Executive Engineer PWD Rnb division Leh
Office of the Executive Engineer Rnb division Leh
Re Construction of Deputy commissioner office Leh by way of external electrical and fire fighting work
2026_PWD_19024_1
E Tender 27 of R and B Division Leh
Open Tender
Electrical Works
45 days
LEH
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,000
Office of the Executive Engineer Rnb division Leh
₹1.6 L
4 Jun 2026
4 Jun 2026
10 Jun 2026
4 Jun 2026
9 Jun 2026
4 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1 | SITC OF MAIN LT/CAPACITOR PANEL Design, manufacturing, testing at works, supply, delivery at site including supervision during installation of the following extensible cubicle type indoor mounting, dead front, fully compartmentalised with hinged lockable detachable front & back openable, dust and vermin proof, floor mounting sheet steel clad switchboard fabricated out of 2 mm thick CRCA powder coated sheet steel suitable for use at 415 volts 3 phase 4 wire 50 cycle system and to withstand a symmetrical fault level of 50 KA at 415 volts. Panels shall be fabricated in easily transportable sections, length, height, depth etc. to match with site condition. All incomer breaker and Bus Couplers shall be interlocked electrically as shown in SLD drawing no. EL/SLD/01.The following provisions shall be required to be made in the Main LT Panel as detailed below:The Switchboards shall have provision to accommodate all cables from the bottom /top as required.All live accessible parts shall be shrouded with 1mm thick polycarbonate/3 mm thick FRP sheet and all equipment shall be finger touch proof. The busbar insulation shall be with heat shrinkable sleeves according to the colour code. SMC shrouds and busbar supports shall be used. All MCCB door handle shall be interlocked and lockable in OFF position.Galvanised hardware with zinc passivation shall be used in fabrication of Switchboards. Suitable Aluminium earth bus to be provided throughout the length of Switchboards.All indication lamps / illuminated push buttons shall be LED type.All incomer meters of Main LT Panel shall be multifunction & should have all the electrical parameters like Ampere, KW, KVAR, KWH, PF, Frequency etc.Coil of all motor starters shall be fed from 440 V / 230 V Control Transformer. MIMIC diagram shall be for Main LT panel as per below: MIMIC shall be made of polycarbonate sheet of 5 mm thickness fixed on acylic sheet of 2mm thick.the size of panel shall be such that the diagram can be visualized from 5 to 6 meter distance. The panel shall display complete single line diagram of Main LT Panel. this line diagram shall be made from luminous non fading materials to glow in dark and each breaker legend shall be provided with bi-colour LED lights to show the ON/OFF status of the respective feeder (Incomers / Bus couplers) 1 Nos. 800 Amps, 50KA, 433 volt 4-P Electrically operated draw out ACB complete with micro processor based tripping mechanism, shunt release (24V DC), earth fault release and inbuilt O/C & SC releases (Microprocessor based) having variable range with time lag facility to acheive discrimination. Required Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / operation scheme indicated in Drawing No.- EL/SLD/001. The ACB shall have suitable arrangement for termination by Al. Ar. XLPE Cables on incoming side for outgoing side termination by Bus Bar complete with following for each ACB: 1 Nos. 500 Amps, 50KA, 433 volt 4-P MCCB with micro processor based tripping mechanism, shunt release (24V DC), earth fault release and inbuilt O/C & SC releases (Microprocessor based) having variable range with time lag facility to acheive discrimination. Required Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / operation scheme indicated in Drawing No.- EL/SLD/001. The ACB shall have suitable arrangement for termination by Al. Ar. XLPE Cables on incoming side for outgoing side termination by Bus Bar complete with following for each ACB: | 1 | SET | 13,13,559.32 | ₹13,13,559.32 | item 01 |
DISTRIBUTION PANELS :- Design, manufacturing, testing at works, supply, delivery at site including supervision during installation of 2 mm thick MS sheet steel fabricated cubicle type Panel dust and vermin proof, fully compartmentalised complete with hinged and lockable doors . The Sheet Steel shall under go minimum eight tank treatment followed by finishing treatment of powder coating with 70 micron minimum thickness. All the panels shall be floor mounted and dead front construction complete with interconnections. Protection of Distribution Panel Shall be IP-42. Also refer SLD Drawing No. EL/SLD/02. All live accessible parts shall be shrouded with 1mm thick polycarbonate/3 mm thick FRP sheet and all equipment shall be finger touch proof. The busbar insulation shall be with heat shrinkable sleeves according to the colour code. SMC shrouds and busbar supports shall be used. All MCCB door handle shall be interlocked and lockable in OFF position.Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required. (Bus Bars)Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 250 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.1 Nos. 63A TPN MCB 1 Nos. 100A TPN MCCB of 16 KA breaking capacity.of 10 KA breaking capacity. GROUND & FIRST FLOOR PANEL as described above .Electrolytic high conductivity aluminium three phase and neutral busbars rated at 1000 amps, 50 KA, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp. Neutral Bus Bar shall be 50% of Phase Bus Bar with providing Potential transformer for outgoing metering.All outgoing feeders shall be provided with RYB Phase Indication Lamp with MCB as backup protection & Dual Energy Meter with CT as required | 2 | SET | 2,11,864.4 | ₹4,23,728.8 | item 02 | |
SECOND FLOOR PANEL Incoming:1 Nos. of 160 Amp FP MCCB of 25 KA breaking capacity. Metering for incoming:Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required.Phase indicating lamps RYB with 6 Amps SP MCB back up.ON/OFF/TRIP Indicating Lamp with 6 Amps SP MCB back up. Bus Bars: Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp. Outgoings 3 Nos. 63A TPN MCB of 10 KA breaking capacity. SPARES 1 Nos. 100A TPN MCCB of 16 KA breaking capacity. 3 Nos. 63A TPN MCB of 10 KA breaking capacity. | 1 | SET | 1,86,440.67 | ₹1,86,440.67 | item 03 | |
LIFT PANEL panel UPS INPUT PANELIncoming:1 Nos. of 100 Amp FP MCCB of 25 KA breaking capacity. Metering for incoming:Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required.Phase indicating lamps RYB with 6 Amps SP MCB back up.ON/OFF/TRIP Indicating Lamp with 6 Amps SP MCB back up. Bus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 125 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Outgoings 2 Nos. 63A TP, ELCB of 25 KA breaking capacity.2 Nos. 40A DP MCB of 10 KA breaking capacity.SPARES 1 Nos. 63A TP, ELCB of 25 KA breaking capacity.1 Nos. 40A DP MCB of 10 KA breaking capacity.LIFT PANEL as described above . | 1 | SET | 88,983.05 | ₹88,983.05 | item 04 | |
UPS INPUT PANEL .Incoming:1 Nos. of 160 Amp FP MCCB of 25 KA breaking capacity.Metering for incoming:Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required.Phase indicating lamps RYB with 6 Amps SP MCB back up.ON/OFF/TRIP Indicating Lamp with 6 Amps SP MCB back up.Bus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Outgoings01 Nos. 50 KVA, UPS (30 MINUTES BACKUP BATTERY BANK)01 Nos. 50 KVA, UPS (30 MINUTES BACKUP BATTERY BANK)UPS INPUT PANEL as described above . | 1 | SET | 1,27,118.64 | ₹1,27,118.64 | item 05 | |
UPS OUTPUT PANEL Incoming:1 Nos. of 100 Amp FP MCCB of 25 KA breaking capacity.1 Nos. of 32 Amp FP MCB of 10 KA breaking capacity.Metering for incoming:Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required.Phase indicating lamps RYB with 6 Amps SP MCB back up,for all incomer ON/OFF/TRIP Indicating Lamp with 6 Amps SP MCB back up,for all incomer Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Outgoings 4 Nos. 40A DP MCB of 10 KA breaking capacity.3 Nos. 16A DP MCB of 10 KA breaking capacity.SPARES 1 Nos. 16A DP MCB of 10 KA breaking capacity.UPS OUTPUT PANEL as described above | 1 | SET | 1,27,118.64 | ₹1,27,118.64 | item 06 | |
EXTERNAL LIGHTING Supplying & fixing of following accessories in the existing cubical panel board / feeder pillar including connection testing etc. as reqd.Supplying, fixing, connecting, testing and commissioning of Astronomical Timer along with power contactor 3 set of Double pole of 32 Amp. in the existing cubical panel board / feeder pillar (Timer shall be capable to operate 3 nos double pole Power contactor seprately to operate at different time schedule), complete in all respects. The above board shall be complete with 3 nos. phase indicating lights, flush mounted Ammeter, Voltmeter, CT's, PT's, selector switches, protective fuses etc. at Incomer with all interconnections by min. 2.5 sq.mm. Copper wires.Danger notice plateBUS BAR : 40 AMP, 500 Volts, 3 phase 50 HZ FP high conductivity electrolytic Aluminium bus bar. The current density of bus bar shall be minimum 1.00 sq mm / amp. OUT GOINGS : 15 nos. 6-32 AMP DP MCB (10 KA) OUT GOINGS : 15 nos. 6-32 AMP DP MCB (10 KA)OUT 3 Nos 40 AMP DP MCB (10KA) | 1 | SET | 1,05,932.2 | ₹1,05,932.2 | item 07 | |
ONLINE UPS & BATTERY BANK Supply, installation, testing and commissioning of 50 kVA UPS, 3 phase (415 V + 15%) Volts input & 3 phase output (440 V + 1%), 50 Hz, 100% IGBT inverter & converter, Input harmonic Current THD 3% typical at 100% load, 6% maximum at 50% load and 30 min battery backup for UPS along with battery cabinet complete in all respect including supporting steel structure for UPS and Battery as required. Quoted price shall be inclusive of approved rating single core copper conductor cable connecting UPS and batteries. (ALONG WITH BYPASS ARRANGEMENT) | 1 | SET | 5,50,847.45 | ₹5,50,847.45 | item 08 | |
Supply ,installation , testing and commissioning of 3 kVA Pure Sine Wave Inverter system for a constant secondary voltage of 220 volts at 50 Hz, single phase, batteries backup of minimum 90 Minutes back up duration including, batteries, battery chargers, rectifiers, transformers, controls, protection and instruments , trolley etc complete as required. (ALONG WITH BYPASS ARRANGEMENT) | 1 | SET | 1,01,694.91 | ₹1,01,694.91 | item 09 | |
SUPPLY OF HT / LT CABLES Supply,Receiving, laying, installation, testing and commissioning of following sizes of 11 KV (E) grade XLPE insulated, aluminium conductor, armoured power cables conforming to IS : 7098 (Part-I) laid in Existing Hume / DWC pipe in an approved manner complete as required and as per specifications including complete as required as per IS 1255 as required. (Necessary end sealing when cables laid in hume pipe shall be done by contractor) 3C X 240 sq. mm | - | RM | 3,347.45 | - | item 10 |