| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.6 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹7.0 L+₹18,861 (2.77%)Rejected-AOC 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NEW DELHI | DELHI | DELHI | 110006 | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | L3₹7.8 L+₹98,400 (14.5%)Rejected-AOC WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | L3 | Rejected-AOC Other than lowest bidder | |
| 4 | L4₹8.7 L+₹1.9 L (27.4%)Rejected-AOC RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L4 | Rejected-AOC Other than lowest bidder |
Tender Value
₹9.9 L
EMD Value
₹19,840
Closing Date
29 Dec 2020, 6:00 pmClosed
AGE I CG
Noida
REPAIR MAINTENANCE OF APFC PANEL SERVO STABILIZER AND OTHER LT EQUIPMENTS AT SEC 23 SEC 24 SEC 52 UNDER AGE I COAST GUARD NOIDA
2020_MES_389964_2
AGE I CGN 35 20 21
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Noida
E b i
7 documents required · 7 mandatory
₹500
AGE I CG
₹19,840
6 May 2021
8 Dec 2020
31 Dec 2020
8 Dec 2020
29 Dec 2020
15 Dec 2020
Amount
(1) Disconnecting Existing defective voltage stabilizer at Sec 24 of 250 KVA capacity 3 phase 415 volts from electric mains , removing from foundations by unscrewing the nuts bolts etc repair/maintenence by draining out the transformer oil through the drain plug , dismantling both nut and bolt and lifting the top portion to carry out through inspection and clean the bottom portion of the voltage stabiliser tank by removing the mud and slurry and deposited material for prevention of short circuit and Refixing in Original position after Repair and testing complete all as specified and as directed by Engineer -in - charge. Note : Additional items/Spare parts required to make stabilizer serviceable, shall be measured and paid separately.
(2) Disconnecting Existing defective voltage stabilizer at Sec 52 of 400 KVA capacity 3 phase 415 volts from electric mains, removing from foundations by unscrewing the nuts bolts etc for repair/maintenence by draining out the transformer oil through the drain plug , dismantling both nut and bolt and lifting the top portion to carry out through inspection and clean the bottom portion of the voltage stabiliser tank by removing the mud and slurry and deposited material for prevention of short circuit and Refixing in Original position after Repair and testing complete all as specified and as directed by Engineer -in - charge.Note : Additional items/Spare parts required to make stabilizer serviceable, shall be measured and paid separately.
(3) Disconnecting Existing defective voltage stabilizer at Sec 23 of 250 KVA capacity 3 phase 415 volts from electric mains , removing from foundations by unscrewing the nuts bolts etc carrying to the factory /workshop including transportation charge for repair by draining out the transformer oil through the drain plug , dismantling both nut and bolt and lifting the top portion to carry out through inspection and clean the bottom portion of the voltage stabiliser tank by removing the mud and slurry and deposited material for prevention of short circuit and Taking out U/S control wiring complete for unbalanced load by providing wiring loom complete to the stabilizer made out of suitable size PVC insulated copper conductor cable including cable lugs, connectors, channels etc for prevention of short circuit and Refixing in Original position after Repair and testing complete all as specified and as directed by Engineer -in - charge. Note : Additional items/Spare parts required to make stabilizer serviceable, shall be measured and paid separately.
(4) Supply & Fixing in replacement of Electronic sensing Control card (PCB). Suitable for Existing Make - Volina & Other ISI marked.
(5) Supply & Fixing in replacement of PVC Connector 12 pin as per existing Make - Volina
(6) Supply & Fixing in replacement of Dimmer varic state unit 150 Amps for 250 KVA stablizer suitable for Existing Make.
(7) Supply only trigger (control) transformer with primary voltage 230 Volte and secondary voltage any desired voltage between 18 volt 500 mA suit the control cercuit of the stabilizer as per sample.
(8) Supply only trigger (control) transformer with primary voltage 230 Volte and secondary voltage any desired voltage between 24 volt 500 mA suit the control cercuit of the stabilizer as per sample.
(9) Supply only panel push to on voltage adjuster switch all as specified and directed by Engr - In - Charge.
(10) Supply only Auto Manual Switch all as specified and directed by Engr - In - Charge.
(11) supply only in- put & out-put switches all as per sample
(12) Supply only Micro switch (Limit switch) suitable to cut of supply to control motor on high and low settings limits all as specified and directed by Engr - In - Charge.
(13) Supply only Gear assembly of 120 teeths suitable for synchronous motor to oprate the shaft for variable dimmer stat all as specified and directed by Engr - In - Charge.
(14) Supply only synchronous motor 10 Kg Torqe suitable to work with voltage stablizer of capacity 250 to 400 KVA.
(15) Supply only Potentiometer suitable for servo voltage stablizer all as directed by Engr in charge.
(16) Supply only carbon brush with holder as per sample suitable for stablizer of Cap 400 KVA all as directed by Engr in Charge.
(17) Supply only carbon brush with holder as per sample suitable for stablizer of Cap 250 KVA all as directed by Engr in Charge.
(18) S&F in replacement of RC Net work 3 Kg suitable for Existing servo stabilizer of cap 250/400 KVA Make - Volina
(19) S&F in repairs voltage Arms of cap 150/200 Ams for Existing servo stabilizer of cap 250/400 KVA all as directed by Engr in charge.
(20) S&F in replacement of Bus bar connections from varic to series transformer suitable for 250 KVA stabilizer.
(21) S&F in replacement of copper Thimbles upto 185 Sqmm all as directed by Engr in charge.
(22) Rewinding of variable Transformer of servo stabilizer up to 250 KVA Capacity 3 Ph all as directed by Engr in charge
(23) Rewinding of series/ load Transformer up to 250 KVA Capacity 3 Ph all as directed by Engr in charge
(24) Dehyderation,filteration of transformer oil of servo stabilize using stream line filter to obtain a dielectric strength above 40 KV, including all arrangement for DG set,filteration plant,filter paper etc mentioned below all as directed and specified.
(25) Supply and Filling the new transfermer oil of approved make conforming to IS- 335 including filtertion of existing and top up oil so as to achieve IR value of the oil not less than 40 KV and all as specifaied and all as directed by Engineer - in - charge.
(26) M&L for Preparation of old painted surface of Servo Voltage stabiliser by scrapping / removing old paint , dirt etc, and spray painting with two coats of blue synthetic enamel paint over a coat of primer including writing of MES / SM No of capacity 250-400 KVA all as specified and directed by Engineer-in-charge.
(27) Supply & Fixing in replacement of Digital Amp Meter with CTs suitable for Existing Make - Volina,AE ,L&T
(28) S&F in replacement of MCCB thermal magnetic release, fixed type, 3 pole, 400 Amps, 415 Volts with repeturing capacity 36 KA and suitable for fixing in existing arrangement with connecting legs. Cat Part No- 422002 Make Legrand or its equivalent in L&T / Havells
(29) S&F in replacement of MCCB, thermal magnetic electric release, fixed type, 3 pole, 250 Amps, 415 Volts with repeturing capacity 36 KA and suitable for fixing in existing arrangement with connecting legs. Cat Part No- 420529 Make Legrand or its equivalent in L&T / Havells
(30) S&F in replacement of MCCB thermal magnetic electric release, fixed type, 3 pole, 200 Amps, 415 Volts with repeturing capacity 36 KA and suitable for fixing in existing arrangement with connecting legs. Make Legrand or its equivalent in L&T / Havells
(31) S&F in replacement of MCCB thermal magnetic electric release, fixed type, 3 pole, 125 Amps, 415 Volts with repeturing capacity 25 KA and suitable for fixing in existing arrangement with connecting legs. Make Legrand or its equivalent in L&T / Havells
(32) S&F in replacement of MCCB, thermal magnetic electric release, fixed type, 3 pole, 100 Amps, 415 Volts with repeturing capacity 16 KA and suitable for fixing in existing arrangement with connecting legs. Make Legrand or its equivalent in L&T / Havells
(33) S&F in replacement of MCCB, thermal magnetic electric release, fixed type, 3 pole, 63 Amps, 415 Volts with repeturing capacity 16 KA and suitable for fixing in existing arrangement with connecting legs. Make Legrand or its equivalent in L&T / Havells
(34) Supply and fixing (in replacement) of power contractor capacitor duty 3 pole 415 volts on pannel mounted type including disconnecting the incoming/outgoing cable connections and re-connecting with suitable copper lugs/ferruls etc. after taking out the existing u/s and making good the disturbed surface for following capacity.Make- L&T,Simens,C&S :- (a) Contactor suitable for up to 1-2 KVAR
(b) Contactor suitable for up to 3-5 KVAR
(c) Contactor suitable for above 5 to 12.5 KVAR
(d) Contactor suitable for above 12.5 KVAR to 20 KVAR
(e) Contactor suitable for above 20 KVAR to 25 KVAR
(f) Contactor suitable for above 33.3 KVAR to 50 KVAR
(35) S&F in replacement of voltmeter 0-500 Volts digital type suitable for Existing Make - Volina,AE ,L&T
(36) Supply and fix in replacement push button switch suitable for operating voltage 110/220 Volt for LT Panel.. Make- L&T,Simens,AE
(37) Supply and fix in replacement indicator lamp LED suitable for operating voltage 110/220 Volt for LT Panel. Make- L&T,Simens,AE
(41) Dismantling APFC panel carefully,removing the defective control device MCCB/MCBs,capacitors,indicator cum push button switches, relays, contacts, CTs, internal wiring, Cleaning all parts by CTC solution / emary paper as required and greasing the metallic and mechanical serviceable parts.
(42) Supply and fix relays NAAC 3P-12 suitable for 12 stage APFC panel Make:NEPTUNE or Equvallaent of EPCOS/L&T
(43) Supply and fix relays NAAC 3P-8 suitable for 8 stage APFC panel Make:NEPTUNE or Equvallaent of EPCOS/L&T
(44) Programming and tuning of relays suitable for APFC panel 8/12 stage all as directed by Engr-in-Charge
(45) Supply and fix Heavy Duty Capacitors of capacity 1 -15 KVAR . Make L&T ,Epcos,Havells
(46) Supply and fix Heavy Duty Capacitors of capacity 20 -50 KVAR box type Make L&T ,Epcos,Havells
(47) Supply and fix fresh air fan suitable for APFC panel
(48) Supply and fix illuminated push button switch suitable for APFC Panel.Make- L&T,Simens,AE
(50) Excavation in trenches not exceeding 1.5mtrs wide and not exceeding 1.5 mtr deep in hard /dense soil for laying underground cables and post holes all as specified and directed.
(51) Returning filling in including spreading levelling watering and well ramming in layres not exceeding 25 cm thick in hard/ dense soil.
(52) Removing surplus soil to a distance not exceeding 50 m and depositing at a level not exceeding 1.5m above the starting point.
(53) Supply and spreed fine river sand intrenches for cable cushioning on top and bottom of cable as specified.for cable protection
(54) Supply and lay sub class 'B' bricks size 230mmx115mmx75mm to be laid on sand cushioning for protection of cable.
(55) PCC 1:4:8, type D-2, using 40 mm graded stone aggregate as in foundation, filling and mass concrete all as specified and as directed
(56) PCC 1:3:6, type C-1, using 20 mm graded stone aggregate as in foundation/ coping of poles including necessary form work and finishing the exposed concrete surfaces even and fair all as specified and as directed
(57) Removing from trench/duct etc old armouned, XLPE insulated LT electric power cables of any size and keeping in safe custody all as specified and directed
(58) Relaying/rerouting of LT UG cable of any size all as specified and directed
(59) Supply and fixing of XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric cable(heavy duty) with aluminium conductor 1100 volts grade cross sectional area 3½ core x 70 sq mm in trenches/on truss/wall/floor through pipe with MS clamps.
(60) All as per item No 59 described here in before but of size 50 sq mm 3½ core
(61) All as per item No 59 described here in before but of size 35 sq mm 3½ core
(62) All as per item No 59 described here in before but of size 25 sq mm 3½ core
(63) All as per item No 59 described here in before but of size16 sq mm 4 core
(64) All as per item No 59 described here in before but of size 10 sq mm 4 core
(65) All as per item No 59 described here in before but of size10 sq mm 2 core
(66) Supplly and replacement of GI tubing medium grade 50 mm bore galvanized with all fitting laid in trenches/road crossing for UG cable protection all as directed/specified.
(67) All as per item No 66 described here in before but 40 mm dia
(68) Straight through joints (epoxy) suitable for 3.5 core PVC insulated and PVC sheathed armoured LT underground cable 50-70 Sq mm with aluminium conductors including joint kits and labour complete for making joints all as specified and directed for following : -
(a) 3.50 core cable 25-35 Sq mm.Make-BM,Raychem or equivalent
(b) 3.50 core cable 10-16 Sq mm.Make-BM,Raychem or equivalent
(69) Demolition of Concrete of any description and in any position not otherwise specifically provided for
(70) M/L for preparation of old steel surfaces of LT Panel of any description, over 10cm in width or girth,not otherwise described and applying one coat of synthetic enamel paint complete all as specified and directed.Make-Asian,Duco,Nerolac synthetic enamel paint
(71) S & F in replacement MS chequered plate of size 5/6 mm thick cut to required size as per the size of cable duct all as specified and directed
(72) Removing the outdoor LT panel board and making the base of panel board with pcc and refixing the same panel on new pcc base with necessry fixing arrangement including disconnecting and reconnecting of LT cables and Earthings as directed by engineer-in-charge .(Earth work and PCC will be measured and paid seperately)
(73) Supply and fixing in replacement of off load Change over switch in sheet metal enclosure 4 pole 415 volts side handle operation along with fixing arrangements with suitable nut, bolts, washers, including terminating the incoming/outgoing cables with suitable aluminum lugs/ferruls with propper crimping and testing comlete all as directed by Engr-in-Charge for 200 Amps.Make-Havells,L&T,Simens
(74) Supply and fixing in replacement of off load Change over switch in sheet metal enclosure 4 pole 415 volts side handle operation along with fixing arrangements with suitable nut, bolts, washers, including terminating the incoming/outgoing cables with suitable aluminum lugs/ferruls with propper crimping and testing comlete all as directed by Engr-in-Charge for 320 Amps.Make-Havells,L&T,Simens
(75) M/L for cutting the bituminous road in the size not exc 0.4 mtr X 0.6 mtr for laying of UG cables and making good with the existing surfaces with PCC after laying the pipe/cable all as directed
(76) M&L in replacement steel tubular swaged poles swan neck complete with cast iron base plate,finial tapper plug, bolt,nuts & screws as specified type 410 SP-31 (9.0 metres long)
(77) S & F in replacement cross arms, bracing, support, clamps etc made out of mild steel channel or angle section of reqd size and shape including clamp, back plate with bolts, nuts & washers drilled for insulator bolts, welding, bending cold or hot in any shape or size including all fixing arrangement on HT over head line and painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified & as directed by Engr-in-Charge.
(78) Material and labour for Painting of LT steel tubular pole with one coat of alluminum paint and black paint upto 1.2 meter from the bottom of the pole after preparing the existing surface of the poles and marking the poles numbers as per existing pattern including fixing three no flouresent tape 50 mm width of three colour around the pole at 1.2 meter height complete all as per specified and directed.
(79) Fixing only MCCB any Capacity and any make only complete all as per site requirement or specified by Engr in Charge. ( Note item will be issued under Sch 'B' from department.)
(80) Labour for Laying only cable 10 Sqmm to 50 Sqmm 2/3/4 core completer all as per site requirement or specified by Engr in Charge. ( Note-1 item will be issued under Sch 'B' from department. 2. Excavation and Returning refilling and removal will be measured and paid seprately under respective item)
Commercial Traders
mayur enterprises
MV Engineers And Contractors
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .