Loading…
Loading…
Tender Value
₹2.5 Cr
EMD Value
₹2.7 L
Closing Date
27 Jan 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
TENDER ELG
14 conditions · 2 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less where V= Advertised value of the tender in crores of Rupees, N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.(In this connection scanned copy of Annexure VIB duly filled up must be attached with offer).
The tenderer must have successfully completed any of the following during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: Three similar works costing not less than the amount equal to 30% of advertised value of the tender, or Two similar works costing not less than the amount equal to 40% of advertised value of the tender, or One similar work costing not less than the amount equal to 60% of advertised value of the tender .Other terms and conditions shall follow of GCC, April 2022. Definition of Similar nature of work has given below (1.1)
Defination of Similar Work :- As per CEE's letter No. EL/112/0/KM, dated 22.08.2013 Item Sl. 1.4. under "HT Electrical Works" : "Design, manufacture, supply, erection, testing and commissioning of 11 KV or above sub- station with HT panel complete or a part of it with or without APFC panel", Item Sl. 1.5.: "Repair/overhauling/supply, installation, testing & commissioning (SITC) of HT/LT transformer, HT/LT switchgear, HT/LT cables, HT/LT panels". OR Item Sl. 2.1. under "LT Electrical Works" : "Design, manufacture, supply, installation and commissioning of LT panels complete with earthing arrangements and associated electrical works". O R Sl 5.1 under "Works of Air-conditioning system" : "Supply, installation, testing and commissioning of window/Split Air- Conditioner/Package type/Water Coolers/Bottle Coolers/Deep Freezer/Refrigerators with or without AMC".
13 conditions · 4 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The following documents should be attached with the tender: (i)Scanned copy of Pan Card. (ii)Scanned Copy of EFTMANDATE FORM .Duly filled up by the bidder(iii)Tender Document (duly digitallysigned by the bidder)
Scanned copy of valid GST (Goods & Service Tax)Registration Certificate.
Scanned copy of valid Trade license or Propitorship Certificate.
List of the Works completed in the last three financial years giving description of work. Organization for whom executed, approximate value of contract at the time of award, date of award and date of scheduled completion of work. Date of actual start, actual completion and date of payment and final value of contract should also be given. (Supportive documents/ certificates from the organization with whom worked/are working should be enclosed) (Please attach scanned copy of Annexure-I duly filled up).
Railway Officers Associated with tenderer: RAILWAY OFFICERS ASSOCIATED WITH TENDERER 1. Ex Railway Officer as tenderer: Should tenderer be a retired Gazetted Officer working before his retirement on any of the Railways owned and administered by the President of India, or should the tenderer being partnership firm have as one of its partners a retired Gazetted Officer as aforesaid, or should the tenderer being an incorporated company have any such retired Officer as one of its Directors, or should the tenderer have in his employment any retired Gazetted Officer as aforesaid, full information of such person shall be submitted along with his tender in the format given in annexure-VI to this chapter of this tender document. (Authority: ACS No.3 to GCC July,2014vide Boards letter No.2014/CEI/CT/O/9/RET dt.22.01.2015)(please attach scanned copy of Annexure-VI duly filled up by the firm).
Option for receiving payment through Letter of Credit . (Please attach scanned copy of ANNEXURE 1 LC & ANNEXURE 2 LC duly filled up by the firm if opted for)
List of works in hand indicating Supportive documents/certificates from the organization with whom worked/are working should be enclosed) description of work, contract value, approximate value of balance work yet to be done and date of award. (Supportive documents/certificates form the organization with whom worked/are working should be enclosed).(Please attach scanned copy of Annexure-IV duly filled up)
The following documents should be attached with the tender ( Annexure-V (A) certificate is to be given by attorney/authorized signatory/each member of Partnership firm/Joint Venture (JV) / Hindu Undivided Family (HUF) / Limited Liability Partnership (LLP) etc. & Scanned copy POA/Partnership deed is to be uploaded Duly filled up by the bidder
Partnership deeds, power of Attorney etc. (if any) : The tender shall clearly specify whether the tender is submitted on his own or on behalf of a partnership concern. If the tender is submitted on behalf of partnership concern he should submit the certified copy of the partnership deed along with the tender authorisation to sign the documents on behalf of the partnership firm. If these documents are not enclosed along with the tender document, the tender will be treated as hearing lease submitted by the individual signing the tender documents. The Railway will not consider any power of Attorney granted by the tender or any changes in the composition of the firm made subsequent to the execution of the contract. It may however recognize such power of Attorney and change after obtaining proper legal advice, the cost of which will be chargeable to the contract.(Scanned copy POA/Partnership deed is to be uploaded Duly filled up by the bidder. As per clause no. 14(e) of GCC'22, the following documents to be uploaded in terms of Company registered under Companies Act2013: (i) The copies of MOA (Memorandum of Association) / AOA (Articles of Association) of the company (ii) A copy of Certificate of Incorporation (iii) A copy of Authorization/Power of Attorney issued by the Company (backed by the resolution of Board of Directors) in favour of the individual to sign the tender on behalf of the company and create liability against the company. (iv) All other documents in terms Para 10 of the Tender Form (Second Sheet) above.
The Contractor/(firm) must go through the entire tender document along with all attachment for any kind of guidance regarding execution of the job & payment there after. In case any thing is left out or not clear then they should consult the General Condition of Contract & standard Specification as attached (uploaded ).The bidders are also advised to preserve a copy of entire tender document/ (Set) for their convenience.
Submission of Documents in support of Eligibility Criteria : All documents in support of fulfillment of eligibility criteria with respect to completion of 'Similar Nature of work for technical Eligibility criteria 'and 'Total Contract value for Financial Eligibility Criteria' should be uploaded online in the website with scanned copy at the time of tender bidding with the details. No post - tender communication , in any form will be made or entertained , after opening of tenders in this regard .Railways may however call for the originals of the credentials for verification or any clarifications/Confirmations on the contents of the documents submitted .Eligibility of tenderers shall be decided solely on the basis of the documents submitted alongwith the tender offers and any subsequent document whatsoever submitted in this connection would not be given any cognizance on any account.
Installation & Commissioning of new RRI Indoor equipment and outdoor at HWH / RRI in connection with remodelling of yard and extension of PFs.
EL-HWH-25-21-3397-R~ER
EL-HWH-25-21-3397-R
Open
Works - General
180 Days
Howrah, West Bengal
₹0
₹2.7 L
27 Jan 2026
5 Jan 2026
13 Jan 2026
159 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 2,45,49,293 | ||
| — | — | — | 15,68,000 | ||
| Supply of Outdoor Units : 72 HP Installation,Testing and Commissioning of Hi efficient DC Inverter Side/Top discharge VRF Outdoor units equipped with Variable refrigerant flow system (Heating & Cooling ), comprising Inverter driven Scroll Compressor with a wide range of frequency from 15 to 120rps (R-refrigeran tgas). All the unit shall be provided with micro-processor based control advance refrigerant control, Liquid back flow protection, precise oil control techno- -logy, 3ph DC motor condenser fan motor ,sub cooling through dual tube heat exchanger & vari- -ous electrical protection like-phase sequence, high/low voltage protection, compressor overload protection, temperature & pressure protection. Nominal Capacity : 18 HP ( Make : O General / Fujitsu-General / Mitsubishi Electric / Panasonic / Samsung / Carrier / Toshiba / LG / Hitachi / Trane / Voltas ) | — | 4.00 | — | — | |
| — | — | — | 22,71,200 | ||
| Supply of Indoor unit : Installation, Testing and commissioning of Floor Mounted AHU with double skin air handling units made of 50mm thick panels consisting of pre- plasticized G.I. casing of 0.8mm outside layer and 0.6 mm inside layer with polyurethane foam (PUF) insulation of minimum 40 kg/cum density factory injected between them by injection mould- -ing machine, complete with DIDW backward/ forward curve SA blower section with blower suit- -able for static pressure of 50mm WG, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick washable synthetic type air prefilters having efficiency 90% with belt drive package,drain connections & drain valve stainless steel (18G) drain pan with PUF insulation, necessary vibration isolation arrangement, canvas conn- - ection etc. complete as per specification and of following outdoor mounted thermal k sand witched puf insulation, fan section with TEFC EFF 1 motor, limit switch, emergency light, guard for inspection door, mixing box, return damper, fresh air damper, outlet damper, view- -ing glass etc. All dampers shall be of alluminium aerofoil blade damper. AHU should be compatible with R410A Refrigerant DX Type Coil with AHU Stater Panel. ( Make : Zeco / Edgetech / Waves ). AHU Capacity : 11500 CFM(28TR), Static pre- -ssure of Blower : 65MM | — | 2.00 | — | — | |
| — | — | — | 1,48,800 | ||
| Supply, installation, testing and commissioning of AHU Electronic Expansion Valve (EEV) Kit | — | 8.00 | — | — | |
| — | — | — | 23,200 | ||
| Supply, installation, testing and commissioning of AHU Separation Tubes | — | 4.00 | — | — | |
| — | — | — | 28,800 | ||
| Supply, installation, testing and commissioning of Wired Remote | — | 4.00 | — | — | |
| — | — | — | 3,41,600 | ||
| Supply, installation, testing and commissioning of AHU Control unit | — | 4.00 | — | — | |
| — | — | — | 19,60,000 | ||
| Supply of Out Door Units : 64 HP VARIABLE REFRIGERANT FLOW SYSTEM Installation,Testing and Commissioning of Hi efficient DC Inverter Side/Top discharge VRF Outdoor units equipped with Variable refrigerant flow system (Heating&Cooling ), comprising Inverter driven Scroll Compressor with a wide range of frequ- -ency from 15 to 120rps (R-refrigeran tgas). All the unit shall be provided with micro-processor based control advance refrigerant control, Liquid back flow protection, precise oil control tech- -nology, 3ph DC motor condenser fan motor,sub cooling through dual tube heat exchanger & various electrical protection like-phase sequence, high/low voltage protection, compressor overload protection, temperature & pressure protection. Nominal Capacity : 8 HP ( Make : O General / Fujitsu-General / Mitsubishi Electric / Panasonic / Samsung / Carrier / Toshiba / LG / Hitachi / Trane / Voltas ) | — | 8.00 | — | — | |
| — | — | — | 7,88,000 | ||
| Supply of Indoor unit including Installation, Testing and Commissioning of High Static Ductable Indoor Unit with nominal capacity 6 TR, air flow not less than 2294 CFM & sound pressure level not more than 51 db with Touch Panel Remote. ( Make : O General / Fujitsu-General / Mitsubishi Electric / Panasonic / Samsung / Carrier / Toshiba / LG / Hitachi / Trane / Voltas ) | — | 8.00 | — | — | |
| — | — | — | 43,500 | ||
| Supply, installation, testing and commissioning of Refrigerant Gas (R410a) Charging as per site requirements. | — | 50.00 | — | — | |
| — | — | — | 89,200 | ||
| Supply, Installation and Testing of Refrigerant pipe of following sizes with (19mm / 13 mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units complete with necessary connecting Y joints and other accessories as per following specifications, all Refrigerant Pipe Should Run on cable trays of required Size and should be complete with Supports, Hangers etc. ( from Sl. No. 10 to Sl. No. 16 ) : 41.28 mm O.D.(with 19 mm insulation ) | — | 40.00 | — | — | |
| — | — | — | 75,600 | ||
| 38.1 mm O.D.(with 19 mm insulation ) | — | 40.00 | — | — | |
| — | — | — | 1,30,500 | ||
| 28.6 mm O.D.(with 19 mm insulation ) | — | 150.00 | — | — | |
| — | — | — | 86,100 | ||
| 22.2 mm O.D..(with 19 mm insulation ) | — | 150.00 | — | — | |
| — | — | — | 60,360 | ||
| 19.05 mm O.D..(with 13 mm insulation ) | — | 120.00 | — | — | |
| — | — | — | 39,440 | ||
| 15.8 mm O.D..(with 13 mm insulation ) | — | 80.00 | — | — | |
| — | — | — | 72,200 | ||
| 12.7 mm O.D.(with 13mm insulation ) | — | 200.00 | — | — | |
| — | — | — | 14,200 | ||
| Supply, installation, testing and commissioning of rigid PVC Drain Piping of following sizes complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation ( from Sl. No. 17 to Sl. No. 19 ) : 40 mm dia | — | 100.00 | — | — | |
| — | — | — | 5,040 | ||
| 32 mm dia | — | 40.00 | — | — | |
| — | — | — | 4,240 | ||
| 25 mm dia | — | 40.00 | — | — | |
| — | — | — | 74,200 | ||
| Wiring of control cum transmission unit using two core, 1.5 Sq. mm Copper conductor cable along with conduit for looping between indoor & outdoor VRF system (Make - Lapp / Belden) | — | 700.00 | — | — | |
| — | — | — | 4,38,200 | ||
| Supply, installation/erection, testing and commissioning of 120 GSM GI Site Fabricated Duct as per specifications and drawings with the following sizes : ( from Sl. No. 21 to Sl. No. 23 ) : 0.63 mm (24G) | — | 350.00 | — | — | |
| — | — | — | 2,68,740 | ||
| 0.8 mm (22G) | — | 180.00 | — | — | |
| — | — | — | 57,750 | ||
| 1.0 mm (20G) | — | 35.00 | — | — | |
| — | — | — | 2,44,650 | ||
| Supply, Installation, Testing & Commissioning of Duct Thermal Insulation (MAKE- A- FLEX / K-FLEX / AEROCELL) by Providing and fixing of Nitrile Rubber insulation of 13 mm thick on duct complete with all accessory as required. | — | 350.00 | — | — | |
| — | — | — | 1,61,200 | ||
| Supply, Installation, Testing & Commissioning of Duct Acoustic Lining for Duct by Acoustic Insulation of 48 kg/cubic mtr. x 12mm thick Rigid Board with RP tissue and 30G Al. perforated sheet | — | 200.00 | — | — | |
| — | — | — | 51,065 | ||
| Supply, Installation, Testing & Commissioning of return air grilles/ diffusers as per specifications and drawings. ( Make - System Air / Premier / Green Air ). Supply of GI Duct Damper | — | 5.00 | — | — | |
| — | — | — | 2,47,260 | ||
| Supply of Aluminium Supply Air Supply & Return Air Continious Square Diffuser | — | 20.00 | — | — | |
| — | — | — | 60,200 | ||
| Supply of Aluminium Coller Damper | — | 10.00 | — | — | |
| — | — | — | 15,300 | ||
| Supply, Installation, Testing & Commissioning of Anti Vibration Rubber Pad. | — | 1.00 | — | — | |
| — | — | — | 54,810 | ||
| Supply, Installation, Testing and Commissioning of Suction Filter & Ball Valve for ODU. | — | 10.00 | — | — | |
| — | — | — | 36,00,000 | ||
| Supply of outdoor type CSS of rating 06 KV / 415 V, 500 KVA, 3 Ph, 50 Hz, complete with DYn11 Cast resin Dry Type Transformer with Off circuit tap link having tapping range of +5% to -5% in steps of 2.5%, Z% : 4% (IST), 11 KV, 630A, 21kA/3s 2 way non-extensible RMU, consisting of 1 No. Load Break Switch ( Motorised ) and 1 No. Fixed VCB ( Motorised charging & closing ), and LT ACB, 800A, 4P, 50kA with Microprocessor Based Release ( LSIG protection ) with RS-485 and 6 nos. outgoing MCCB, 4P, microprocessor based release ( LSIG ) including necessary HT, LT and control cabling works, internal earthing connections by GI strips etc. ( Make - Siemens / ABB / Schneider / EATON ) ( Please see detailed technical specification ) | — | 1.00 | — | — | |
| — | — | — | 1,80,000 | ||
| Installation, testing and commissioning of above CSS including cable glanding, socketing and plinth construction alongwith construction of Iron shed structure with transparent sheet top cover and MS grill structure duly painted at four sides of CSS | — | 1.00 | — | — | |
| — | — | — | 19,15,099 | ||
| Supply of Fully motorised indoor extensible type Ring Main Units ( RMU ) of rated Voltage ( Nominal / Max ) 6 / 11 / 12KV, rated current 630A, short time withstand current 21 / 26.3 KA for 3 sec., compact switch gear encapsulated in SF6 gas filled stainless steel tank complete with numerical protection relay and metering facilities and remote operation facility ( SCADA Compatible ) consisting of : a) Vacuum Circuit Breaker for Incomer & Outgoer - 4 nos. b) Bus coupler - 1 no. ( Make - Siemens / ABB / Schneider / EATON ) ( Please see detailed technical specification ) | — | 1.00 | — | — | |
| — | — | — | 95,755 | ||
| Installation, connection, cable glanding, testing and commissioning of above RMU Panel. | — | 1.00 | — | — | |
| — | — | — | 4,86,000 | ||
| Supply of Fully motorised indoor extensible type Ring Main Units ( RMU ) of rated voltage ( Nominal / Max ) 11 / 12KV, rated current 630A, short time withstand current 21 / 26.3 KA for 3 sec., compact switch gear encapsulated in SF6 gas filled stainless steel tank complete with numerical protection relay and metering facilities and remote operation facility consisting of : a) Vacuum Circuit Breaker - 1 no. ( Without BUS PT Panel, working as extension part of existing Schneider make RMU Panel. ) ( Make - Siemens / ABB / Schneider / EATON ) ( Please see detailed technical specification ) | — | 1.00 | — | — | |
| — | — | — | 24,300 | ||
| Installation, testing, connection, cable glanding, and commissioning of above single Panel RMU | — | 1.00 | — | — | |
| — | — | — | 6,49,313 | ||
| Supply of SCADA RTU ( Remote Terminal Unit ) comprise of PLC ( Programable Logic Controller ), 02 nos. DI ( Digital Input Card ), 02 nos. DO ( Digital Output card ), 01 no. network card, 01 no. PSC ( Power Supply Card ) and 01 no. Ethernet gateway, 24V DC SMPS, Relay channels, Ethernet switch, Media Converter, 8 Port OFC LIU Box,1 KVA UPS including all power and control cabling works with erection, testing and commissioning. ( The above SCADA RTU Panel should be fully compatible with existing Vijio Citec SCADA system.) ( Make - Siemens / ABB / Schneider ) ( Please see detailed technical specification ) | — | 1.00 | — | — | |
| — | — | — | 67,900 | ||
| Supply of 6 Core Multimode Glass Fibre Optic Cable for other Sub-Station controlling from Main Sub-station SCADA room. ( Make - Dlink / Finolex / Belden / Molex ) | — | 350.00 | — | — | |
| — | — | — | 1,63,500 | ||
| Laying of cable underground through 32 mm diameter HDPE pipe by Micro Tunneling cable laying method including supply and jointing of HDPE pipe. ( Cable will be supplied by Railway ) | — | 300.00 | — | — | |
| — | — | — | 1,36,620 | ||
| Conceal wiring on wall/ceiling/floor through PVC pipe of suitable diameter for Light point / Fan point / Call Bell point / Indication point / Glow Sign point by two nos. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral along with one no. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC ) including supply of cable, GI concealed box with modular cover plate, PVC pipe, junction / circular box, modular switch, ceiling rose and all other associated work along with make good of wall surface as its original condition. ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) ( Make of Modular switch, socket, box, cover plate etc. - Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) | — | 396.00 | — | — | |
| — | — | — | 13,000 | ||
| Conceal wiring on wall/ceiling/floor through PVC pipe of suitable diameter for 6A/5 pin plug point by two nos. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral along with one no. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC ) including supply of cable, GI concealed box with modular cover plate, PVC pipe, junction / circular box, modular switch, modular plug socket and all other associated work along with make good of wall surface as its original condition. ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) ( Make of Modular switch, socket, box, cover plate etc. - Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) | — | 50.00 | — | — | |
| — | — | — | 13,710 | ||
| Conceal wiring on wall / ceiling / floor through PVC pipe of suitable diameter for 16A/6 pin plug point by two nos. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm., 1100V grade for phase and neutral along with one no. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC ) including supply of cable, GI concealed box with modular cover plate, PVC pipe, junction / circular box, modular switch, modular plug socket and all other associated work along with make good of wall surface as its original condition. ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) ( Make of Modular switch, socket, box, cover plate etc. - Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) | — | 30.00 | — | — | |
| — | — | — | 27,216 | ||
| Conceal wiring on wall/ceiling/floor through PVC pipe of suitable diameter for modular type Multi plug board consisting with three nos. 6A/5 pin modular plug socket, three nos. 6A modular switch, one no. 16A / 6 pin modular plug socket, one no.16A modular switch, one no.10A modular type MCB by two nos. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm., 1100V grade for phase and neutral along with one no.single core, HRFR / FRLS 'grade, PVC insulated, copper conductor cable of size 1.5 sq.mm., 1100V grade for Earth Conti- nuity Conductor ( ECC ) including supply of cable, GI concealed box with modular cover plate, PVC pipe, 'junction / circular box, modular switch, modular plug socket and all other associated work along with make good of wall surface as its original condition. ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) ( Make of Modular switch, socket, box, cover plate etc. - ABB / Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) | — | 24.00 | — | — | |
| — | — | — | 23,260 | ||
| Conceal wiring on wall / ceiling / floor through PVC pipe of suitable diameter for Mobile Charging Plug Board consisting with four nos. 6A /5 pin modular plug socket, four nos. 6A modular switch with one no. 10A modular type MCB by two nos. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm., 1100V grade for phase and neutral alongwith one no. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC ) including supply of cable, GI concealed box with modular cover plate, PVC pipe, junction / circular box, modular switch, modular plug socket and all other associated work along with make good of wall surface as its original condition. ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) ( Make of Modular switch, socket, box, cover plate etc. - Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) | — | 20.00 | — | — | |
| — | — | — | 18,040 | ||
| Conceal wiring on wall/ceiling/floor through PVC pipe of suitable diameter for Window AC / Split AC / Water Cooler Point by two nos. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm., 1100V grade for phase and neutral along with one no. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC ) including supply of cable, GI concealed box with modular cover plate, PVC pipe and each board comprising with one power unit which includes one double pole modular MCB, one single phase starter and one 25A socket and plug with indicating light similar to NORTH-WEST Cat.No.- ACPU 6M-BT and all other associated work along with make good of wall surface as its original condition. ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) ( Make of Modular switch, socket, box, cover plate etc. - Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) | — | 20.00 | — | — | |
| — | — | — | 44,800 | ||
| Conceal wiring on wall/ceiling/floor through PVC pipe of suitable diameter for Submain by two nos. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm., 1100V grade for phase and neutral along with one no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm., 1100V grade for Earth Continuity conductor including supply of cable, GI concealed box with modular cover plate, PVC pipe and all other associated work along with make good of wall surface as its original condition. ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) ( Make of Modular switch, socket, box, cover plate etc. - Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) | — | 700.00 | — | — | |
| — | — | — | 42,000 | ||
| Conceal wiring on wall/ceiling/floor through PVC pipe of suitable diameter for Main line by two nos. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 10.0 sq.mm., 1100V grade for phase and neutral along with one no. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC ) including supply of cable, GI concealed box with modular cover plate, PVC pipe and all other associated work along with make good of wall surface as its original condition. ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) ( Make of Modular switch, socket, box, cover plate etc. - Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) | — | 250.00 | — | — | |
| — | — | — | 23,200 | ||
| Fixing, connection, testing and commissioning of indoor LED luminaire fittings with suitable arrangement. ( LED indoor light fitting will be supplied by Railway ) | — | 290.00 | — | — | |
| — | — | — | 16,260 | ||
| Supply of 6W Crysta chip on board (COB) downlight with swivel feature, warm white colour (3000K) LED accent light fitting material - aluminium, light source - LED, Watt - 6W, complete with LED and all other accessories, operating voltage 140V to 270V and frequency 50 Hz similar to Make - Havells, Cat.No. - LHEEGEPBIE1W006 or equivalent. | — | 20.00 | — | — | |
| — | — | — | 1,600 | ||
| Fixing, connection, testing and commissioning of above indoor LED luminaire fittings with suitable arrangement. | — | 20.00 | — | — | |
| — | — | — | 2,520 | ||
| Fixing, connection and commissioning of Street Light luminaire with suitable dia heavy gauge GI bend pipe with GI clamps made of GI flat of size 40mm x 6mm and GI nut-bolts on structure / wall ( LED Street light fitting will be supplied by Railway ) | — | 10.00 | — | — | |
| — | — | — | 3,200 | ||
| Fixing, connection and commissioning of BLDC Ceiling fan with suitable size GI clamps made of GI flat and GI nut-bolts. ( BLDC Ceiling Fan will be supplied by Railway ) | — | 50.00 | — | — | |
| — | — | — | 42,950 | ||
| Supply of BLDC Wall Bracket Fan of size 400 mm sweep suitable for operation on 1Ph, 220-240V, 50Hz supply system ( Make : Havells / Usha / Orient / Halonix / Atomberg / Crompton / Bajaj ) | — | 10.00 | — | — | |
| — | — | — | 870 | ||
| Installation, connection and commissioning of above Wall Bracket fan with GI clamps made of GI flat of suitable size and GI nut-bolts on wall / structure. | — | 10.00 | — | — | |
| — | — | — | 2,544 | ||
| Fixing, connection and commissioning of AC Exhaust Fan with suitable size and shape GI clamps / GI nut & bolts including necessary masonry work ( AC Exhaust Fan will be supplied by Railway ) | — | 16.00 | — | — | |
| — | — | — | 78,060 | ||
| Supply of SPN DB ( Metal Enclosure ), 6 way, 1Ph, 240V, 50Hz, complete with 4 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / Havells / C&S ) | — | 15.00 | — | — | |
| — | — | — | 1,980 | ||
| Fixing, connection and commissioning of above SPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. | — | 15.00 | — | — | |
| — | — | — | 63,260 | ||
| Supply of TPN MCB DB ( Metal Enclosure ), 3Ph, 4 way per phase, 415V, 50Hz, complete with 4 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz per phase as per requirement of load and 1 no. FP RCBO, of current rating 63A, 300mA, 10kA, 415V, 50Hz. ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / BCH / C&S ) | — | 5.00 | — | — | |
| — | — | — | 655 | ||
| Fixing, connection and commissioning of above TPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. | — | 5.00 | — | — | |
| — | — | — | 12,040 | ||
| Supply of LED Signage Board containing script of officer's designation made of high quality acrylic 8mm sheet with laser make - acast / ub / astari, in aluminium extruded slot of 24g and Light Emitting Diodes - Red & Green ( Make / brand of LED chip - NICHIA, OSRAM, SEOUL, PHILIPS, LUMILEDS, AVAGO, CREE ) complete with necessary electronic driver and all other accessories including fixing, connection, testing and commissioning of LED Signage Board with suitable clamps / fixtures. | — | 7.00 | — | — | |
| — | — | — | 3,11,241 | ||
| Supply of Auto Change Over control and distribution panel for colour light signalling of rating 60A, 1Ph, 240V, 50Hz in 25KV AC Traction System as per RDSO's specification no. TI / SPC / PSI / CLS / 0023 or latest including installation, connection, testing and commissioning of above panel board along with terminal cable connection ( Make : RDSO approved sources ) | — | 7.00 | — | — | |
| — | — | — | 42,288 | ||
| Supply, installation and commissioning of different size and suitable width self- illuminated LED display system with all necessary accessories : 1) Aluminium panel - 3mm Pvdf coated aluminium composite panel.(Make-Alstone/Aludecor/Alstom/ Timexbond ) Designed artwork by ER shall be on router cut 3D alphabets of 2" depth to be flushed with the ACP sheet. 2) 1" X 1" 18g MS square pipe structure with red oxide and white enamel paint, ISI marked. 3) Imported translucent Acrylic sheet for making alphabets : a) Physical form - Sheets b) Thickness range - 3mm (+/-) 0.5mm c) Colour - White mild translucent d) Outdoor Stability - UV Stabilised e) Output - Excellent to cast Vinyl and self display f) Make - acast / Mitsubishi / sumiplex 4) 26g Galvanised iron sheet / 3mm acp for back panel. ( Make - Tata / Jindal / Bansal ) 5) Light Emit- -ting Diodes ( LED ) sign modules - ( Make of LED chip - NICHIA/ CRE / OSRAM/ SEOUL/ PHILIPS/ LUMILEDS/ AVAGO ) a) Power consumption - 1 W each module b) Operating Temperature - (-) 40 deg to 60 deg C c) Viewing Angle - 150 degree d) Input Voltage - 12V DC e) Protection Class inbuilt - IP 66 or higher f) Standards - UL94HB g) Certifications - UL. CE. C tick. ROHS h) Housing material of the module - PC & ROHS compliant i) Colour - White / Red / Warm white 6) Power Drivers -( Make-Union / Meanwell or similar ) a) Protection Class - IP 65 b)Rated Supply Voltage - 108V - 305V AC c) Fre- -quency - 50/60 Hz d) Power Factor - greater than 0.9 e) Driver Output current - .8A to 25 Ampere f) Operating Temperature - (-) 40 deg to 60 deg C g) Output Voltage Tolerance -10% | — | 48.00 | — | — | |
| — | — | — | 1,06,143 | ||
| Supply of On Load Manual Change Over Switch of capacity 400 A, 415V, 50Hz, 4P complete with all accessories fitted in metal enclosure including fixing, testing and comissioning ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / BCH / C&S ) | — | 3.00 | — | — | |
| — | — | — | 13,23,928 | ||
| Supply of LT Wall Mounted/ Floor Mounted Double Door Cubical Outdoor type Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder comprising with the following items : a) MCCB, 4 Pole, ( 160 - 400 )Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ) Microprocessor based release with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt Ground Fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memorry, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication - 5 nos. b) MCCB, 4 Pole, ( 100 - 250 )Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ) Microprocessor based release with above features of (a) - 6 nos. c) MCCB, 4 Pole, ( 25 - 63 )Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ) Microprocessor based release with above features of (a) - 9 nos.d) Tinned Copper Busbar (4 Bar) each of capacity 600 Amps., 415V, 50 Hz. - 1 set. e) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 20 nos. f) CT of suitable ratio for MFM - 60 nos. g) LED indication lamp for 3-Phases for incoming feeders and "ON, OFF & TRIP" indication for all incoming and outgoing feeders - 66 nos. h) Petty Store for control cable, MCBs, gland, socket, fuse, push button, TNC switch, selector switch, rotary handle operating mechanism, spreader terminals, interlocking arrangement, auxiliary contacts, shunt release, terminal blocks & NO/NC relays for SCADA RTU connectivity etc. - 1 job. i) Fabrication work for above panel - 1 job. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - Secure / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor ) | — | 1.00 | — | — | |
| — | — | — | 66,196 | ||
| Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection with all suitable arrangement | — | 1.00 | — | — | |
| — | — | — | 63,760 | ||
| Supply of MCCB with Thermal - Magnetic Release of breaking capacity 36 kA at 415V AC, 50Hz of capacity 25-32A / 32-40A / 40-50A, 4 Pole complete with metal enclosure with spreader terminals, LED indication lamps for phases including fixing, connection, testing and commissioning. ( Make of MCCB and Metal Enclosure - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) | — | 10.00 | — | — | |
| — | — | — | 82,050 | ||
| Supply of Dust and vermin proof metal Busbar Chamber made of 16 SWG ( 1.6mm ) MS sheet duly powder coated consisting of 4 nos. tinned copper busbar of each bar of capacity 63 Amp, 6 way, suitable for 415V, 50Hz supply system including all accessories alongwith fixing, connection, testing and commissioning of incoming and outgoing cables glanding, cable socketing and connection with all suitable arrangement. ( Make - Havells / Standard / HPL / LK (Formerly L&T) / C&S / Indoasian ) | — | 10.00 | — | — | |
| — | — | — | 16,772 | ||
| Supply of Junction Box made of 14 SWG GI sheet of size 450 mm x 300 mm x 250 mm consisting with 2 nos. 63A porcelain fuse units (kitkats) conforming to IS:2086 -1993 complete with hinged door with locking arrangement duly painted with two coats of paint after one coat of anti-corro- sive Red Oxide paint as per Sr. DEE/G/HWH's Drawing No. MISC / E / 2 / 05 including fixing, connection and commi- ssioning of above Junction Box on AT Mast with GI clamps made of GI flat of size 40mm x 6mm with GI nuts-bolts. | — | 14.00 | — | — | |
| — | — | — | 2,67,000 | ||
| Supply of FRP Cable Tray ( Perforated ) type ( Width x Collar x Thick ) - 200 mm x 50 mm x 4 mm including fixing, connec- tion, testing and commissioning of above cable tray with necessary arrangement ( Make - RMC Switchgears / Sintex / Fiber Tech Composite / Ferrotech / Grasp / OBO Bettermann ) | — | 250.00 | — | — | |
| — | — | — | 11,160 | ||
| Supply of Coupler Plate with S/S 316 Bolts ( Width x Collar x Thick ) - 50 mm x 170 mm x 4 mm of 8 sets including fixing, connection, testing and commissioning of above coupler plate with necessary arrangement ( Make - RMC Switchgears / Sintex / Fiber Tech Composite / Ferrotech / Grasp / OBO Bettermann ) | — | 40.00 | — | — | |
| — | — | — | 49,488 | ||
| Supply, jointing, testing and commissioning of Straight Through Jointing Kits ( Heat shrinkable ) suitable for XLPE / PVC insulated stranded Aluminium conductor cable of size 3 x 70 / 95 / 120 sq. mm., 11 KV grade complete with all accessories ( Make - m-seal / Raychem / Mahindra / Densons / 3M ) | — | 4.00 | — | — | |
| — | — | — | 20,298 | ||
| Supply, jointing, testing and commissioning of Indoor End Termination and Jointing Kits ( Heat shrinkable ) suitable for XLPE / PVC insulated stranded Aluminium conductor cable of size 3 x 120-150 sq.mm., 11 KV grade complete with all accessories ( Make - m-seal / Raychem / Mahindra / Densons / 3M ) | — | 2.00 | — | — | |
| — | — | — | 7,96,500 | ||
| Laying of cable underground through 100 mm diameter HDPE pipe by Micro Tunneling cable laying method including supply and jointing of HDPE pipe. ( Cable will be supplied by Railway ) | — | 500.00 | — | — | |
| — | — | — | 1,04,200 | ||
| Trenching, laying under road / track through 100 mm dia GI pipe ( medium gauge ) including supply of GI pipe and commi- ssioning of cable including back filling of trench with excavated soil after laying of cable ( Cable will be supplied by Railway ) | — | 200.00 | — | — | |
| — | — | — | 34,400 | ||
| Drawing of cable on wall / structure with suitable size and shape GI clamps including supply of suitable size GI Clamp and GI nut-bolts and commissioning of cable ( Cable will be supplied by Railway ) | — | 800.00 | — | — | |
| — | — | — | 23,000 | ||
| Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) | — | 250.00 | — | — | |
| — | — | — | 2,72,000 | ||
| Trenching and laying of cable under ground by soil cutting through suitable dia HDPE pipe including supply of HDPE pipe alongwith refiling of trench by excavated soil and make good of surface as its original condition. ( Cable will be supplied by Railway ) | — | 1700.00 | — | — | |
| — | — | — | 41,055 | ||
| Earthing with 2 nos.of 50 mm diametre, 3.0 metres long heavy gauge GI pipe ( Make - Tata / Jindal / Bansal ) including construction of earth pit and necessary earth connection from pit by suitable Galvanized Iron ( GI ) strip. ( For details not covered in this specifications, Indian Standard Code of Practice for earthing IS : 3043 - 1987, Reaffirmed - 1996 should be followed ) | — | 15.00 | — | — | |
| — | — | — | 37,44,807 | ||
| Goods & Services Tax ( at present @ 18% ) | Lumpsum | 1.00 | — | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .