| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.9 LAccepted-AOC 5574 A KANSHI RAM MARKET NEW CHANDRAWAL KAMLA NAGAR DELHI 07 | ₹2.9 L | L1 | Accepted-AOC Firm is L1 bidder |
| 2 | L2₹4.0 L+₹1.1 L (36.7%)Rejected-Finance | ₹4.0 L+₹1.1 L (36.7%) | L2 | Rejected-Finance Firm is L2 Bidder |
| 3 | L3₹4.1 L+₹1.2 L (39.6%)Rejected-Finance | ₹4.1 L+₹1.2 L (39.6%) | L3 | Rejected-Finance Firm is L3 Bidder |
Tender Value
₹4.2 L
EMD Value
₹8,400
Closing Date
13 Jul 2026, 11:00 amClosed
Puran Dass Kabeer
MUNICIPAL CORPORATION OF DELHI Office of the Executive Engineer E and M Central Zone Under Sewa Nagar Flyover , Lodhi Road , Delhi -03
Renovation/ strengthening of electrical panel and allied works at Jaitpur no. 2 pumping station under central zone.
2026_MCD_283733_1
EE(EandM)/MCD/2026-27/30.1
Open Tender
Electrical Works
Percentage
30 days
Lodhi Road
Please refer Tender documents
3 documents required · 3 mandatory
₹590
₹8,400
4 Aug 2026
10 Jul 2026
14 Jul 2026
10 Jul 2026
13 Jul 2026
10 Jul 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Automatic Power Factor Correction (APFC) System: SITC of Automatic Power Factor Correction (APFC) panel, indoor type floor mounted free standing totally enclosed, extendable, IP 42, of following capacity for 3 phase, 415 V + 10 %, 50 Hz AC System for Ambient temperature -5°C to +40°C, fabricated in compartmentalised designed made of CRCA sheet steel of 2.0mm thick for framework & covers, 3 mm thick for gland plate i/c cleaning & finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section capacitor and reactor, front and rear access, having suitable current carrying capacity, extensible TPN Aluminium alloy bus bar of high conductivity, DMC/SMC bus bar supports, bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS13340 Part -1 & 2) APFC Panel shall be in compliance with IS :16636 & CPWD Specifications etc. as per below details
(A) Incomers Suitable capacity MCCB Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set alongwith required Instruments and accessories with extended rotary handel and door interlocking arrangment. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating.
(B) Instruments & Indications i) 3-Phase current sensing APFC microprocessor relay/controller, advance 8/12 stages (8 stages for capacity below 100 KVAR and 12 stages 100 KVAR & above) with Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge and having display of Phase wise V, A, PF, Cos-Phi, Kw, KVA, KVAR, THD-V , THD-I, harmonics up to 31 level. 3 nos of dual core CT's accuracy class 1, 15VA at incomer of PCC Panel for APFC relay.
ii) Auto Manual Selector switch, auxiliary contactors with timer for delay in manual mode.383DELHI ANALYSIS OF RATES (E&M) 2025 iii) Digital Multi function meter with LED Display for V, A, PF,KW, KVA, KVAR, THD-V & I, Frequency. iv) Suitable rating control transformer shall be provided for control and indication circuit. v) All components like control transformer, meter, relay and indicating lamp shall be protected by using suitable rating individual MCB's. vi) Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS/HFFR 1100 V grade, PVC insulated multi stranded copper control wire.
(C) Bus Bars 1.3 Amp per Sq.mm,TPN, Electrolytic grade Aluminium bus bar of capacity 1.25 times of incomer rating as per CPWD specification. (D) Outgoings (APFC Section) Selection of the capacitors combinations shall be for continuous rating and each capacitor bank shall have suitable capacity Heavy Duty ISI Marked Capacitor, capacitor duty contactor,the capacitor shall be mounted on channel with base of perforated M S Powder coated sheet, connections inter connections etc. and other features as per CPWD Specifications and relevant IS Code having following: (i) Capacitor bank ratings & stages shall be as per the
technical specifications sheet of NIT. (ii) Capacitor will be MPP self healing type with discharge resistor, pressure release mechanism. (iii) Since Capacitor Voltage is 525 Volts, thus higher KVAR has to be considered to get rated output at 415 Volts.
(iv) 14% Detuned Reactor of class H insulation & 150% linearity in series with Capacitor. 125 KVAR | 1 | Each | 3,20,033 | ₹3,20,033 |
| 2 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3.5C*50 sqmm | 30 | Meter | 327 | ₹9,810 |
| 3 | Laying and fixing of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) | 30 | pm | 151 | ₹4,530 |
| 4 | Providing and fixing of 24/30V, tripping system 1 incoming & 2 outgoing. The job Includes disconnection of relay from the panel, calibration and testing with primary injection test. The job includes the replacement of defective wiring as required at site. (Over current and earth fault relay | 2 | Each | 14,160 | ₹28,320 |
| 5 | Rectification of wiring of panel for protection relay and metering system | 2 | Each | 8,260 | ₹16,520 |
| 6 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 50 sq. mm (35mm) | 12 | Each | 442 | ₹5,304 |
| 7 | Providing and fixing of indicating lamp unit with holder | 20 | Each | 354 | ₹7,080 |
| 8 | Providing & fixing of Jaw/axuilary contact as requied | 3 | Each | 5,900 | ₹17,700 |
| 9 | Providing and fixing of space heater with thermostat including controling switch to maintaining the panel moisture free. | 3 | Job | 2,950 | ₹8,850 |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.09 MB
GCC2024_merged.pdf
Tender Documents • 17.92 MB
TandCsupply.pdf
Tender Documents • 0.06 MB
BOQ_331005.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .