Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.9 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹22.8 L+₹3.1 L (16.0%)Rejected-AOC | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | L3₹24.0 L+₹4.3 L (21.9%)Rejected-AOC 0 MANPUR CHITBARAGAON CHITBARAGAON BALLIA UTTAR PRADESH 221713 | BALLIA | UTTAR PRADESH | 221713 | L3 | Rejected-AOC Other than lowest bidder | |
| 4 | Rejected-Technical | - | Rejected-Technical Adverse remarks in WLR Sep 2020 |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
12 Feb 2021, 6:00 pmClosed
CWE Rajouri
HQ CWE Rajouri PIN-900129 C/o 56 APO
REPAIR TO HT OH LINES, TRANSFORMERS AND HT SWITCH GEAR AT ZONE A UNDER GE 862 EWS
2021_MES_412467_1
CANO-CWE/RAJ-59/2020-21
Open Tender
Support/Maintenance Service
Item Rate
180 days
AOR of GE 862 EWS
Class D Category b(ii)
9 documents required · 9 mandatory
₹500
GE 862 EWS
₹60,000
Yes
25 Mar 2021
14 Jan 2021
15 Feb 2021
14 Jan 2021
12 Feb 2021
28 Jan 2021
Amount
Filtration & dehydration of transformer oil in distribution transformer, servo voltage stabilizers, isolation tramsformer and HT OCBs (at different locations) using ON-LINE electrically operated filtration plant to achieve dielectric strength minimum 50 KV / 4mm including testing of oil before and after dehydation and also topping up of the transformer oil upto required level, complete all as specified and directed. Note:-(i)Transformer oil supplyng and top-up shall be measured and paid separately. (ii) The quoted rates shall also be deemed to include for submission of test reports for testing as specified above (iii) Quantity payable under the item shall be the Qty of oil filtered and dehydrated at site only.
Supply only transformer oil conforming to IS 335-1993 (Make : 'Savita', 'Power Oil', APAR) having di-electric strength minimum 50 KV/4mm, complete all as specified and directed.
Disconnecting of LT and HT connection carefully from the existing Transformer of capacity 50 KVA to 100 KVA , 11KV/433 volts of any make/type, taking down/remove from existing site. Transporting the transformer from various locations to the workshop for carrying out repair work, opening of top cover and decanning of transformer oil, checking of connections internally,dismantling of core and remove HT/LT coil for replacement, replacing burnt HT and LT bushing and studs and soldering and brazing the connections including removal of sediments, carbon deposits at bottom of transformer tank, on core, on winding, tightening of all connections etc, cleaning of oil tank and rectification of leakage problem and renewal of all gaskets and assembling and filling back of tranformer oil (after filtration and dehydration of transformer oil at work shop for required value) including top up of transformer oil upto required level and after repair the transporting the same back to the same site including installation and connecting of HT and LT side connection of transformer and charging the transformer including testing it
upto proper functioning complete all as specified and directed by Engineer-in-Charge. Note : (i) The contractor will take down and refix the transformer at site located at various location as directed by Engineer-in-charge. (ii) The rate deemed to including transportation of transformer Jammu workshop and back. (iii) T & P required for taking down and refixing of transformer deemed to be included in the rate quoted by contractor, Rewinding of HT & LT coils and oil shall be measured and paid separately under erlevant items and cost of gaskets, nuts and bolts etc. will be deemed to be included in this above item quoted rate. (iv) Repair/rewinding of transformer carried out by authorized workshop only. (v) Spare parts required for maintenance measured and paid separetely in respective items. (vi) Transformer oil for top up will be measured and paid separately.
All as per serial item No 03 above but for transformer of capacity more than 100 KVA and upto 315. KVA complete all as specified and directed.
Replacement of burnt defective HT copper coil of different type capacity winding from transformer with and including superior quality enamelled copper winding wire of approved make of suitable size/guage and number of turns matching as per original winding of transformer including all insulating papers and material required for making of coil all as specified and directed by Engineer-in-Charge.
Replacement of burnt defective LT copper coil of different type capacity winding from transformer with and including superior quality enamelled copper winding strips of approved make of suitable size/guage and number of turns matching as per original winding of transformer including all insulating papers and material required for making of coil all as specified and directed by Engineer-in-Charge.
Brass terminal studs and bushing with brass check nuts including all accessories for primary (HT) side of transformer capacity 250 KVA to 315 KVA, 11KV/433 volts of any make/type including removing of old unserviceable items and testing complete all as specified and directed. Note:- This item shall not be applicable for item No 3 & 4 above.
Brass terminal studs and bushing with brass check nuts including all accessories for primary (HT) side of transformer capacity 50 to 200 KVA, 11KV/433 volts of any make/type including removing of old unserviceable items and testing complete all as specified and directed. Note:- This item shall not be applicable for item No 3 & 4 above.
Brass terminal studs and bushing with brass check nuts including all accessories for secondary (LT) side of transformer capacity 250 KVA to 315 KVA , 11KV/433 volts of any make/type including removing of old unserviceable items and testing complete all as specified and directed. Note:- This item shall not be applicable for item No 3 & 4 above.
Brass terminal studs and bushing with brass check nuts including all accessories for secondary (LT) side of transformer capacity 50 to 200 KVA, 11KV/433 volts of any make/type including removing of old unserviceable items and testing complete all as specified and directed. Note:- This item shall not be applicable for item No 3 & 4 above.
Servicing and maintenance of HT VCB 800 Amps, one incoming-four out going panel including cheking of contacts, lubrication of mechanism, cleaning, tightening , Insulation resistance test for existing rated HT beaker. Tightening of all control wiring panel,repair to manual/electrical closing/trippping. Opening of panel back covers, removing of Bus bar, removing of PT, removing of CT's, cleaning of all bus bar , CT chamber and heating up chamber to remove moisture pressure test with pressure test kit.complete testing of breaker, checking mechanism of fixed and moving contacts and removing carbon deposits and overhauling of spring charged mechanism and operation of indicators are correctly showing the ON/OFF and spring charged / discharged system, cleaning the surfaces of insulators, fasten the bolts fixed in interrupting units, mechanism linkages, replacing all unserviceable parts/mechanism etc. lubricating and greasing the mechanism of moving parts and reparing of trip push button assembly including testing and calibration of protection relays and reconnecting back the VCB and testing complete all as specified and directed. Contd to item No-11.01....
Note:- The quoted rates shall also be deemed to include for submission of test reports for testing as specified above.
Servicing and maintenance of HT OCB 800 Amps, one incoming and four outgoing panel including checking of contacts, lubrication of mechanism, cleaning, tightening , Insulation resistance test for existing rated HT breaker . Tightening of all control wiring panel,repair to manual/electrical closing/trippping. Opening of panel back covers, removing of Bus bar, removing of PT, removing of Ct's, cleaning of all bus bar , CT chamber and heating up chamber to remove moisture pressure test with pressure test kit.complete testing of breaker ,checking mechanism of fixed and moving contacts and removing carbon deposits and overhauling of spring charged mechanism and operation of indicators are correctly showing the ON/OFF and spring charged / discharged system, cleaning the surfaces of insulators, fasten the bolts fixed in interrupting units, mechanism linkages, replacing all unserviceable parts/mechanism etc. lubricating and greasing the mechanism of moving parts and reparing of trip push button assembly including testing and calibration of protection relays and reconnecting back the Contd to item No-12.01.......
OCB and testing complete all as specified and directed. Note:- (a)The quoted rates shall also be deemed to include for submission of test reports for testing as specified above. (b) Draining, refilling and filtration of oil for required value is deemed into quoted rates.
PCC 1:4:8 (nominal mix) type D-2 using 40mm graded crushed stone aggregates, as in foundation filling and mass concrete for poles and stay assembly /installation paths or similar location, complete all as specified and directed.
Brick work with sub class ‘B’ bricks straight or curved on plan exceeding 6m mean radius built in cement mortar 1:6, complete all as specified.
15mm thick cement plaster rendering in CM 1:4 on fair faces of bricks or concrete surfaces & finishing the surface even and smooth without using extra cement, complete all as specified.
PCC (1:3:6) type C1 using 20 mm graded crushed stone aggregate for coping on brick walls, ducts etc including necessory form work, complete all as specified and directed
Precast RCC (1:2:4) type B1 using 20 mm graded aggregate (factory made), smooth finish, flush handle, cover slabs cum including form work, laid dry in position, all as specified and directed. Note :- Reinforcement (TMT bars) will be measured and paid separately.
PCC 1:2:4 (nominal mix) type B-1 using 20mm graded crushed stone aggregate, as in coping of poles and the like complete including weathering, slightly rounded or chamfered angles and throating, all as specified and directed.
PCC 1:3:6 (nominal mix) type C-2 using 40mm graded crushed stone aggregates, as in foundation filling and mass concrete for poles and stay / installation paths complete all as specified and directed.
Mild steel bars (TMT Bars) 10mm dia and over, cut to length, bent to shape required, including cranking, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips all as specified and directed.
Synthetic insulating mat of 2 mtr x 1mtr x19 mm thick fixed in repairs, complete all as specified and directed.
Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections conforming to Fe-290 Gde E-165 including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed with and including of one coat of red oxide primer and two coats of aluminium paint including preparation of new steel steel surface, all as specified.
Rolled mild steel plates chequered channels, Fe 410-W (Grade-E-250 ) quality ''A'' square/rectuangular cut or notched (ordinary and counter sunk) forming holes, with out any attachment , of appropriate size of cable duct all as specified and directed by Engineer-in-Charge.
Painting of HT 4 pole structure consisting of steel tubular poles, bracing, cross arms, channels,clamps, supports, nuts, bolts with & including two coats of Silver paint over a coat of red oxide primer after preparing the existing external surfaces and marking of nomenclature of pole with black paint and including making alternate strips each of 30 cm height with black and red with synthetic enamel paint upto 1.20 mtr height from top of PCC copping, complete all as specified and directed.
Painting of HT two pole structure consisting of steel tubuler poles and connected steel sections such as bracing, cross arms, channels, supports, clamps , nuts , bolts of any type with & including two coat of aluminium paint over a coat of red oxide primer after preparing the old painted external surfaces and marking of nomenclature of pole with black paint and including making alternate strips each 30 cm with black and red with synthetic enamel paint upto 1.20 mtr height from ground level complete all as specified and directed .
HT Danger notice plate of size 25x20 cm made cut of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with and including M.S. clamps, bolts and nuts of approved size fixed in repairs, complete all as specified and directed.
11 KV air break gang operated device of rating 400 amps, 3 Pole, vertical type, mechanically operated,mounted on and including 11 KV porcelain insulators and steel frame with operating machanism worked from ground level with and including GI tubing 25 mm bore light grade and providing ACSR conductor jumpers duly crimped with lugs, connected to existing 11 KV supply and testing and including removing old unserviceable items complete all as specified and directed.
33 KV air break gang operated device of rating 400 amps /600 amps , 3 Pole, horizontal mounting, mechanically operated,mounted on and including 33 KV porcelain insulators and steel frame with operating machanism worked from ground level,copper flat terminals, connected to existing 33 KV supply and testing and including removing old unserviceable items complete all as specified and directed.
High tension lightning arrestor, expulsion type suitable for 11 KV with all fittings of transmission class, discharge capacity 65 Kilo Amps and testing including removing old unserviceable item, complete all as specified and directed.
High tension lightning arrestor, expulsion type suitable for 33 KV with all fittings of transmission class, discharge capacity 65 Kilo Amps and testing including removing old unserviceable item, complete all as specified and directed.
Drop out fuse unit expulsion type for outdoor air break gang operated switch, single pole, mounted on and including insulators for 11 KV working pressure, fixed to and including channel with nuts, bolts and washers etc,synthetic bounded fuse carrying tube with line taps and suitable for current carrying capacity 25 Amp to 50 Amp, testing including removing of old unsv items, complete all as specified and directed. Note for Item Nos 27 & 28 : Steel work (channels for GOD) for installation of above items to Pole(s) shall be measured and paid separately.
Earthing complete with galvanised steel earth plate electrode 600mmX 600mmX 6mm thick buried directly in ground vertically ( earth pit not less than 2.25 metres deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including galvanised iron strip of size 32 X 6 mm from earth electrode to test point or up-to 7.5mtr whichever is less by means of GI bolts, nuts, check nuts and washers all as per electrical plate no 3 of SSR Part-I provision of G I Pipe 40mm bore light grade for protection of GI strip and GI watering pipe of 20 mm bore medium grade, GI funnel with wire mesh, including char-coal, salt packed all around the earth electrode plate in layers, PCC earth pit chmaber of size 30cmx30cm made of 1:3:6 type C1, with suitable handle, angle iron made of frame out of angle iron of size 40x40x4 mm, excavation, earth work in any type of soil and returning filling, removal of surplus soil and testing for required value including taking down old unsv earthing, complete all as specified and directed.
Supply and erecting in true vertical position steel tubular swaged pole, 11 metre long, complete with mild steel base plate 6mm thick of size 300mm x 300mm, B-118 finial taper plug, bolts, nuts, washers and screws, type 410 SP-55 including drilling of holes of required size and nuts for fixing of cross arms, painting with two coats of aluminium paint over a coat of red oxide and two coats of black bituminous paint for portion embedded in concrete, painting five black and white alternate bands at lower portion of pole each of 300 mm height at 300mm spacing including taking down of old existing broken/cracked pre stresed concrete pole 11 metres long complete all as specified and directed. (Note : Excavation, earth work and PCC in foundation of poles, coping etc shall be measured and paid separately under respective items of Sch 'A').
Stay assembly complete with accessories and GI stay rod 20 mm dia 1900 long, stay plate 300mm x 300mm x 6mm, galvanised thimbles, GI stay wire 7/4 SWG, galvanised steel 14mm dia 400mm long stay bow and GI nuts, washers including loop type insulators, vitreous porcelain, white brown or green of large size with overall dimensions 90mm x 140mm, clearance of hole 25.5mm, etc and all other accessories as shown in electrical plate No 1 on Ser Page No 495 of MES Schedule Part-I (2009) complete including dismantling stay assembly complete all as specified and directed. Note : Stay clamp, stay wire, excavation and earth work and concrete for stay pit shall be measured and paid separately.
Disc type insulators, porcelain vitreous white brown or green, 145 mm high and 255mm dia ball and socket type, two-in-series assembly for tension with tension clamps for conductor having working pressure 11000 Volts including taking down existing cracked/unserviceable disc type insulator complete all as specified and directed.
Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut 150mm height, 150mm dia for working pressure 11000 Volts grade of HT line including taking down existing cracked/unserviceable pin type insulator, complete all as specified and directed.
Disc type insulators, porcelain vitreous white brown or green, 145mm high and 255mm dia ball and socket type, single disc assembly for tension with tension clamps for conductor having working pressure 11000 Volts including taking down existing cracked/unserviceable disc type insulator, complete all as specified and directed.
Cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia including taking down old unserviceablecradles, complete all as specified and directed.
Synthetic insulating mat of size 2m x1m x 25 mm thick all as specified and directed.
Fibre glass discharge rod 11 KV complete all as specified and directed. Make:- Jaipuriya or equivalent makes as approved by GE.
Fibre glass discharge rod 33 KV complete all as specified and directed. Make:- Jaipuriya or equivalent makes as approved by GE.
Eectrical rubber hand gloves 11 KV complete all as specified and directed. Make:- Jaipuriya or equivalent makes as approved by GE.
Eectrical rubber hand gloves 33 KV complete all as specified and directed. Make:- Jaipuriya or equivalent makes as approved by GE.
Aluminium conductor, steel reinforced (ACSR) of following sizes as in overhead conductor including fixing aluminium tapes for binding including dismantling of old conductor of any size and capacity complete all as specified and directed: - (a) 6/1 x 3.0 - Ferret (b) 6/1 x 2.59 - Weasel (c) 6/1 x 2.11 - Squirrel Note: The weight of the conductor shall be determined as stipulated in Preamble (b) on Page 406 of SSR-2010 Part-II (Rates).
HT cable 11 KV grade, XLPE insulated (earthed) screened, PVC bedded, galvanized iron strip armoured with stranded aluminium conductor cable of cross sectional area 120 sqmm; 3 core, ISI marked with IS:7098 (part-II) as amended upto date in trenches/ ducts/ through pipes etc and making connection by providing suitable aluminium lugs with proper crimping, including removal of old unserviceable defective cable of any size and capacity including testing complete all as specified and directed Note :- (i) Excavation & Earth work,sand cushioning, cable cover and protection pipe shall be measured and paid separately. (ii) The cable shall be in one length unless otherwise directed by the GE.
Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with and including jointing material and accessories suitable for 3 core XLPE armoured aluminium cable of size 120 Sqmm, also including connecting with single thimbles etc after disconnecting of electric supply including removing burnt out jointing kit etc, complete all as specified and directed.
Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrinkable type joint, complete with and including jointing material and accessories suitable for 3 core XLPE armoured aluminium cable of size 120 Sqmm, also with and including connecting single thimbles etc after disconnecting of electric supply including removing burnt out jointing kit etc, complete all as specified and directed.
Cable jointing kit for 11 KV (earthed) grade cable for straight through heat shrinkable type joint, complete with and including jointing material and accessories suitable for 3 core XLPE armoured aluminium cable of size 120 to 180 Sqmm, also with and including connecting single ferrules/thimbles etc after disconnecting of electric supply including removing burnt out jointing kit etc, complete all as specified and directed.
Unreinforced precast factory made concrete cable cover, class HV, Type -I, flat, size 300 mm x 180mm x 40mm,ISI marked complete all as specified and directed.
GI tubes, "light grade", 100 mm bore with and including all fittings laid in trenches/road crossing/floors etc for cable protection, complete all as specified and directed. Note: Excavation and earth work shall be measured and paid for separately.
Excavation in trenches not exceeding 1.5 mtr wide and not exc 1.5 mtr depth for laying of cables, pipe lines, protection pipes and foundations etc and getting out in any type of soil, complete all as specified and directed.
Returning filling in soil including spreading leveling watering and well rammimg in layer n exc 25 cm complete all as specified and directed.
Removing excavated soil not exc 50 mtr ant depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
Dry sand cushioning to UG cable 8 cm thick before laying and 15cm thick after laying complete all as specified and directed. Note:- 1.Dry fine sand of best available quality shall be used. 2.Punned thickness shall be made and paid.
Mild steel angle iron cut to shape as directed drilling holes notching for wire as in posts and struts in fencing etc including all necessary cutting and welding etc,including locking arrangement and for similar work complete all as specified.
Mild steel screw bolts (machine cut) with hexagonal or square heads at one end and srewed the other or screwed both ends each screwed end to be fitted wth washers and one hexagonal or square not exceeding 5 cm long and diameter of neck 5 to 10mm complete all as specified.
Supply only Chain link fencing 4mm dia of 100mm mesh size complete all as specified and directed.
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc including provision of binding wire complete all as specified and directed.
Rough excavation , not exceeding 1.5 m deep and getting out in any type of soil complete all as directed by Engr-in-charge.
Hard core of broken stone/boulders of gauge n exc 63mm deposited spreed and leveled in layers n exc 15cm thick watered and rammed to a true surface, complete all as specified.
Galvanised stay wire stranded 7/4 mm complete all as specified
Jiwan Singh
NATIONAL TRADING COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .