S&F in repair Moduler stepped type electronic fan regulator 450 watt flush type, two module all as specified & as directed.
S&F in repair Moduler bell push, 2 modue, 10 Amp all as specified & as directed.
S&F in repair ceiling rose surface bakelite 65 x 50 mm two to three terminals complete all as specified and as directed.
S&F in repair Modular blank plate 1 module all as specified & as directed.
S&F in repair Modular blank plate 2 module all as specified & as directed.
S&F in repair Moduler Switch , flush type single pole, two way 6 Amp, 1 module all as specified & as directed.
Supply and fix white modular cover plate with frame 1 module all as specified & as directed.
Supply and fix white modular cover plate with frame 2 module all as specified & as directed.
Supply and fix white modular cover plate with frame 3 module all as specified & as directed.
Supply and fix white modular cover plate with frame 6 module all as specified & as directed.
Supply and fix white modular cover plate with frame 8 module all as specified & as directed. Make for Item No 37 to 51 :- Crabtree(Athena)/Anchor(Roma)/Legrand(Britzy)
S & F in repair Modular type AC Box, 4 Module with Socket and 25 Amp SP mini MCB in plastic box enclosure along with cover plate and top all as specified and directed. Make : Anchor Model No : 98498 or equivalent model in Havells/ Legrand.
S&F in repair Bell ding dong, AC, 230 volts, single pole complete all as specified and as directed Make: Anchor /legrand / Crabtree/ SSK as approved by GE
S&F in repair Modular electronic chime Bell ding dong 2 Module, AC, 230 volts all as specified and as directed Make: Legrnd (Arteor) cat part No : 5734 42 or equivalent in Anchor / Havells
S&F telephone socket - RJ11 with shutter - 1 module all as specified and as directed Make :- Crabtree(Athena)/Anchor(Roma)/Legrand(Britzy)
Supply & Fix non-metallic PVC casing capping of size 25X12mm dia (for fixing the telephone cable and lan cable) all as specified and as directed Make : Precision/ Pressfit/ Prestoplast /Asian
Supply and Fix 20 watt LED in repair, 4 feet long fixed on pvc square for mounting the fittings and electrically conncected with suitable size of pvc insulated multistranded copper flexible cable from ceiling rose to light fitting (connector block of lamp fitting) complete all as specified and directed Make: Havells Model No :20W Bajaj IVORA 20W CDL of Bajaj / havells / Wipro.
Supply and fix surface mounted 9/10 watts LED tube light fitting in repair, and electrically conncected with suitable size of pvc insulated multistranded copper flexible cable from ceiling rose to light fitting all as specified and as directed Make:- Havells Model No E-lite LED Pride Plus NEO Cat pat NO : 10W Bajaj IVORA 10W CDL of Bajaj./havells/wipro
Supply and Fix 20 watt smart extruded aluminium LED batten high efficiency inbuilt sensor in repairs, 4 feet long fixed on pvc square for mounting the fittings and electrically conncected with suitable size of pvc insulated multistranded copper flexible cable from ceiling rose to light fitting (connector block of lamp fitting) all as specified and directed Make: Bajaj No- BCLAB 20W LED PS /Havells / SHAKTI/ Wipro.
S&F in repairs decorative wall mounting fitting, working on 240 volts, 50 hz ac supply fittings comprising with stainless steel finish fixture including with opal glass diffuser and with led bulb of capacity 7 watt all as specified and directed. Make : Havells Cat NO-LHFOECE1PZ18B014/ Bajaj/shakti/crompton
Supply and fix exhaust fan metal body having 70 watt power double ball bearing high speed of sweep size 300 mm, inbuilt bird guard and air delivery more than 450 CMM with nuts bolts, fastners including connecting with PVC insulated and PVC sheathed copper flexible cable and necessary fixing arrangement all as specified and as directed. Make - Bajaj BAHAR 300MM METTALIC GRAY / Havells / CROMPTON.
Supply and fix for Exhaust fan metal body having 70 watt power double ball of bearing high speed of sweep size 225 mm, inbuilt bird gaurd and air delivery more than 450 CMM with nuts bolts, fastners including connecting with PVC insulated and PVC sheathed copper flexible cable and necessary fixing arrangement all as specified and as directed. Make - Bajaj BAHAR 225 MM METTALIC GRAY / Havells / CROMPTON.
Supply and fix for wall mounted Exhaust fan PLASTIC body having high speed 1325 rpm of sweep size 200 mm, inbuilt bird gaurd and air delivery more than 450 CMM with nuts bolts, fastners including connecting with PVC insulated and PVC sheathed copper flexible cable and necessary fixing arrangement all as specified and as directed. Make - Bajaj MAXIMA DXI 200MM / Havells / CROMPTON.
Supply and fix wall fan PLASTIC body having high speed 1350 rpm of sweep size 300 mm, inbuilt gaurd and 55 watt power with nuts bolts, fastners including connecting with PVC insulated and PVC sheathed copper flexible cable and necessary fixing arrangement all as specified and as directed Make - Bajaj ESTEEM 300MM / Havells / CROMPTON.
Supply and Fix for wall fitting one LT Conical opal glass mirror light with LED Lamp one 4/6 watt and conncected with suitable size of pvc insulated multistranded copper flexible cable from ceiling rose to light fitting (connector block of lamp fitting) all as specified and directed Make: Jaquar Cat Part No - Jaquar JNL-BRG-WLCONESIE14/equivalent model in Havells/ Philips/ Bajaj.
S&F in repairs decorative wall mounting fitting, working on 240 volts, 50 hz, fittings comprising with stainless steel finish fixture including with opal glass diffuser and with LED bulb of capacity 7 WATT all as specified and directed. Make : Jaquar, Cat Part No JNL-CHR-WLSL55004E27 or equivalent in Philips / Havells Wipro / sample as approved by GE
Supply and fix in repairs bed side off white/ivory fabric shade LED light fitting, with chrome finishing including LED lamp of capacity 4 Watt and an adjustable reading led light fitted to it at bottom, electrically conncected with suitable size of pvc insulated multi stranded copper flexible cable from ceiling rose to light fitting (connector block of lamp fitting) all as specified and directed Make : Jaquar, Cat Part No: WBR-CHR-MB12021192B or equivalent in Philips / Havells/ Wipro
Supply and fix LED 18 Watt 6500 K , Slim surface mounted LED panel with premium diffuser to ensure glare free & even light distribution in LIFT Corridor area, with integrated electronic driver of same make connecting with PVC insulated and PVC sheathed copper flexible cable and necessary fixing arrangement all as specified and as directed . Make - Havells (Cat part No - LHEAAKP7IL1W018) /BAJAJ/ Wipro/ Philips
S&F in repair DB vertical type 4 way TPN, doubble door load line powder coated complete alongwith 200 Amp rated Bus bar fixed on wall duly grouted in solid block wall or on wooden board in and including copper lugs/thimbles duly crimped for connection all as specified and directed. Note: Thimble/lugs of rating of MCCB should be used with wire for fixing in the MCB. Make : Havells / Legrand / Schneider / Legrand
Supply and fix in repair MCB TPN 100 amps, 'C' series, breaking capacity 10 KA, 'C' curve 240 volts, 50 Hz including necessary incoming and outgoing electric connection with suitable size of copper lugs all as specified and directed. Make :Havells / Legrand / Schneider / Legrand
Supply and fix in repair sheet metal enclosures double door, for DBs when MCBs to be used 240 volts 2 way without bus bar fixed on wall duly grouted in solid block wall or on wooden board in and including copper lugs/thimbles duly crimped for connection all as specified and directed. Make : Havells / Legrand / Schneider / Legrand
Supply and fix in repair sheet metal enclosures double door, for DBs when MCBs to be used 240 volts 4 way with 200 Amps rated bus bar single pole and neutral fixed on wall by cutting chasing and making good to the disturbed surfaced board in and including copper lugs/thimbles duly crimped for connection all as specified and directed. Make : Havells / Legrand / Schneider / Indo Asian
Supply and fix in repair sheet metal enclosures double door, for DBs when MCBs to be used 240 volts 4 way with 200 Amps rated bus bar single pole and neutral fixed on wall by cutting chasing and making good to the disturbed surfaced board in and including copper lugs/thimbles duly crimped for connection complete all as specified and directed. Make : Havells / Legrand / Schneider / Indo Asian
Supply and fix in repair sheet metal enclosures double door, for DBs when MCBs to be used 240 volts 12 way with 200 Amps rated bus bar single pole and neutral fixed on wall by cutting chasing and making good to the disturbed surfaced board in and including copper lugs/thimbles duly crimped for connection complete all as specified and directed. Make : Havells / Legrand / Schneider / Indo Asian
Supply and fix in repair MCB SP 240 volt, 16 to 40 Amps, C series, all as specified and directed. Note: Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB Make : Havells / Legrand / Schneider / Indo Asian
Supply and fix in repair MCB SPN 240 volt, 40 to 63 Amps, C series, all as specified and directed. Note: Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. Make : Havells / Legrand / Schneider / Indo Asian
Supply and Fix in repair for 10 watt, PDC Housing 6500 K Bulk head luminaire with opal diffuser LED , IP 65 protection working on 240 volts, 50 hz AC fittings comprising inbuilt surge protection all as specified and directed. Make: Bajaj Cat NO- BIBWP 10W LED /Havells / Wipro.
NOEL ENGINEERS
Bidder Name
NOEL ENGINEERS
shree arihant constrution
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .