Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.0 CrAccepted-AOC | ₹14.0 Cr Quoted ₹14.1 Cr | L1 | Accepted-AOC Being L1 and reasonable |
| 2 | L2₹14.2 CrRejected-Finance 5037 5038 URBAN ESTATE PH 1 PATIALA 147002 PUNJAB | PATIALA | PATIALA | PUNJAB | 147002 | ₹14.2 Cr | L2 | Rejected-Finance Being other than L1 |
| 3 | L3₹14.4 CrRejected-Finance AT 75 JN ROAD HADDO PORT BLAIR SOUTH ANDAMAN PORT BLAIR 744102 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744102 | ₹14.4 Cr | L3 | Rejected-Finance Being other than L1 |
| 4 | L4₹14.4 CrRejected-Finance | ₹14.4 Cr | L4 | Rejected-Finance Being other than L1 |
| 5 | L5₹14.5 CrRejected-Finance | ₹14.5 Cr | L5 | Rejected-Finance Being other than L1 |
Tender Value
₹12.9 Cr
Closing Date
14 Sept 2021, 6:00 pmClosed
CE AandN ZONE
Headquarters Chief Engineer AN Zone Military Engineer Services Birchgunj Junglighat Post Port Blair 744 103
INFRASTRUCTURE DEVELOPMENT FOR MODERNIZATION OF AIRFIELD INFRASTRUCTURE (MAFI) AT INS UTKROSH, PORT BLAIR
2021_MES_444626_1
801195
Open Tender
Civil Works
750 days
Portblair
Please refer Tender documents.
10 documents required · 10 mandatory
₹3,000
GE (P) Central, Port Blair
Exempted
30 Sept 2021
21 May 2021
18 Sept 2021
21 May 2021
14 Sept 2021
21 Jul 2021
Amount
GENERAL SUMMARY NOTE: Schedule ‘A’ Part I to XV are prepriced by MES under Ser No. 2.00 to 16.00. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lumpsum price worked out by the contractor for "Building / Structures” as listed in Schedule ‘A’ Part - I, inserted by MES
Lumpsum price worked out by the tenderer for "Internal Water Supply " as listed in Schedule ‘A’ Part-II
Lumpsum price worked out by the tenderer for "Internal Electrification " as listed in Schedule ‘A’ Part-III
Lumpsum price worked out by the tenderer for "Sewage Disposal " as listed in Schedule ‘A’ Part-IV
Lumpsum price worked out by the tenderer for "Area Drainage" as listed in Schedule ‘A’ Part-V
Lumpsum price worked out by the tenderer for "Road/Path/Culvert/Hardstanding " as listed in Schedule 'A' Part-VI
Lumpsum price worked out by the tenderer for "Site clearance/Land devlopment/Retaing wall" as listed in Schedule ‘A’ Part-VII
Lumpsum price worked out by the tenderer for "Compound wall/Fencing and Steel gate " as listed in Schedule ‘A’ Part-VIII
Lumpsum price worked out by the tenderer for "Demolition and Dismantling " as listed in Schedule ‘A’ Part-IX
Lumpsum price worked out by the tenderer for "External Water Supply " as listed in Schedule ‘A’ Part-X
Lumpsum price worked out by the tenderer for "External Electric Supply " as listed in Schedule ‘A’ Part-XI
Lumpsum price worked out by the tenderer for "Fire Fighting and Fire Detection System" as listed in Schedule ‘A’ Part-XII
Lumpsum price worked out by the tenderer for "Lightning Protection" as listed in Schedule ‘A’ Part-XIII
Lumpsum price worked out by the tenderer for "Pile Foundation" as listed in Schedule ‘A’ Part-XIV
Lumpsum price worked out by the tenderer for "Excavation & Earthwork" as listed in Schedule ‘A’ Part-XV
Subtotal
SCH 'A' PART XVI MISCELLANEOUS ITEMS NOTE: Schedule ‘A’ Part - XVI is not prepriced by MES and prepriced rate indicated as 0.00 under Col.5 signifies this fact only. Bidder shall insert their rates in Green colour filled under Col-6.
Internal Electrification : Supply & fix Ceiling fan, 5 star rating suitable for working of AC 230V, 50 Hz, 1200 mm sweep with electronic regulator, down rod and canopy rating and the colour of milky white including anchor flusher, ceiling hook for fixing of fan on celing complete all as specified and directed by Engr-in-charge. Make: Bajaj/Havells/CG
Supply & fix exhaust fan, 225mm sweep,sigle phase, AC 230V, 50 Hz, heavy duty,1400 rpm energy efficient smooth functioning with suitable size of louvers including fixing arrangement, opening of whole all as directed by Engr-in-charge. Make: Crompton/Bajaj/Usha
S&F LED type tube light fittings, 4 feet long, 1x20 watts, 230V, decorative ultra slim square profile liner LED lighting fixture with extruded polycarbonate envoirement friendly, energy efficient tube light, voltage protection 160-360V, power factor >0.9 complete & prewired for LED tube complete fixed to wall/ceiling by suitable down rods, PVC round block and connection by flexible PVC cable with stranded copper conductor from ceiling rose to connector of the fitting including 1x20W LED tube complete all as specified and directed. Make: Phillips Cat No-BN021C LED 20S PSU CW GR S2 or equivalent to Wipro, Crompton
S&F 10 watt LED fittings with wide voltage protection 160-360 Volt, lumen output 900lm complete & prewired for LED tube complete fixed to wall/ceiling by suitable downrods, PVC round block and connection by flexible PVC cable with stranded copper conductor from ceiling rose to connector of the fitting complete all as specified and directed. Philips Cat No-BN010C LED 20S PSU CW GR S1 or equivalent to Wipro/Crompton
S & F building street light LED fitting 30 W capacity including electronic driver IP 65 peotection, fixing with suitable size of brackets 1.2 mtr long bend to shape, including clamp nut and bolt, connected from ceiling rose or existing point all as specified and directed by Engr-in-Charge. Philips Cat No-BRP046LED 30CWMRS1 PSU GR or equivalent to Wipro/Crompton
S & F miniature circuit breaker(RCBO/MCBs/MCCBs) of following capacity.
MCB SP 230 volts, 10 KA, 6 to 32Amps, 'C' curve.
MCB SPN 230 volts, 10 KA, 6 to 32Amps, 'C' curve.
MCCB 4 Pole, 415 volts, 32-100 Amps, 16 KA Capacity.
RCBO 4 pole, 415 volts, 32 to 63 Amps, 16KA Capacity.
S & F TV socket/Telephone socket complete all as specified and directed.
M &L for earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directlry in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 mtr below normal ground level, earth plate surrounded from all sides by with 15cm thick packed layer of charcoal dust and common salt filling in alternate layer and electrode connection by using galvanized earth including provision of galvanized earth wire 4mm dia connected by mean of bolt, nut, chck nut & washer of galvanised iron, provision of 15mm dia GI pipe medium grade for protection of GI earth wire & 20mm dia GI pipe medium garde for watering arrangement and PCC (1:3:6), type C1 chamber, MS funnel, wire gauge, 50mm thick RCC 1:2:4, type B1, earth pit cover with 6 Nos, 8mm dia high strenght deformed steel TMT bars on both ways including necessary excavation in any type of soil returning filling in removal of surplus soil to distance n.exc 50 mtrs, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I 2009 all as specified and directed.
Sewage Disposal: Supply and laying double wall Corrugated DWC pipe HDPE pipe of outer dia 200mm and inner dia 157mm of approved make ISI marked high density polythyne with smooth internal wall & corrugated external surface for non pressure for sewage complete all asdirected.
Road/Path/Culvert/Hardstanding : M & L for approved earth brought from outside MD land & forming embankment including raising earth, spreading in two layers n exc 30 cm thick watering rolling (8 to 10 tonne roller) & finished to required size & shape n exc 1.5 m from base etc. all as specified and directed.
Security Wall/Fencing/Gate : Supply only PVC Coated chain link fencing exc 2.0 but n exc 3.5kg per sqm with size of mesh50x50mm apperture, thickness of wire n exc 2.83mm all as specified and as directed.
EXTERNAL WATER SUPPLY: M &L for Construction of masonry valve chamber of size 600x600x600mm internal size, 100mm thick foundation using PCC 1:4:8, type D-2, over 15cm thick hard core, 20cm thick solid block masonry with blocks cast using PCC 1:3:6, type C-1, set in cement mortar 1:4m, 15MM thick plaster to internal surfaces and external surfaces up to 15cm below ground level and top of floor in cement and sand mortar 1:4, finished even and smooth with out using extra cement, 3.15mm thick MS sheet cover including 50mmx50mmx6mm thick MS angle frame fixed in PCC 1:2:4, type B1 coping with 25mmx6mm flat iron hold fasts, handle, hinges with locking arrangments, applying one coat of red oxide primer and two coats of synthetic enamel paint to all steel surfaces and earth work in any type of soil including disposal of surplus soil to distance not exceeding 50M complete all as specified and directed.
M/L for cutting the existing CI /DI pipe line 150 mm dia and inserting Tee of size 150x150 mm x 80 mm dia complete for making new branch connection of 80mm dia GI pipe including necessary fittings complete all as specified.. (for ASR bldg)
M/L for cutting the existing CI /DI pipe line 150 mm dia and inserting Tee of size 150x150 mm x 50 mm dia complete for making new branch connection of 50 mm dia GI pipe including necessary fittings complete all as specified.. (for PAR bldg)
Supply & fix GM seat lift type CI foot valve confirming to IS 4038 of 80 mm dia Make:- Kirlosker/ Upadhyay/ L&T
Supply & istall cast iron air release valve with two air outlets 80 mm dia bore and fixing up in 80mm GI pipe line Make:Kirlosker/ Upadhyay/Audco
Supply install testing & commisioning of monoblck water pump, 3 phase of 1500 RPM or suitable RPM, self primming for pumping water of 200 lpm and head 31 M with appropriate capacity of motor approved make , electrical connection from near by source with copper wire of 6 sqmm dia for phase & neutral in rigid PVC conduit , foundation for hole unit complete all as specified & as directed at site by enginner-in-charge. Make : Kirloskar, Crompton.
Supply install testing & commisioning of monoblck water pump, 3 phase of 3000 RPM or suitable RPM, self primming for pumping water of 200 lpm and head 25M with appropriate capacity of motor approved make , electrical connection from near by source with copper wire of 6 sqmm dia for phase & neutral in rigid PVC conduit , foundation for hole unit complete all as specified & as directed at site by enginner-in-charge. Make : Kirloskar, Crompton.
Supply ,install, testing and commissioning of indoor type LT panel board, factory made out of 2mm thick MS sheet fabricated, powder coated after seven tank process, mounted on MS equal angle iron 5mm thick, dust and vermin proof, with both side openable , hinged door and locking arrangement with IP 43 protection including 4wire alluminium bus bar chamber suitable for phase and neutral , complete wirring, and powder coated painting with synthetic enamel paint, fixed on platform PCC 1:4:8 type D2 coping with PCC 1:3:6 type C1 including provisioning of the following:- (a) INCOMMER- Supply and install MCB 25 Amps, 4 pole , C series- 1 No. BUS BARS:- (b) 40 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. OUT GOING:- (c ) (i) MCB 10 Amps, 2 pole , C series -1 No. (ii) Automatic star Delta starter shall be provided suitable for pumps of tem No.33- 2 Nos. (e) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load (f) indicator lamp LED for R,Y,B, with MCB.
Supply ,install, testing and commissioning of indoor type LT panel board, factory made out of 2mm thick MS sheet fabricated, powder coated after seven tank process, mounted on MS equal angle iron 5mm thick, dust and vermin proof, with both side openable , hinged door and locking arrangement with IP 43 protection including 4wire alluminium bus bar chamber suitable for phase and neutral , complete wirring, and powder coated painting with synthetic enamel paint, fixed on platform PCC 1:4:8 type D2 coping with PCC 1:3:6 type C1 including provisioning of the following:- (at PAR Pump house ) . (a) INCOMMER- Supply and install MCB 16 Amps, 4 pole , C series- 1 No. BUS BARS:- (b) 40 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. OUT GOING:- (c ) (i) MCB 10 Amps, 2 pole , C series -1 no. (ii) DOL starter suitable for pumps of item no. 34 - 2 No. (d) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load (e) indicator lamp LED for R,Y,B, with MCB.
Supply & fix PVC water tank 3 layers of approved make, Rotational moulded polyethylene water storage tanks (cylindrical vertica lwith closed top) hoisted and fixed in position all asspecified in SSR Part I of 5000 Ltr Make:- Sintax/Rotex/Polycon
Supply & fix PVC water tank 3 layers of approved make, Rotational moulded polyethylene water storage tanks (cylindrical vertica lwith closed top) hoisted and fixed in position all asspecified in SSR Part I of 10000 Ltr Make:- Sintax/Rotex/Polycon
M &L for earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directlry in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 mtr below normal ground level, including provision of galvanized earth strip 32 x 6mm , earth plate surrounded from all sides by with 15cm thick packed layer of charcoal dust and common salt filling in alternate layer and electrode connection by using galvanized earth strip 32x6mm connected by mean of bolt, nut, chck nut & washer of galvanised iron, provision of 40mm dia GI pipe medium grade for protection of strip & 20mm dia GI pipe medium garde for watering arrangement and PCC (1:3:6), type C1 chamber, msfunnel, wire gauge, 50mm thick RCC 1:2:4 TMT bars on both ways including necessary excavation in any type o soil returning filling in removal of surplues soil to distance n.exc 50 mtrs complete all as shown in electrical plat no 5 of schedule part-I 2009 all as specified and directed. (i) The unit rate shall include for Earth work and protection of GI pipe, GI water pipe, wire mesh, funnel, excavation, RCC pit cover, P.C.C chamber pit,. test point, 32x6mm GI strip from top of earth plate upto 5 metres above ground level. (ii) PCC pit shall be provided at least 500mm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipes and fitting junction etc shall be deemed to be included in the unit rate.
EXTERNAL ELECRIFICATION: Supply , fixing ,testing and commisioning and training of executives at site of CSS( compact type substation) Non walking type confirming of dry type transformer step down 160 KVA capacity 11 /.433 KV (Dyn11) as per IS standered, off load tap changer as per IS 1180 (part 1) :2014, Tapping +5% to -15% step @2.5 % in HV side, AN cooling, RMU with 3 phase HT VCB 630 A, rupturing capacity 350 MVA , LT panel with incommer MCCB 250 A, 50 KA - 1 No. & Out going MCCB 250 A , 50 KA -2 No. including APFC panel of capacity 80 KVAR capacity, arrangements for connection with AMF panel / change over switch,. The enclouser should be IP 54 protection & HT, LT switchgear should have IP 35 degree of protection icluding complete interconnection as per IS standered. (for ASR radar section)
The RMU description shall be as below. RMU-NON-Extensible FBX- CCT2 OR Equivalant ( 2 Isolators & 1 Vacuum circuit breaker(T2) (AL Busbars)-BIL 28kv (RMS)/75 Kvp Each LBS ( LOAD BREAK SWITCH) will have the following :- 1 Manually operated 11 KV 630A, 21 KA for 3 sec Load Break switch and Earthing Switch with making capacity. 2 Mechanical ON/OFF/EARTH Indication. 3 Live Cable “ Indicating LEDs energized thru Capacitive Voltage Dividers. 4 Interlock arrangement between Cable cover & Isolator. 5 Cable box suitable for cable termination of 1 no. 3Cx 240 sq.mm. XLPE cable. 6 Flexible boots 7. FPI for only one number LBS funcion - FPI shall be with inbuild O/C & E/F indication. 8. VCB FUNCTION Type:- 3 position Disconnector and Earthing switch equipped with separate drive unit. The VCB equipped with over current time release for transformer protection and SCADA Port facilities. (a) . Vacuum circuit breaker 11 kV, 630 A, 21 KA/3 sec. (b) Operation of breaker – Motorized (c) Self Powered Electronic numerical protection relay providing over-current & earth fault protection – Schneider make DPX-V5 / equivalant (d) Ring core protection current transformers. CTR 30/1 , 5P10 , 2.5 VA (e) Aux. contacts for VCB. ( 2 NO + 2NC ) (f) Capacitive voltage indication fixed type. (g) ON, OFF, TRIP indication on the front mimic of the panel. (h) Cable box for termination of cable up to 3 nos. 1C X 95 sq.mm. Aluminum unarmoured (E) XLPE cable (j) Cable cover standard. (k) Emergency trip push button. (l) Shunt trip coil – 24 V DC (m) .Transformer fault alarm & trip
TRANSFORMER (TYPE:- DRY TYPE) 1. Ratio- 11 KV/433V, 2. Capacity:- 160 KVA, 3. Vector Group- DYn11, 4. Off Load Tappings 5% to -15% @ 2.5%, 5. Insulation class- F 6. Temp. Rise above ambient temperature : 90 Deg C 7. No Load Losses - As per the IS standard 8. Full load losses - As per the IS standards. 9. %Impedance- 6 % 10. Hermetically sealed type suitable for CSS/PSS 11. Conforming to IS 1180(Part- I) : 2014 Transformer Accessories Winding Temperature Scanner, Oil drain plug, Air Vent plug, Temperature guage, Necessary lifting lugs. HT terminals suitable for CSS/PSS application LT terminals Suitable for CSS/PSS applications.
LT PANEL :- Supply, installation, testing and commissioning of LT panel ( Construction shall be for suitable use inside CSS/PSS, i.e. non compartmentalized design) for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers, bus bars, inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel with 3mm thick CRCA sheet complete as required size conforming to relavant IS specification. The MCCB shall have the valid type test certificate and all the LT side compenents shall be placed inside the CSS/PSS enclosure having IP 34 degree of protection. Type test certificate for Ingress protection for enclosure needs to be provided. The LT side configuration shall be as below.
Outgoing 2 nos. 250A, 35 KA, 4P Adjustable type, microprocessor based MCCB with overload, short circuit and earth fault protection APFC Panel (80 KVAR) INCOMING: 1 nos. 100 Amps, 4P, 433 volts, 35 KA MCCB ( TMD based) Automatic power factor correction relay to sense power factor and to give 20 phased impulses for switching capacitors. BUS BAR Main bus bars rated 200A suitable for 433 V, 50 Hz, 3 phase and neutral aluminium bus bar shall have current density of not less than 1.0 Amp per sq.mm. and the neutral bus of 50% capacity interconnections between bus bars and breakers shall be through solid copper strip.
OUTGING SECTIONS ( APFC panel with MD-XL capacitor (super Heavy duty square capacitor with detuned reactor (Aluminium) of 3 mm thick and suitable size to accommodate capacitor bank of rating 80 KVAR comprising of step size (1x1)+(2x2)+(3x5)+(2x10)+(2x20) KVAR 10 steps, super Heavy duty gas filled capacitors with copper busbar of rated capacity including MCCB as incomer, auto+manual switches, outgoing of corresponding rated MCCBs along with necessary contractors, Ammeter (0-500A Analog type), Voltmeter (0-500 V) analog type). Energy meter digital type with CTs, LED indication lamps complete with incoming cable and CTs alongwith control wiring and inbuilt exhaust fan with auto sensor forautomatic operation when required complete all as specified and directed The panel shall be complete with busbars, discharge resistors protection MCB's, all internal wiring, labels, capacitor numbers in terms of switching process, all and above APFCR with manual overridden facility, total in all respects and complete as required.
ENCLOSURE FOR CSS/PSS Outdoor type enclosure having modular construction of 3.15 mm thick Galvanized sheet steel for load bearing and non load bearing members . The enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for Transformer compartment. The enclosure exterior shall be painted with powder coating ( RAL 7032) . Each compartment will be provided with the door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided for Each compartment. Note: The size & layout drawing for CSS shall be got approved from the accepting officer before execution of work Please note it is required for the Transformer compartment to have K10 temperature class. Type test for the same needs to be there for Transformer compartment. The CSS/PSS enclosure needs to be internal arc tested and the type test certificate for the same needs to be provided. Also please note the RMU and APFC Panel needs to be inside the CSS/PSS. Note:-Transformer, VCB, RMU, APFC etc shall be OEM make of CSS only..
Interconnection , Earthing & Conection with AMF Panel Interconnection between HT switchgear & Transformer using 1Cx3x95 Sq.mm HT cable XLPE Single core & Interconnection between Transformer & LT switchgears using aluminium Busbars/trunking system & Interconnection between LT panel & APFC panel using aluminium Busbars/trunking system and all internal earthing connections by AL Strips of suitable size as to be carried out by the contractor for which rate is deemed to be included in the unit rate qouted. Also facility /arrangement for conecction with AMF panel should be provided. The foundation shall be provided at site as per recommandation of manufacturers design & drawing cost for the same is deemed to be included in unit rate of above item.
Supply ,install , testing & commisioning of Servo Voltage stabilizer copper wound, for automatic operation /regulating of voltage comprising of auto transformer ,servo motor, intelligent micro controller based circuit, 3 phase 415 V, 50 HZ, naturally oil cooled indoor type for unbalanced load & designed for input variation beween 340 volt 460 volt with output voltage stabilized at 415 with accuracy +,- 1% and speed of correction 8 volt /sec , of capacity 160 KVA . responce time 10ms along with Suitable for all power factor load as per specification. LED for each phase to indicate Mains ON, Output ON,
Incorporated by means of contractor to trip in event of Under voltage, over voltage, overload, single phasing alongwith audio alarm Metering- Digital microprocessor Based cards for voltage, output load current with CT Protection- Overload, short circuit, High / Low voltage cut off & Bypass arrangement to be provided First filling of oil to be provided, Temp rise -50 degree C in oil, Control- Auto/ Manual, Insulation class -A, Fitting with four Plain Rollers, Two Earthing Terminals, Four Lifting Hooks, Oil filling Hole with Cap, Drain wall, oil level indicator, Sillica gel breather, Oil temperature indicator, Thermometer Pocket As per IS 9815 Testing- All routine tests as per DGAQA & IS to be conducted & Test reports to be furnished alongwith equipment.
Supply, install , testing & commisioning of Isolation transformer of capacity 160 KVA indoor type complet with standard fittings,3 phase, 50 Hz 4 wire , 415 + 5%/ 415 +5% volts, ratio 1:1, Oil cooled potential difference between neutral to earth less than 1 Volt with off load tapping on to vary secondary voltage within limit . Note: Isolation transformer tested on high voltage insulated test transformer varnished with fine grade varnish in vaccum inpregnation plant. Efficiency -98.5-99% at Full load / UPF,Dielectric strenght 3KV for 2 min, copper wounded, Over load, short circuit, high/low cutoff protection .
Copper Winding Tapping- Nil , Impedence 4 % Max Input frequency- 47 to 53 HZ Insulation class H & Insulation resistance better than 100M ohms Fittings- Two lifting hooks, four plain rollers, Two earthing terminals, Base channels with Towing holes. Termination- Suitable links to be provided behind front door above gland place to accept bottom entry of cables. As per IS 2026 Testing- All routine tests as per DGAQA & IS to be conducted & Test Reports to be furnished along with equipment.
Supply, installation, testing and commissioning of factory made powder coated compartmentalized cubicle LT Panel for ASR bldg outdoor type with canopy, fabricated from 3.15 mm thick CRCA sheet steel with necessary angle iron frame fabricated with 50x50x5 mm MS angle, weather proof vermin proof ,including chamber of 500 Amps rating aluminium bus bar for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers , inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel complete as required size conforming to relavant IS specification. The panel should be CPRI approved and having dust , vermin proof, weather proof, IP- 54 ingress protection including necessary foundation for mounting all as specified and directed. Incorporating the following:
INCOMMER - 250A 415V, 4P, 50kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. microprocessor release type.- 1 No. BUS BARS- 400 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. OUT GOING - 250A 415V, 4P, 50kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. microprocessor release type.- 3 Nos. Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT Indicator lamp LED for R,Y,B, with MCB.
Supply, installation, testing and commissioning of factory made powder coated compartmentalized cubicle LT Panel for ASR bldg outdoor type with canopy, fabricated from 3.15 mm thick CRCA sheet steel with necessary angle iron frame fabricated with 50x50x5 mm MS angle, weather proof vermin proof ,including chamber aluminium bus bar for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers , inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel complete as required size conforming to relavant IS specification. The panel should be CPRI approved and having dust , vermin proof, weather proof, IP- 54 ingress protection including necessary foundation for mounting all as specified and directed. Incorporating the following:
Incommer- 250A 415V, 4P, 36kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. microprocessor release type.- 1 No. Bus bar 400 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. Out going . (a) 125 A MCCB 4 P 36 KA- 1 No. (b) 100 A MCCB 4P, 25KA- 3 Nos. (1 Spare). (c) 25 A MCB 4P C series 2 Nos. (d) 20 A MCB 2 P- 2 Nos. Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT. Indicator lamp LED for R,Y,B, with MCB.
Supply, install, Testing & commisioning of on-load Manual change over switch - Disconnector ( Confirm to IEC 60947-3, IS /IEC 60947-3) of 250 A , 415 V, SS Enclosure, Terminal Shrouds , Source separater and phase barrier , IP 43 Protection suitable of vertical as well as horizontzl mounting as per site requirement , Complete all as per specified & directed. Make L & T cat part No. CO32500OSOO and equivalent in Schenider, Havells. (for Isolation transformer & Servo voltage stabilizer) (at ASR bldg.)
S&F GI cable tray of 150mm width, 50 mm height, 2 mm thick hot deep galvanised ladder type cable tray including fixing with wall, piller e.t.c. with bullet type anchor fastener, cable securing with GI clamp of 2mm thick including coneccted accesories complete, all as specified & as directed at site.
S&F GI cable tray of 300 mm width, 50 mm height, 2 mm thick hot deep galvanised ladder type cable tray including fixing with wall, piller e.t.c. with bullet type anchor fastener, cable securing with GI clamp of 2mm thick including complete all as specified & as directed.
Supply , fixing , commisioning and training of executives at site of CSS( compact type substation) non walking type, confirming of dry type transformer step down 100 KVA capacity 11 /.433 KV,(Dyn11) as per IS standered 1180 (part-1) : 2014, Tapping +5% to -15% step @2.5 % in HV side, AN cooling, off load tap changer, RMU with 3 phase HT VCB 630 A rupturing capacity 350 MVA , LT panel with incommer MCCB 150 A, 50 KA - 1 No. & Out going MCCB 150 A , 50 KA -2 No. including APFC panel of capacity 50 KVAR capacity, arrangements for connection with AMF panel / change over switch,. The enclouser should be IP 54 protection & HT, LT switchgear should have IP 34 degree of protection icluding complete interconnection as per IS standered. (for PAR radar Hut)
The RMU description shall be as below. RMU-NON-Extensible FBX- CCT2 OR Equivalant ( 2 Isolators & 1 Vacuum circuit breaker(T2) (AL Busbars)-BIL 28kv (RMS)/75 Kvp Each LBS ( LOAD BREAK SWITCH) will have the following :- 1 Manually operated 11 KV 630A, 21 KA for 3 sec Load Break switch and Earthing Switch with making capacity. 2 Mechanical ON/OFF/EARTH Indication. 3 Live Cable “ Indicating LEDs energized thru Capacitive Voltage Dividers. 4 Interlock arrangement between Cable cover & Isolator. 5 Cable box suitable for cable termination of 1 no. 3Cx 240 sq.mm. XLPE cable. 6 Flexible boots 7. FPI for only one number LBS funcion - FPI shall be with inbuild O/C & E/F indication. 8. VCB FUNCTION Type:- 3 position Disconnector and Earthing switch equipped with separate drive unit. The VCB equipped with over current time release for transformer protection. (a) Vacuum circuit breaker 11 kV, 630 A, 21 KA/3 sec. (b) Operation of breaker – Motorized (c) Self Powered Electronic numerical protection relay providing over-current & earth fault protection – Schneider make DPX-V5 / equivalant (d) Ring core protection current transformers. CTR 30/1 , 5P10 , 2.5 VA (e) Aux. contacts for VCB. ( 2 NO + 2NC ) (f) Capacitive voltage indication fixed type. (g) ON, OFF, TRIP indication on the front mimic of the panel. (h) Cable box for termination of cable up to 3 nos. 1C X 95 sq.mm. Aluminum unarmoured (E) XLPE cable (j) Cable cover standard. (k) Emergency trip push button. (l) Shunt trip coil – 24 V DC (m) Transformer fault alarm & trip
TRANSFORMER TYPE:- DRY TYPE 1. Ratio- 11 KV/433V, 2. Capacity:- 100 KVA, 3. Vector Group- DYn11, 4. Off Load Tappings 5% to -15% @ 2.5%, 5. Insulation class- F 6. Temp. Rise above ambient temperature : 90 Deg C 7. No Load Losses - As per the IS standard 8. Full load losses - As per the IS standards. 9. %Impedance- 6 % 10. Hermetically sealed type suitable for CSS/PSS 11. Conforming IS 1180(Part- I):2014 Transformer Accessories Winding Temperature Scanner Oil drain plug Air Vent plug Temperature guage Necessary lifting lugs. HT terminals suitable for CSS/PSS application LT terminals Suitable for CSS/PSS applications.
LT PANEL :- Supply, installation, testing and commissioning of LT panel ( Construction shall be for suitable use inside CSS/PSS, i.e. non compartmentalized design) for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers, bus bars, inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel with 3mm thick CRCA sheet complete as required size conforming to relavant IS specification. The MCCB shall have the valid type test certificate and all the LT side compenents shall be placed inside the CSS/PSS enclosure having IP 34 degree of protection. Type test certificate for Ingress protection for enclosure needs to be provided. The LT side configuration shall be as below.
Outgoing 2 nos. 150A, 50 KA, 4P Adjustable type, microprocessor based MCCB with overload, short circuit and earth fault protection APFC Panel (50 KVAR) INCOMING: 1 nos. 63 Amps, 4P, 433 volts, 35 KA MCCB ( TMD based) Automatic power factor correction relay to sense power factor and to give 20 phased impulses for switching capacitors. BUS BAR Main bus bars rated 100A suitable for 433 V, 50 Hz, 3 phase and neutral aluminium bus bar shall have current density of not less than 1.0 Amp per sq.mm. and the neutral bus of 50% capacity interconnections between bus bars and breakers shall be through solid copper strip.
OUTGING SECTIONS ( APFC panel with MD-XL capacitor (super Heavy duty square capacitor with detuned reactor (Aluminium) of 3 mm thick and suitable size to accommodate capacitor bank of rating 50 KVAR comprising of step size (1x1)+(2x2)+(5x3)+(10x1)+(20x1) KVAR 8 steps, super Heavy duty gas filled capacitors with copper busbar of rated capacity including MCCB as incomer, auto+manual switches, outgoing of corresponding rated MCCBs along with necessary contractors, Ammeter (0-100A Digital type), Voltmeter (0-500 V) analog type). Energy meter digital type with CTs, LED indication lamps complete with incoming cable and CTs alongwith control wiring and inbuilt exhaust fan with auto sensor for automatic operation when required complete all as specified and directed The panel shall be complete with busbars, discharge resistors, protection MCB's , all internal wiring, labels, capacitor numbers in terms of switching process, all and above APFCR with manual overridden facility, total in all respects and complete as required.
ENCLOSURE FOR CSS/PSS Outdoor type enclosure having modular construction of 3.15 mm thick Galvanized sheet steel for load bearing and non load bearing members . The enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for Transformer compartment. The enclosure exterior shall be painted with powder coating ( RAL 7032) . Each compartment will be provided with the door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided for Each compartment. Note: The size & layout drawing for CSS shall be got approved from the accepting officer before execution of work Please note it is required for the Transformer compartment to have K10 temperature class. Type test for the same needs to be there for Transformer compartment. The CSS/PSS enclosure needs to be internal arc tested and the type test certificate for the same needs to be provided. Also please note the RMU and APFC Panel needs to be inside the CSS/PSS. Note:--Transformer, VCB, RMU, APFC etc shall be OEM make of CSS only..
Interconnection , Earthing & Conection with AMF Panel Interconnection between HT switchgear & Transformer using 1Cx3x95 Sq.mm HT cable XLPE Single core & Interconnection between Transformer & LT switchgears using aluminium Busbars/trunking system & Interconnection between LT panel & APFC panel using aluminium Busbars/trunking system and all internal earthing connections by AL Strips of suitable size as to be carried out by the contractor for which rate is deemed to be included in the unit rate qouted. Also facility /arrangement for conecction with AMF panel should be provided. The foundation shall be provided at site as per recommandation of manufacturers design & drawing cost for the same is deemed to be included in unit rate of above item.
Supply, installation, testing and commissioning of factory made powder coated compartmentalized cubicle LT Panel outdoor type with canopy, fabricated from 3.15 mm thick CRCA sheet steel with necessary angle iron frame fabricated with 50x50x5 mm MS angle, weather proof vermin proof ,including chamber of aluminium bus bar for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers , inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel complete as required size conforming to relavant IS specification. The panel should be CPRI approved and having dust , vermin proof, weather proof, IP- 54 ingress protection including necessary foundation for mounting all as specified and directed. Incorporating the following :
IINCOMMER- 150A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. thermal magnetic release type.- 1 No. BUS BARS: Bus bar 250 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. OUT GOING - 150A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. thermal magnetic release type.- 3 Nos. Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT Indicator lamp LED for R,Y,B, with MCB. (For main panel & bi pass arrangement )
Supply, installation, testing and commissioning of factory made powder coated compartmentalized cubicle LT Panel indoor type with canopy, fabricated from 3.15 mm thick CRCA sheet steel with necessary angle iron frame fabricated with 50x50x5 mm MS angle, weather proof vermin proof ,including chamber of aluminium bus bar for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers , inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel complete as required size conforming to relavant IS specification. The panel should be CPRI approved and having dust , vermin proof, weather proof, IP- 54 protection including necessary foundation for mounting all as specified and directed. Incorporating the following :
(a) Incomming 150 A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. Thermal magnetic release type -1 No.. (b) Out going (i) 150 A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. Thermal magnetic release type- 2 Nos. (1 No. as spare) (ii) 63 A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. Thermal magnetic release type.- 2 Nos. (1 No. as spare) (c) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT (d) Indicator lamp LED for R,Y,B, with MCB. BUS BARS: (e) Bus bar 250 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. (For PAR )
Supply, installation, testing and commissioning of factory made powder coated compartmentalized cubicle LT Panel indoor type with canopy, fabricated from 3.15 mm thick CRCA sheet steel with necessary angle iron frame fabricated with 50x50x5 mm MS angle, weather proof vermin proof ,including chamber of aluminium bus bar for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers , inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel complete as required size conforming to relavant IS specification. The panel should be CPRI approved and having dust , vermin proof, weather proof, IP- 54 protection including necessary foundation for mounting all as specified and directed. Incorporating the following : (For PAR EB Panel )
(a) Incomming - 150 A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. microprocessor release type. -2 Nos. (b) Auto Transfer switch 160 A -1 No. c) Bus bar 250 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. (d) (i)Out going 100 A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. microprocessor release type. -2 Nos. (ii) 32 A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. microprocessor release type.- 2 No. (as spare). (iii) 25 A /16 A MCB 4 Pole C series .- 3 Nos. (1 spare) (iv) 10 A to 32 A MCB 2 Pole C series.- 4 Nos. ( 1 as spare) (e) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT (f) indicator lamp LED for R,Y,B, with MCB. requirement .
Supply, installation, testing and commissioning of factory made powder coated compartmentalized cubicle LT Panel indoor type with canopy, fabricated from 3.15 mm thick CRCA sheet steel with necessary angle iron frame fabricated with 50x50x5 mm MS angle, weather proof vermin proof ,including chamber of aluminium bus bar for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply complete with gland plates, lifting hooks, ventilating louvers , inter connections, earthing terminals, labeling , cable alley suitable for termination of cables including supply and fixing of following switchgear and accessories in the panel complete as required size conforming to relavant IS specification. The panel should be CPRI approved and having dust , vermin proof, weather proof, IP- 54 protection including necessary foundation for mounting all as specified and directed. Incorporating the following :
(a) Incomming . 63 A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. Thermal magnetic release type-1 No. (b BUS BAR: (b)Bus bar 100 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. (c) Out going . -(i) 63 A 415V, 4P, 25 kA MCCB having Overload, Short circuit and Earth fault Protection with Overvoltage and undervoltage protection. Thermal magnetic release type. -2 Nos. (ii ) 25A to 32 A, 4 Pole, MCB C Series- 3 Nos. ( 2 Nos. as spare). (iii) 10 A MCB 2 Pole C series - 2 Nos (d) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT (e ) Indicator lamp LED for R,Y,B, with MCB. (For PAR UPS Panel ) as per user requirement.
Supply, install, Testing & commisioning of on load Manual change over switch - Disconnector ( Confirm to IEC 60947-3, IS /IEC 60947-3) of 125 A , 415 V, SS Enclosure, Terminal Shrouds , Source separater and phase barrier , IP 43 Protection suitable of vertical as well as horizontzl mounting as per site requirement , Complete all as per specified & directed. Make L & T cat part No. CO21250OSOO and equivalent in Schenider, Havells. (at PAR bldg.)
Supply ,install , testing & commisioning of Servo Voltage stabilizer copper wound, for automatic operation /regulating of voltage comprising of auto transformer ,servo motor, intelligent micro controller based circuit, 3 phase 415 V, 50 HZ, naturally oil cooled indoor type for unbalanced load & designed for input variation beween 340 volt 460 volt with output voltage stabilized at 415 with accuracy +,- 1% and speed of correction 8 volt /sec , of capacity 100 KVA . responce time 10ms along with Suitable for all power factor load as per specification. LED for each phase to indicate Mains ON, Output ON, Incorporated by means of contractor to trip in event of Under voltage, over voltage, overload, single phasing alongwith audio alarm
Metering- Digital microprocessor Based cards for voltage, output load current with CT. Protection- Overload, short circuit, High / Low voltage cut off & Bypass arrangement to be provided. First filling of oil to be provided, Temp rise -50 degree C in oil, Control- Auto/ Manual, Insulation class -A, As per IS 9815 Fitting with four Plain Rollers, Two Earthing Terminals, Four Lifting Hooks, Oil filling Hole with Cap, Drain wall, oil level indicator, Sillica gel breather, Oil temperature indicator, Thermometer Pocket. Testing- All routine tests as per DGAQA & IS to be conducted & Test reports to be furnished alongwith equipment.
Supply, install , testing & commisioning of Isolation transformer of capacity 100 KVA indoor type complet with standard fittings,3 phase, 50 Hz 4 wire , 415 + 5%/ 415 +5% volts, ratio 1:1, Oil cooled potential difference between neutral to earth less than 1 Volt with off load tapping on to vary secondary voltage within limit . Note: Isolation transformer tested on high voltage insulated test transformer varnished with fine grade varnish in vaccum inpregnation plant. Efficiency -98.5-99% at Full load / UPF,Dielectric strenght 3KV for 2 min, copper wounded, Over load, short circuit, high/low cutoff protection .
Copper Winding Primary Delta & secondary star connected Tapping- Nil , Impedence 4 % Max, Input frequency- 47 to 53 HZ Insulation class H & Insulation resistance better than 100M ohms Fittings- Two lifting hooks, four plain rollers, Two earthing terminals, Base channels with Towing holes. Termination- Suitable links to be provided behind front door above gland place to accept bottom entry of cables. As per IS 2026 Testing- All routine tests as per DGAQA & IS to be conducted & Test Reports to be furnished along with equipment.
Supply & fix HDGI Octagonal pole 9 Meter height having top dia 70 mm and bottom dia 155 mm and thickness 3 mm, including heavy duty GI pile bracket with nuts & bolts, 4 Nos 'J' type foundation bolts of dia 16 mm and 450 mm long with base plate 16 mm thick all as specified and directed make: National pole agency / India Tube co / Zindal steel/ Crompton/ Bajaj
Excavation on post holes not exceeding 0.5 Cum for erection of poles removing the exavated materials to distance not excedding 50 meter and providing PCC bed and RCC foundation as per following including form work (i) PCC BED - 450 mmX 450mm X 100 mm (ii) RCC Column - 400 mm x 400 mm x 1300 mm , M 20 Design, using 4 Nos 12 mm Steel bar
Supply and fixing cable route indicator, consisting of 200mm dia 6mm thick cast iron to be painted with brown colour with inscription casting as HT Cable 11000 Volts grade as of laying cable potential,and fixed with and including hot dipped GI angle of size 40mm x 40mm x 6mm, 0.60m long, GI bolts, nuts embedded in ground in route of cable with and including PCC 1:3:6 type C2 of size 200mm x 200mm x 300mm all as directed
Supply installation & commisioning of silent Diesel Generator 415 V, 3 phase 4 wire , Comprising Diesel engine Alternator set, electric start , 4 stroke, engine as per IS 10001/10002 and alternator as per IS: 13364 complete with foundation( as per OEM desine) with AMF panel , control Panel with necessary meter and sound proof canopy as per CPCB norms, DG set should be able to run normally at 10 % more of rated capacity for 1 hour. capacity 160 KVA. ( FOR ASR Bldg.) complete with all necessary accesories
A. Diesel Engine:- (i) Radiator Cooling (iii) Flywheel with starter ring (iii)Dry type air cleaner (iv) Vacuum Indicator (v) Exhaust Silencer (vi) Inline fuel pump (vii) Water Pump (viii) Lub Oil Filter (ix) Lub Oil Pump (x) 24 V electric start system complete with starter, battery charging alternator (xi) Engine control panel consisting of starting key switch, lub oil pressure gauge, ammeter Safety shut down system for Low Lube oil pressure & High coolant temperature Engine maintenance manual with spare parts list. (xii) First fill of lube oil & coolant (xvii) Residential Silencer with cladding & supports (xiii) Residential Silencer with cladding & supports
B. ALTERNATOR :Alternator confirming toIS: 13364 Part II:1992 with standard design with IP 23 Protection, suitably rated at 128KW / 160 KVA at 0.8pf, 415 Volts, 3 phase, 4 Wires, 50 Hz., 1500 RPM, self excited (brushless excitation)and self regulated,Band of Voltage Regulation +/-1.5% of rated voltage (from no load to full load) and Class “H” Insulation. Alternator should be mounted on a common single base frame and coupled directly to the engine all as specified.
C. Acoustic Enclosure : Acoustic enclose as per norms of Central Pollution Control Board (CPCB) issued by Ministry of Environment & Forests, Government of India
E. ACCESSORIES: Base frame of sturdy design -1 set Battery 24 V maintenance free with leads & connecting accessories.-2 Nos Spare parts & tools (i) Rottary pump for diesel with 3 meter hose- 1 set (ii) Box spainer set complete all sizes make taparial – 1 set (iii) Oil filter- 2 Nos (iv) Air filter complete with element- 2 Nos (v) Fuel fiter set- 2 Nos (vi) AVR -1Nos (vii) Rubber matting size 0.9 mtr x 1.5 mtr 15 mm thick- 2 Nos (viii) Jerrican MS sheet capacity 20 Ltr- 2 Nos
NOTE :(i) PCC foundation shall deemed to be included in unit rate of DG set. PCC foundation of adequate/ required size extending 500 mm all-round more than size of DG set, as per manufacturer design.
NOTE :(i) PCC foundation shall deemed to be included in unit rate of DG set. PCC foundation of adequate/ required size extending 500 mm all-round more than size of DG set, as per manufacturer design. (ii) DG set shall be tested as type test, routine test as per IS in presence of rep of Accepting Officer. (iii) The contractor shall submit QAP (quality assurence programe) for DG set testing to factory. DG set shall be dispatch after inspection clearence by inspecting officer. (iv). prior to manufacturing the genral arrengement drawing design details of the DG set and AMF panel shall be got approved by GE.
Supply Fix & commisioning including wirring of obstruction light (Twin aviation light) LED type cast aluminium with polymer housing, general light spreading, life up to 50000 hours 240 v supply, connection with 2.5 sqmm multy stranded copper wire of 3 run ( not more than 15 M) for main, earth & neutral inrigid PVC conduit with necessary fixing measures in wall/ anteena base, stands etc. 9m above roof top with necessary holding measure secured at roof top/ anteena foundation with necessary PCC complete with separate control swith of 5 A on Independent board. Make: Bajaj/Philips/ CG for ASR bldg.
Supply and lay intrenches or fixed with walls / laid in floors DWC pipes of 40mm dia, 6mm thick.
Supply , Installation, testing & Commisioning of of RING MAIN UNIT( out door type) 1 incomming 4 out going with motorised VCB each of 11 KV , 630 A with Bus Coupler of capacity 630 A, 11KV (1 VCB RMU) rating having rupturing capacity of 350 MVA (as per relevent IS standered) complete with all standered accessories all as per described and directed As per IS standered. all required test certificate should be provided by contractor. Compleye all as specified and as directed at site.
The RMU description shall be as below. RMU-NON-Extensible 5 Vacuum circuit breaker , with motorised operation, with self powered series trip microprocessor based numerical earth fault & over current relay which shall be operated on power pack unit for protection including provision of interconnection between transformer & DG set through 95 sq mm Al cable Each VCB unit will have the following :- 1 ON/OFF/EARTH Indication. 2 Live Cable “ Indicating LEDs energized thru Capacitive Voltage Dividers. 3 Interlock arrangement between Cable cover & Isolator. 4 Cable box suitable for cable termination of suitable size XLPE cable. 5 Flexible boots Note-:all standered accesories should be provided with RMU unit. The contractor shall submit QAP (quality assurence programe) for RMU testing to factory. RMU shall be dispatch after inspection clearence by inspecting officer.
Supply ,fix insulating mat Elecsafe- AH- Insulated electrical matting as per IS 15652: 2006 Class B, working voltage upto 11 KV, 2.5 mm thickness, 1x5 m with one side fine chequered and other side anti skid small button .Make: Raychem/Jaipuria and equivalent
Supply ,fix insulating mat Elecsafe- AH- Insulated electrical matting as per IS 15652: 2006 Class A, working voltage upto 3.3 KV, 2 mm thickness, 1x5 m with one side fine chequered and other side anti skid small button .Make: Raychem/Jaipuria and equivalent
Supply & installation of copper wound transformer step down , outdoor type complete with standered fittings, HT 11 KV 3 Phase , LT 433 Volt,accordance with Dyn11, 3 phase 4 wire with off load tappings on HT side to vary secondary voltage with in limit in the steps of HV side to take care of voltage from +5 to (-) 15 % @ 2.5% to give output on 433V secondary side and including initial oil fitlling to appropriate level, control cable, and following standard fittings complete, all as per IS 1180 of capacity 750 KVA, 5 star BEE rating.
(i) Oil conservator with oil fitting hole cap and drain plug. (ii) 01 No of prismatic oil level gauge mounted on conservator wall with first fill of charge upto maximum level. (iii) Silica gel dehydrating breather with oil seal and with first fill of charge. (iv) Pressure release valve with automatic resetting arrangement after rlease of pressure- 01 Set (v) Adequate No of thermometer pocket including one thermometer. (vi) Top oil filter valve. (vii) Bottom oil filter cum drain valve. (viii) Rating diagram and terminal marking plate. (ix) Earthing terminal - 02 Nos (x) Lifting lugs - 01 Set. (xi) Jacking pads - 01 Set (xii) Under carriage with 4 Nos of plain rollers. (xiii) Air release plug on main transformer tank. (xiv) Adequate Nos of cooling radiators. (xv) 150mm dial type oil temperature indicator with maximum read pointer and resetting device. (xvi) 150mm dial type winding temperature indicator with maximum read pointer resetting device (xvii) Air insulated cables box on HV and LV side. (xviii) Full load & No load losses as per IS standered. (xix) Necessary wiring from trip terminals of buchholtz relay to control panel of HT switch gear. (xx) Terminal box for alarm and trip contacts
Supply, install and testing Isolation transformer of capacity 750 KVA indoor type complet with standard fittings,3 phase, 50 Hz 4 wire , 415 + 5%/ 415 +5% volts, ratio 1:1, Oil cooled potential difference between neutral to earth less than 1 Volt with off load tapping on to vary secondary voltage within limit . Note: Isolation transformer tested on high voltage insulated test transformer varnished with fine grade varnish in vaccum inpregnation plant. primary - 415 V 3 phase 3 wire Delta connection, secondary- 415 V 3 phase 3wire star connected, Efficiency -98.5-99% at Full load / UPF,Dielectric strenght 3KV for 2 min, copper wounded, Over load, short circuit, high/low cutoff protection .with following--
Copper Winding Primary Delta & secondary star connected. Tapping- Nil , Impedence 4 % Max Input frequency- 47 to 53 HZ Insulation class H & Insulation resistance better than 100M ohms Fittings- Two lifting hooks, four plain rollers, Two earthing terminals, Base channels with Towing holes. Termination- Suitable links to be provided behind front door above gland place to accept bottom entry of cables As per IS 2026 Testing- All routine tests as per DGAQA & IS to be conducted & Test Reports to be furnished along with equipment.
Supply ,install , testing & commisioning of Servo Voltage stabilizer copper wound, for automatic operation /regulating of voltage comprising of auto transformer ,servo motor, intelligent micro controller based circuit, 3 phase 415 V, 50 HZ, naturally oil cooled indoor type for unballanced load & designed for input variation beween 340 volt 460 volt with output voltage stabilized at 415 with accuracy +,- 1% and speed of correction 8 volt /sec , of capacity 750 KVA . responce time 10ms along with Suitable for all power factor load as per specification. LED for each phase to indicate Mains ON, Output ON,
Incorporated by means of contractor to trip in event of Under voltage, over voltage, overload, single phasing alongwith audio alarm Metering- Digital microprocessor Based cards for voltage, output load current with CT Protection- Overload, short circuit, High / Low voltage cut off & Bypass arrangement to be provided First filling of oil to be provided, Temp rise -50 degree C in oil, Control- Auto/ Manual, Insulation class -A, As per IS 9815 Fitting with four Plain Rollers, Two Earthing Terminals, Four Lifting Hooks, Oil filling Hole with Cap, Drain wall, oil level indicator, Sillica gel breather, Oil temperature indicator, Thermometer Pocket Testing- All routine tests as per DGAQA & IS to be conducted & Test reports to be furnished alongwith equipment.
Supply, Instalation, testing & Commissioning of 1250 amps rated Current of following Class of protection level mentioned as under Sandwich type Busduct System (Low impedence totally enclosed, non segregated) size busbar size ( phase/ neutral conductor) of 150mm x 5.2 mm (rectangular bar with rounded corner) of 1000 V, 50Hz, TPN with 100% Neutral with Copper conductor made from high Electrolyte Copper (ETP) grade Cu, conductivity not less than 99.9% insulated by Class F (PET Materials)having Current density 160 A/sq.cm with 1.5mm thick hot-galvanized sheet steel enclosure confirming IK-10 degree of Impact strength treated according to UNI 10327 and painted with RAL7035 resins with high resistance to chemical agents with three phase short time current withstand capacity of 75KA for 1 Sec , fire retardant including factory fitted Junction monobloc, IP-55 Joint Cover, Expansion Joint ( If straight length above 40 Mtrs), with MS Channel/angle for support, Elbow, Flanged End, Standard support brackets with 50x6 mm two runs of GI external earth strip and Busduct design will bein compliance with IEC-61439-6. Make: Legrand/ ABB/ Seimens/ L&T Note:- Rate of MS Channel/angle for support will be measured and paid separately (ii) Item shall be procured after installation of transformer 750 KVA capacity and connected LT Panels for exact site requirement. (iii) Cost is included in item/unit rate for 2 run of GI strip.
1250 A outdoor Busduct with IP 65 protection
1250 A indoor Busduct with IP 55 protection
1250 A Elbow with IP 65 protection
1250 A Elbow with IP 55 protection
1250 A Flange End with IP 65 protection
1250 A Flange End with IP 55 protection
1250 A Thermal expansion Unit L= 300 mm
Copper Flexible jumpers (TPN)
Copper shorting links
Adopter Box
Canopy made by 1.5 mm sheet steel with Duly painted for outdoor application
Supply ,install, testing & commisioning of APFC panel with MD-XL capacitor (super Heavy duty square capacitor with detuned reactor (Aluminium) of 3 mm thick and suitable size to accommodate capacitor bank of rating 350 KVAR comprising of step size (1x100 +3x50+3x25+2x10+1x5) KVAR 10 steps, super Heavy duty gas filled capacitors with copper busbar of rated capacity including MCCB as incomer, auto+manual switches, outgoing of corresponding rated MCCBs along with necessary contractors, Ammeter (0-800 A Digital type), Voltmeter (0-500 V) Digital type). Energy meter digital type with CTs, LED indication lamps complete with incoming cable and CTs alongwith control wiring and inbuilt exhaust fan with auto sensor for automatic operation when required complete all as specified and directed
Supply, install, Testing & commisioning of on load Manual change over switch - Disconnector ( Confirm to IEC 60947-3, IS /IEC 60947-3) of 1000 A , 415 V, SS Enclosure, Terminal Shrouds , Source separater and phase barrier , IP 43 Protection suitable of vertical as well as horizontzl mounting as per site requirement , Complete all as per specified & directed. Make L & T cat part No. CK90170BOOOand equivalent in Schenider, Havells. (for Isolation transformer & Servo voltage stabilizer) (at PS1)
Supply ,install, testing and commissioning of outdoor type LT panel board, factory made out of 3.15mm thick MS sheet fabricated, powder coated after seven tank process, mounted on MS equal angle iron 5mm thick, dust and vermin proof, with both side openable , hinged door and locking arrangement with IP 54 protection including 4wire Copper bus bar chamber with 1500 Amps rated bus bars mounted on insulator suitable for phase and neutral , complete wirring, and powder coated painting with synthetic enamel paint, fixed on platform PCC 1:4:8 type D2 coping with PCC 1:3:6 type C1 including provisioning of the following:- ( Main panel after transformer at PS1)
INCOMMER:- (a) ACB 1250 Amps, 50 KA 4 pole , microprocessor release (Adjustable Type),Manual drawout as incommer - 1 No. (b )Bus bar 1500 A rating of copper with epoxy based insulation for R,Y,B & Neutral OUT GOING (c) ACB 1000 Amps, 50 KA 4 pole , microprocessor release (Adjustable Type)- 4 No. With CC, TC, UV Coil (d) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT (e ) indicator lamp LED for R,Y,B, with MCB.
Supply ,install, testing and commissioning of outdoor type LT panel board, factory made out of 3.15mm thick MS sheet fabricated, powder coated after seven tank process, mounted on MS equal angle iron 5mm thick, dust and vermin proof, with both side openable , hinged door and locking arrangement with IP 54 protection including 4wire copper bus bar chamber with 1000 Amps rated bus bars mounted on insulator suitable for phase and neutral , complete wirring, and powder coated painting with synthetic enamel paint, fixed on platform PCC 1:4:8 type D2 coping with PCC 1:3:6 type C1 including provisioning of the following:- (at PS1 as per user requirement)
INCOMMER- (a) ACB 630 Amps(Adjustable Type), 50 KA 4 pole , microprocessor release, Manual drawout as incommer- 1 No. (b ) Bus bar 1000 A rating of aluminum alloy with epoxy based insulation for R,Y,B & Neutral. OUTGOING :- (i) MCCB 630 Amps, 50 KA 4 pole (Adjustable Type) , thermal magnetic release -1 No. (ii) MCCB 100 Amps, 25 KA 4 pole , thermal magnetic release (Adjustable Type) -2 Nos. (iii) MCCB 63 Amps, 25 KA 4 pole , thermal magnetic release (Adjustable Type) -4 Nos. (iv)10-20 A MCB TPN-01 No. (v) 40A MCCB, 10 KA 4 Pole - 03 Nos (d) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT (e ) indicator lamp LED for R,Y,B, with MCB. (For Ps1 )
Supply ,install, testing and commissioning of outdoor type LT panel board, factory made out of 3.15mm thick MS sheet fabricated, powder coated after seven tank process, mounted on MS equal angle iron 5mm thick, dust and vermin proof, with both side openable , hinged door and locking arrangement with IP 54 protection including 4wire alluminium bus bar chamber with 1500 Amps rated bus bars mounted on insulator suitable for phase and neutral , complete wirring, and powder coated painting with synthetic enamel paint, fixed on platform PCC 1:4:8 type D2 coping with PCC 1:3:6 type C1 including provisioning of the following:- (at PS1)
INCOMMER- (a) ACB 1000 Amps, 50 KA 4 pole , microprocessor release, as incommer- 2 No. (b ) Bus bar 1500 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. OUTGOING :- (c) ACB 1000 Amps, 50 KA 4 pole, microprocessor release -3 Nos. (d) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT (e ) indicator lamp LED for R,Y,B, with MCB. (For Ps1 )
Supply ,install, testing and commissioning of outdoor type LT panel board, factory made out of 3.15mm thick MS sheet fabricated, powder coated after seven tank process, mounted on MS equal angle iron 5mm thick, dust and vermin proof, with both side openable , hinged door and locking arrangement with IP 55 protection including 4wire alluminium bus bar chamber with 1500 Amps rated bus bars mounted on insulator suitable for phase and neutral , complete wirring, and powder coated painting with synthetic enamel paint, fixed on platform PCC 1:4:8 type D2 coping with PCC 1:3:6 type C1 including provisioning of the following:- ( Main panel after transformer at PS1)
INCOMMER- (a) ACB 1000 Amps, 50 KA 4 pole , microprocessor release, Manual draw out as incommer- 2 Nos. (b ) Bus bar 1500 A rating of copper with epoxy based insulation for R,Y,B & Neutral. OUTGOING :- (c) ACB 1000 Amps, 50 KA 4 pole, microprocessor release -3 Nos. (d) Manual change over switch 4 Pole without enclouser 1000A- 1 No. (e) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT (f ) indicator lamp LED for R,Y,B, with MCB.
Supply ,install, testing and commissioning of outdoor type LT panel board, factory made out of 3.15mm thick MS sheet fabricated, powder coated after seven tank process, mounted on MS equal angle iron 5mm thick, dust and vermin proof, with both side openable , hinged door and locking arrangement with IP 65 protection including 4wire alluminium bus bar chamber suitable for phase and neutral , complete wirring, and powder coated painting with synthetic enamel paint, fixed on platform PCC 1:4:8 type D2 coping with PCC 1:3:6 type C1 including provisioning of the following:- (at PS2) .
(a) INCOMMER- Supply and install MCB 250 Amps, 36 KA 4 pole , microprocessor release as incommer- 1 No. BUS BARS:- (b) 400 A rating of aluminium alloy with epoxy based insulation for R,Y,B & Neutral. OUT GOING:- (c ) (i) MCCB 100 Amps, 25 KA 4 pole , thermal magnetic release -1 no. (ii) MCCB 40 Amps, 25KA 4 pole , thermal magnetic release -3 Nos. (iii) MCB 32 Amps, 10 KA 4 pole , C series - 2 Nos (e) Multifunction electronic digital display meter suitable for reading current , Voltage, frequency, PF, load with suitable CT (f ) indicator lamp LED for R,Y,B, with MCB.
Material & labour for Earthing complete with GI earth plate electrode of size 60cm X 60cm X6 mm thick burried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, earth plate surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connectionsusing galvanized earth lead wire 4 mm dia as earthing lead by means of bolts, Nuts, check Nuts and washers of galvanized iron or steel and protected by medium grade 40mm dia galvanised iron pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1:2:4 type B-2 (including necessary GI earth wire for connection with DB and excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown on plate No 3 of SSR Part-I 1991. (for lightening arrester)
Note: (i) Cost of GI earth strip and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item (ii) The unit rate shall include for Earth work and protection of GI pipe, GI water pipe, wire mesh, funnel, excavation, RCC pit cover, P.C.C chamber pit,. test point, 4mm GI wire from top of earth plate upto 5 metres above ground level. (iii) PCC pit shall be provided at least 500mm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipes and fitting junction etc shall be deemed to be included in the unit rate.
M&L for earthing complete with Copper earth plate eletrode 600 mm x 600 mm x 3.15 mm thick burried directly in groung (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Copper earth strip 20x3 mm connected by means of bolts, nuts, check nuts and washer of galvanised iron or steel, provision of 50 mm dia GI pipe light grade for protection of copper earth strip and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) , type C1 chamber, MS funnel, wire gauge, 50 mm thick RCC 1:2:4, type B1 earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I
Note: (i) Cost of GI earth strip and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item (ii) The unit rate shall include for Earth work and protection of GI pipe, GI water pipe, wire mesh, funnel, excavation, RCC pit cover, P.C.C chamber pit,. test point, 4mm GI wire from top of earth plate upto 5 metres above ground level. (iii) PCC pit shall be provided at least 500mm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipes and fitting junction etc shall be deemed to be included in the unit rate.
M&L for Chemical earthing complete with Copper earth plate eletrode 900 mm x 600 mm x 5 mm thick burried directly in groung (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick and packed layer of soil enhancement compound having high moister retention capability, very high electrical conductivity, high thermal stability, corrosion resistance, filling in prper way and in required thickness and electrode connections by using Copper earth strip 50x6 mm connected by means of bolts, nuts, check nuts and washer of galvanised iron or steel, provision of 50 mm dia GI pipe light grade for protection of GI earth strip and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) , type C1 chamber, MS funnel, wire gauge, 50 mm thick RCC 1:2:4, type B1 earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I
Note: (i) Cost of copper earth strip and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item (ii) Resultant Impedence should be in order of 0.1 Ohm. (iii) The unit rate shall also includes for Wire mesh, funnel, excavation, PCC chamber pit, test point (iv) PCC pit shall be provided at least 0.5Mtr away from the earth pit and not just on the earth pit
Earthing conductivity conductor or main earthing lead copper 50x6mm fixed to wall on batten or chases or burried on ground or drawn in pipe fixed to pole or any other situation as required complete as directed at site
Earthing conductivity conductor or main earthing lead copper 20x3 mm fixed to wall on batten or chases or burried on ground or drawn in pipe fixed to pole or any other situation as required complete as directed at site ( for Copper Earthing)
Supply, laying & fixing in trenches Double wall corrugated (DWC) pipes made of High density Polyethylene (HDPE) with all accessories i.e Rubber joint with synthetic solvent, Elbows, Bends & End caps etc. complete of following sizes:-
100mm dia
50 mm dia
25 mm dia
OFC route indicator of size 30cmx20cmx4cm thick, engraved "OFC" both side made out of PCC 1:3:6 type C1, using 20mm stone aggregate and necessary foundation work in same aggregate. (185 Nos Approx.)
Supply & fix 10mm dia asbestos rope for extension of DG exhaust all as directed.
FIRE FIGHTING: Supply & fixing CO2 fire extinguisher of 3KG capacity, .fitted with discharge control valve, with ISI mark with discharge hose complete with initial charge as per IS :15683 with ISI mark and wall bracket , complete all as specified and as directed.make:- MTS Technologies Ltd , Omex Technology or any other approved make
Material & labour for Dry chemical powder type fire extinguisher of 6 Kg capacity , fitted with gunmetal union cap assembly of suitable capacity as per IS 4947 with ISI mark and powder as per IS 4308 with ISI mark with discharge hose and applicator complete with initial charge as per IS : 10658 with ISI mark complete all as specified and as directed. MTS Technologies Ltd or any other approved make
Material & labour for Dry chemical powder type fire extinguisher of 9 Kg capacity , fitted with gunmetal union cap assembly of suitable capacity as per IS 4947 with ISI mark and powder as per IS 4308 with ISI mark with discharge hose and applicator complete with initial charge as per IS : 10658 with ISI mark complete all as specified and as directed. MTS Technologies Ltd or any other approved make
Supply and install AFF mechanical Foam type fire extinguisher of 9 ltrs capacity, .fitted with discharge control valve( squeeze grip type) inside Foam partical catridge of as per IS with ISI mark with discharge hose and open nozzel complete with initial charge as standered, with ISI mark and wall bracket , complete all as specified and as directed.make:- MTS Technologies Ltd or Omex or any other approved make
Material & labour for Dry chemical powder type fire extinguisher of 25 Kg capacity , fitted with gunmetal union cap assembly of suitable capacity as per IS 4947 with ISI mark and powder as per IS standered with discharge hose and applicator complete with trolly mounted initial charge with ISI mark complete all as specified and as directed. MTS Technologies Ltd or any other approved make
Supply and fix control cable armoured (2XWY/2XFY) 1.5 sqmm 6 core
AIR CONDITIONING
Design ,supply, installation, testing & commisioning of central type AC plant suitable for maintaining the tempreture 22o C ( + ) 2o C and relative humidity < 55 % in side the room. Typical design parameter are given below . The AC plant should be comprising of two running and one standby compressor unit including AHU, Condensor, Colling Tower, Colling system including pump & motor with standby arrangement , ducting with thermal insulation. Refrigerent gas to be used R- 407c / R- 410a. The AC plant should be VRV / VRF type. Tentitive Plant capacity 44 TR Standby supply DESIGN PERAMETRES: (a) Height of bldg 25M(Drg Enclosed) (b) Dimension of each floor 9mx9mx4.2m (c) Floors to be airconditioned : 1st, 2nd and 4th (Ref Bldg Drawing). (d) Detail viz. No of persons, load of equipment, etc. attached at Appx. (e) AC plant shall be nstalled at ground floor. Note: (i) Site inspection to be carried out by the bidder before deigning the AC plant. (ii) Design of Ac plant shall be approved by competent Engineer authority of MES before placing the order. (iii) Installation to be donr in presence of OEM Rep.
NOTE AS PER CFEES RECOMMENDATION :- following points should be considered. Insulation and lining including vapour barrier & coating used in conjuction with dut shall be of non combustible type material . All filter for use in the air conditioning system shall be such that it will not burnt freely or emit large volume of smoke or other objectionable products of combustion when attacked by flame. In case of fire incidence, to stop or restrict the flow of hot gases/flame from one room, compartment zone or section to the other room, compartment, zone or section, the AC duct shall be provided with the arrangement of Fire Dampaer/Stoppers, actuating at a pretdetermine temparture by means of a fusible link or an electro megnatic device operated by either a smoke detector system or failure of pwer supply, thereby emitting audit-visual alarm. (b) Dampers shall be installed in the inlet ducts at the pont of originating from AC plant room and at all points of entry or exit where the return duct pass from one room or compartment to the other room or compartment. (c) Arrangement shall exist to switch 'off' the plant automatically on sounding of alarm and also from the working place manually.
Supply and install high wall split units indoor / outdoor complete inverter type with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2 with necessary copper pippe connection between indoor & outdoor, starter etc of capacity 1.5TR ,and making disturbed surface good with provision of 3/4" dia pvc pipe as drainage of accumulated water including properly fixing on wall ,coloumn etc. complete all as specified & as directed at site. Make Blue star, Hitachi, voltas.
Supply and install high wall split units indoor / outdoor complete inverter type with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2 with necessary copper pippe connection between indoor & outdoor, starter etc of capacity 1.5TR ,and making disturbed surface good with provision of 3/4" dia pvc pipe as drainage of accumulated water including properly fixing on wall ,coloumn etc. complete all as specified & as directed at site. Make Blue star, Hitachi, voltas.
Chain Pully Block : Supply install testing & commisioning of motorised chain pully block suitatable for lifting of 2 Ton load at a height of 25 M from ground level, having hardened steel gear teeth up to addendum , frictional break system , hardened hook to withstand shock load , all as per relevant IS standered complete.
UPs :Supply install testing & commisioning of UPS 2KVA, single phase AC supply160 to 260 Volts and output 230 V +- 1% 30 min power backup . Comprissing of 12V/12Ah x6 no. SMF Batteries. With 24 month UPS warranty & 12 month warranty cover on battery . complete all as describe and as directed. Make: Microtech/ APC Scheinder/ Luminous
Water Cooler : Supply and Install water cooler stainless steel body, electric driven single phase having appx storage cap of 80 ltrs and normal cooling capacity of 40 ltrs per hour. Make - Blue star, Voltas/ equivalent.
Anti Static Flooring : Earthing conductivity conductor or main earthing lead copper 20x3 mm fixed to wall on batten or chases or burried on ground or drawn in pipe fixed to pole or any other situation as required complete as directed at site ( for anti static flooring)
M&L for earthing complete with Copper earth plate eletrode 600 mm x 600 mm x 3.15 mm thick burried directly in groung (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Copper earth strip 20x3 mm connected by means of bolts, nuts, check nuts and washer of galvanised iron or steel, provision of 50 mm dia GI pipe medium grade for protection of copper earth strip and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) , type C1 chamber, MS funnel, wire gauge, 50 mm thick RCC 1:2:4, type B1 earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I . Note: (i) Cost of GI earth strip and GI protection pipe upto 7.5mtr length shall be deemed to be included in the rate quoted for this item. (ii) The unit rate shall also includes for Wire mesh, funnel, excavation, PCC chamber pit, test point . (iii) PCC pit shall be provided at least 0.5Mtr away from the earth pit and not just on the earth pit
Test point terminal block made of gun metal or phosphorous bronze size 75x75x25 mm drilled and screwed including 3 no. 8mm dia 25 mm long hex head screw.
PILE FOUNDATION : Drilling/ boring through any type of soil (soft/ loose soil or hard/ dense soil) up to the depth as directed/ indicated for 600mm outer dia bored cast-in-situ vertical piles duly stabilising the sides by drilling fluids (Reverse or DMC method) or by driving 6mm thick casing pipe upto loose strata or refusal level or by any other approved method and disposal of drilled/ bored material to a distance exceeding 50m and not exceeding 100m all as specified and shown on drawings.
Carrying out / conducting standard penetration test all as per IS - 2911 Part-IV -1985 in the strata where pile is proposed to be rested/ terminated including bringing at site all testing equipment, making arrangement for testing and removal of the same after completion and recording the test results and preparing the test sheets complete for 600mm dia piles all as specified and directed.
Carrying out / conducting testing of pile for Initial load test all as per clause 6.1.5 & 6.1.6 of IS - 2911 Part-IV -1985, for 300 MT safe load on test pile of 600mm bore including bringing at site all testing equipment, making arrangement for testing and removal of the same after completion and recording the test results and preparing the test sheets complete all as specified and directed.
Carrying out / conducting testing of pile for Routine load test all as per IS - 2911 Part-IV -1985 for 220 MT on working pile of 600mm bore including bringing at site all testing equipment, making arrangement for testing and removal of the same after completion and recording the test results and preparing the test sheets complete all as specified and directed.
Subtotal
Sant Construction Co.
RAVI REALCONS PRIVATE LIMITED
P NAIDU
surendra infrastructure pvt ltd
PRASHANTH ERECTOR AND BUILDERS PVT LTD
B D Raizada Projects Pvt Ltd
A K BANSAL AND CO
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid