Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹5.1 LAccepted-Finance 306 3RD FLOOER ALMASH TOWER VIDHAN MARG LUCKNOW LUCKNOW UTTAR PRADESH 226013 | LUCKNOW | UTTAR PRADESH | 226013 | 1 | Accepted-Finance L-1 | |
| 2 | 2₹6.5 L+₹1.4 L (26.7%)Accepted-Finance | 2 | Accepted-Finance L-2 | |
| 3 | 3₹6.5 L+₹1.4 L (27.9%)Accepted-Finance | 3 | Accepted-Finance L-3 |
Tender Value
₹5.3 L
EMD Value
₹5,500
Closing Date
18 Jul 2025, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE
ETC-II, UPPTCL, PAARESHAN BHAWAN, VIBHUTI KHAND, GOMTI NAGAR, LUCKNOW-226010
WORK
2025_UPTCL_1050765_1
Very Short Term E-Tender No. ETC-II/L/27/2025-26
Open Tender
Electrical Works
Item Rate
30 days
ETD
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE, ETC-II, UPPTCL, LUCKNOW
₹5,500
29 Jul 2025
21 Jun 2025
19 Jul 2025
21 Jun 2025
18 Jul 2025
21 Jun 2025
Amount
1- Online Testing to be conducted on Transformer:- (A) 1- On line Partial Discharge Measurement. 2- Thermography Measurement. 3- Noise Level Measurement. 4- Vibration Level Measurement. 5- Oil Test (NABL Approved Lab): (i)- General oil test as per IS 1866:2000 (Resistivity, Tan Delta, BDV, Water PPM, IFT, Acidity, Flash point & Sludge content) (ii) DGA as per relevant IEC (iii) Furan analysis 2- Online Testing to be conducted on Transformer:- (i)- Capacitance & ten Delta of Bushing & Windings. (ii)- Turn Ratio at each taps. (iii)- Vector Group test. (iv)- Short Circuit Impedance test. (v)- Magnetizing current on each tap. (vi)- Magnetic balance test. (vii)- Winding resistance at all taps. (viii)- IR & PI Test. (ix)- Sweep frequency response analysis test & Mechanical assessment. (x)- Frequency response on stray loss test (FRSL). (xi)- Leakage Reactance & Impendence measurement. (xii)- Dynamic Contact resistance test for OLTC performance check. (xiii)- Moisture assessment & Dielectric analysis of winding insulation (FDS measurement). Note- 1. All testing equipment (with latest calibration from NABL lab) will be provided by the contractor. 2. Cost of transportation for Oil samples & shifting equipment of all testing equipment will be in the scope of the contractor. No extra payment will not be allowed. 3. Petty or sub-contracting will not be allowed. 4. Contractor should have own NABL approved lab.
132 KV S/S Bangarmau, Unnao
132/33 KV 40 MVA Transformer-II (M/s Alstom Make, Mfg. 2000)
132/33 KV 20 MVA Transformer (M/s NGEF Make, Mfg. 1984)
132 KV S/S Bighapur, Unnao
132/33 KV 40 MVA Transformer (M/s EMCO Make, Mfg. 2002)
Gupta Elect and Engg Works (BID ID -5353800)
Perfect Power Transformer Associates (BID ID -5353821)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .