Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹39.9 LAccepted-AOC D1C 47A JANAK PURI NEW DELHI 110058 | NEW DELHI | DELHI | DELHI | 110058 | L-1 | Accepted-AOC L-1 | |
| 2 | L-2₹45.5 L+₹4.3 L (10.4%)Rejected-AOC WZ 409 0 B 1ST FLOOR PLOT NO 12 JANAK PARK HARI NAGAR NEW DELHI 110064 | NEW DELHI | WEST DELHI | DELHI | 110064 | L-2 | Rejected-AOC L-2 |
Tender Value
Refer Docs
EMD Value
₹99,000
Closing Date
26 Feb 2022, 6:00 pmClosed
GE I RND Delhi
MILITARY ENGINEER SERVICE, GARRISON ENGINEER I RND, LUCKNOW ROAD, TIMARPUR, DELHI-110054
MISC REPAIR/REPLACEMENT AND MAINTENANCE OF CENTRAL AC PLANT AT SHALAKA HANGER, LASTEC OLD MAIN BLDG, ISSA BLDG AND CONNECTED WORKS OF METCALFE HOUSE AREA UNDER GE I RND DELHI
2021_MES_495982_1
GE/RND-88/DLI/2021-2022
Open Tender
Civil Works
Item Rate
270 days
Delhi
Class-D, Cat c(i)
2 documents required · 2 mandatory
₹500
GE I RND Delhi
₹99,000
Yes
21 Mar 2022
18 Dec 2021
28 Feb 2022
18 Dec 2021
26 Feb 2022
14 Feb 2022
Amount
Supply, Installation, commissioning and testing condensing coil for 2 x 60 TR AC Plant including installation of New coil with Brazing, Vaccuuming including taking down old userviceable condensing coil as per existing OEM of make - Blue star complete all as specified and directed.
M&L for Epoxy protective coating on Copper piping system, headers (Discharge line, Liquid line, all open fittings of copper, suction line etc) for 2 x 60 TR AC plant of make - Blue star complete all as specified and directed.
Supply and charging the refrigerant R-22 for 2X60 TR chiller type AC plant of make - Blue star including testing complete all as specified and directed.
M&L for Pressure testing with Application of Nitrogen Gas and replacement of Spares/Consumable for 01 Chiller application to find out any leakage, brazing and stopping of all leakage detected, re-application of nitorgen pressure to ensure leak proof gas circulator system flushing out the nitrogen gas complete all as specified and directed.
S&F in replacment of Coolant for topping up of compressor for 2 x 60 TR AC plant of make - Blue star as per OEM all as specified and directed (1 Can = 18.9 Ltrs).
S& F in Replacement of Compressor oil (Blue Star, L5 Gal Pail) for 2 x 60 TR AC plant of make - Blue star complete all as specified and directed.
M& L for Servicing of complete AC plant 2x60 TR of make - Blue star including electrical panels, VSD Panels & setting of all parameters all as per OEM complete all as specified and directed.
S&F in replacement of old unserviceable FILTER DRIER 3/8 0RFS for 2 x 60 TR AC Plant of make - Blue star as per existing OEM complete all as specified and directed.
S&F in replacment of old unserviceable CTG DEHY 100 PERCENT MOLECULAR for dehydrator for refrigrant circuit for 2 x 60 TR AC Plant of make - Blue star complete all as specified and directed.
S&F in replacment of old unserviceable Oil Filter for 2x60 TR AC plant of make - Blue star as per existing OEM complete all as specified and directed.
S&F in replacment of old unserviceable O- RING size 2.62 x 81.97 mm for 2x60TR AC plant of make - Blue star as per existing OEM for each circuit complete all as specified and directed.
M&L for overhauling of pump and motor 7.5 HP -15 HP capacity by opening up and cleaning of all parts such as impeller , rotor, stator, fan cover, greasing including replacing all unserviceable/damaged part like impeller, bearing bush,seal,shaft,coupling, machine work etc and reconnecting back and testing complete all as specified and directed.
Disconnecting, dismantling and strip opening of the existing air handling unit of any description and in any position and of capacity of 10000 CFM to 25000 CFM for overhauling and servicing, including cleaning of cooling coils with chemical including taking out existing shaft, blower drum, pulley and de-humidifier pump etc of air handling unit, checking thoroughly serviceability of the parts, fixing the serviceable parts in positiion, replacement of the defective/non functional/unserviceable parts/spares, reassembling, commissioning, fixing in position and testing of the air handling unit on full load for its smooth and trouble free operation complete all as specified and directed. Note : Spare parts i.e V- belt, filters for AHU, Bearing & pulley are measured and paid separately under respective items
BLANK
S&F in replacement of Bearing and bearing hub as per existing size suitable for AHU 10000 CFM to 25000 CFM complete all as specified and directed.
S&F in replacement of metal pulley with hub as per existing size suitable for AHU 10000 CFM to 25000 CFM complete all as specified and directed.
S&F in replacement of V belt of size A42 complete all as specified and directed.
S&F in replacement of V belt of size A43 complete all as specified and directed.
S&F in replacement of V belt of size A46 complete all as specified and directed.
S&F in replacement of V belt of size A48 complete all as specified and directed.
S&F in replacement of V belt of size A49 complete all as specified and directed.
M&L for pre filter section with 50mm thick with GI frame metal viscous/ washable synthetic type air prefilters (EU-4, 90% down to 10 micron), fine filter (EU-7, 99% down to 3 micron) as per existing size (600mm x 600 mm) and as per OEM specification complete all as specified and directed.
Supplying, laying/ fixing, testing and commissioning for chilled water piping plumbing of size 150 mm dia MS pipes class 'c' (heavy class) IS-1239 (75 mm insulation) inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated PUF moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date ) at joints repairing of damage to building etc. as per specifications and as required including taking out old unserviceable complete all as specified and directed.
All as per item No 23 but of size 125 mm dia MS pipes (50 mm insulation)
All as per item No 23 but of size 100 mm dia MS pipes (50 mm insulation)
All as per item No 23 but of size 80 mm dia MS pipes (50 mm insulation)
All as per item No 23 but of size 65 mm dia MS pipes (50 mm insulation)
All as per item No 23 but of size 50 mm dia MS pipes (50 mm insulation)
Supply,installation,testing and commissioning for "B" class GI drain piping 80 mm dia complete with fitting etc & 25 mm thick PUF insulation with sealing tapes & 28 G Aluminium cladding complete including taking out old unserviceable complete all as specified and directed.
M & L for Insulation of M S Pipe bore of pipe 40 mm dia with PUF slab 30 mm thick with and including applying bituminuous compound and GI cladding with 26 gauge GI sheet including taking out old unserviceable complete all as specified and directed.
All as per item no 30 above but bore of pipe 50 mm dia
All as per item no 30 above but bore of pipe 65 mm dia
M & L for Insulation of M S Pipe with PUF slab 40 mm thick with and including applying bituminuous compound and GI cladding with 26 gauge GI sheet complete of size 80 mm dia Pipe complete all as specified and directed.
All as per item no 33 above but bore of pipe 100 mm dia
All as per item no 33 above but bore of pipe 125 mm dia
All as per item no 33 above but bore of pipe 150 mm dia
Supplying, fixing, testing and commissioning of BUTTERFLY VALVE 150 mm dia (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot water circulation as specified valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications including taking out old unserviceable complete all as specified and directed.
All as per item no 37 above but bore of valve 100 mm dia
All as per item no 37 above but bore of valve 80 mm dia
All as per item No 37 above but bore of valve 65 mm dia
S&F in repair BALANCING VALVE 125 mm dia WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation complete all as specified and directed.
All as per item No 41 above but bore of valve100 mm dia
All as per item No 41 above but bore of valve 80 mm dia
All as per item No 41 above but bore of valve 65 mm dia
All as per item No 41 above but bore of valve 50 mm dia
S&F in repair Y - STRAINER 125 mm dia of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation complete all as specified and directed..
All as per Item No 46 above but 100 mm dia
All as per Item No 46 above but 80 mm dia
All as per Item No 46 above but 65 mm dia
All as per Item No 46 above but 50 mm dia
All as per Item No 51 above but 50 mm dia
S&F in repair Bellows type rubber expansion joints 125 mm dia for Chilled water piping located at Pump inlet & exit, AHU inlet & exit and at chiller inlet & exit. Complete with double bellows, tie rods, MS flanges, necessary hardware and gaskets etc., with insulation of following sizes:
All as per Item No 53 above but 100 mm dia
All as per Item No 53 above but 80 mm dia
All as per Item No 53 above but 65 mm dia
All as per Item No 53 above but 50 mm dia
S&F in repair in position the industrial type pressure gauges 0-500 PSI with SS-304 valves and syphone bend complete all as specified and directed.
S&F in position the mercury in glass industrial type thermometer complete all as specified and directed..
Supply,installation,testing and commissioning of proportional type cooling and heating thermostats for the various Air Handling Units complete with required control wiring/installation kit etc. all as specified and directed.
Supply, fabricating and installing perforated M.S. cable trays of size 50 x 450 x 50 x 2 mm thick including horizontal and vertical bends, reducers, tees, cross members and other accessories as required, and duly suspended from the ceiling with M.S. suspenders, including painting etc complete all as specified and directed.
All as per Item 61 above but 50 x 200 x 50 x 2 mm thick
All as per Item 61 above but 50 x 150 x 50 x 2 mm thick
M&L for laying of in trenches insulated, armoured heavy duty XLPE electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 sq. mm 3.5 core as main power cable to chiller control panel including taking down old unserviceable cable complete all as specified and directed.
M&L for laying in trenches insulated, armoured heavy duty XLPE electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sq. mm 3.5 core as main power cable to AHU Panel including taking down old unserviceable cable complete all as specified and directed.
M&L for laying in trenches insulated, armoured heavy duty XLPE electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95 sq. mm 4.0 core as main power cable to AHU Pane including taking down old unserviceable cable complete all as specified and directed.
M&L for laying in trenches insulated, armoured heavy duty XLPE electric cable with copper conductor, 1100 volts grade, cross-sectional area 16 sq. mm 3.0 core as main power cable to Motor connecton/Compressor including taking down old unserviceable cable complete all as specified and directed..
All as per Ser Item No. 67 but 25 Sqmm 3.0 Core
M&L for overhauling of electric motor and blower of AHU including rewinding with super enamelled copper winding wire of existing gauge of capacity 5 to 7.5 HP by opening up and cleaning of all parts such as impeller , rotor, stator, fan cover, greasing including replacing all unserviceable/damaged part like impeller, bearing, bush,seal,shaft,coupling,machine work etc and reconnecting back and testing complete all as specified and directed.
M&L for overhauling of electric motor and blower of AHU including rewinding with super enamelled copper winding wire of existing gauge of capacity 10 to 15 HP by opening up and cleaning of all parts such as impeller , rotor, stator, fan cover, greasing including replacing all unserviceable/damaged part like impeller, bearing, bush,seal,shaft,coupling,machine work etc and reconnecting back and testing complete all as specified and directed.
Supply,assembly and erection of PGI sheet 22 gauge with TDF flange rectangular/square duct made out of 'L'shape hollow profile ,duly factory boxed including all accessories such as Corner ,Cleat,Carriage bolt,Gasket and appropriate sealant on longitudinal joints etc including taking down old rusted duct complete as per drawings and specifications complete all as specified and directed.
All as per ser Item No. 71 above but PGI sheet 20 gauge
M & L for duct insulation with resin bonded fibre glass wool roll of density 24 Kg /Cum and 40mm thickness with factory laminated aluminium vapour barrier , thickness of insulation as specified and including the following:- (a) M & L for cleaning the duct surface( to be insulated ) by scrapping carefully with wire brush etc. to make the surface completely free of mild scale ,durt,dust, grease and other foreign materials, taking special care so that all duct joints are sealed against any leakage. (b) M & L for applying rubber based adhesive CPRX compound. (c) M & L for sealing of all longitudinal joints and circular overlaps with and including aluminium foil tape 50 mm wide, to make the insulation leakproof. (d) M & L for securing the insulation with and including mechanically fastened nylon / steel straps of size 12mm / 50mm at maximum intervals of 1.2 mtr.
M&L for painting of all metal surfaces of Cetral AC plant 2x80 TR comprising 04 Nos chiller plant, Chiller Pump Motors, Hot water Generator Unit, LT Panel for AC Plant and AHUs with spray gun with two coats of synthetic enamel heat resistant paint matching the existing colour including preparation of old painted surfaces/removing old faded/rust/ cemented material off the surface complete all as specified and directed.
M&L for painting of Cetral AC plant 2x60 TR complete ( i.e 02 Nos chillers unit, compressor, condensers, Condensing pipes, Chillers pump motors, Condensing pump motors, LT Panel for complete AC Plant etc) with spray gun with two coats of synthetic enamel heat resistant paint matching the existing colour including preparation of old painted surfaces/removing old faded/rust/cemented material off the surface complete all as specified and directed.
S&F in replacement of mild steel work (MS angle iron, flat iron & bracing ) for supporting chilled water pipe, condesing pipe, base channel for pump motor or any other requirement at site including necessary fabrication, welding nuts & bolts complete all as specified and directed.
M&L for prepartion of new steel surface and applying two coats of synthetic enamal paint over a coat of red oxide primer complete all as specified and directed.
S&F in replacement of MCCB 630 Amps 4 Pole breaking capacity 35KA including taking down old burnt MCCB complete all as specified and directed.
S&F MCCB 250Amps 4 Pole breaking capacity 35KA Microprocessor release including taking down old burnt MCCB complete all as specifed and directed.
S&F MCCB 160 Amps 4 Pole breaking capacity 25KA Microprocessor release including taking down old burnt MCCB complete all as specifed and directed.
S&F in replacement of power contactor of MNX - 45 three pole complete all as specified and as directed.
S&F in replacement of HRC fuse link DIN type 400 Amps, 100 KA , 415 volt complete all as specified and as directed.
S&F in replacement of HRC fuse link DIN type 80 Amps 100 KA , 415 volt complete all as specified and as directed.
Supply only digital Psychrometer with psycrometric chart - 01 No. and Digital Anemometer - 01 No.
M&L for repair for hot water generator of capacity 20 KW in five banks complete with one slave bank controlled by semi conductor rectifier & other necessary controls, electrical panels including control wiring with 2.5 sqmm multistranded copper FRLSH cable complete all as specified and directed.
M&L in repairs earthing complete with galvanised earth plate electrode size 600 x 600 x 6mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level ) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to GI earth strip 32 x 6 mm as earth strip by means of nuts bolts, nuts check nuts and galvanised iron or steel including earth work in any type of soil, GI funnel with GI mesh charcoal salt 15 cm alternate layer and around the earth plate as shown in electrical plate Nos 3 of SSR Part I 2009, 20 mm dia watering pipe medium grade 1.70 mtr long GI protection pipe light grade 40 mm dia from earth pit to main board & testing on completion :- (a) GI earth strip 32 x 6 mm (b) Watering pipe GI medium grade 20mm dia from top of the earth electrode up to Ms funnel with wire mesh embeded in floor of PCC earth pit. (GI funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitab le for watering of earth pits). (c) Excavation & earthwork in any type of soil PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15 mm thick plaster in cement mortar 1:6 including RCC pit cover 50 mm thick 1:2:4 type B 1 reinforced with 8mm dia mild steel TMT bar 75mm centre to centre with 2 Nos MS handles of 12 mm dia suitable for carrying of pit cover.
M&L Earth continuity conductor or main earthing lead fixed to wall, on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6mm galvanised iron strip including taking down old unserviceable strip all as specified and directed.
S&F in replacment of old unservicable single phase preventer kit compete all as specified and directed.
S&F in repair timer electronic type complete all as specified and as directed.
S&F in repair power contactor of MNX - 25 complete all as specified and as directed.
S&F in repair of LP switch complete all as specified and as directed.
S&F in repair of HP switch complete all as specified and as directed.
S&F in repair of refrigerant copper pipe 15mm complete all as specified and as directed.
S&F in repair of refrigerant copper pipe 12 mm complete all as specified and as directed.
Supply, installation, testing and commissioning in replacement of gun metal auto air vent valve of 15 mm dia complete all and specified and directed.
Supply and fixing in replacement including testing of chiller water flow valve with electric control and other works as required at site to make the system functional incl welding as required at site etc complete all as specified and as directed.
Supply and fixing in replacement including testing of thermostatic expansion valve for 2x60 TR AC Plant complete all as specified and directed.
MOTOR CONTROL PANEL FOR AC PLANT Supply, fixing, testing and commissioning of factory made and tested (incl proto type being CPRI test certified) cubicle type MV panel out door type consisting of the 3 phase, 415 volt, 25 MVA rupturing capacity made of 3.15 mm thick 2500 x 2000 x 750 mm (approx) CRCA sheet powder coated conforming to IP-64, out door type including interconnection wiring (internal wiring with PVC insulated, copper conductor, FRLS cables IS-694 marked of adequate size but not less than 1.5 sqmm.), indicating lamps etc. The cubicle panel shall be free floor standing type, complete with interlocking arrangement & earth bus. The panel shall have compartmentalized arrangement to accommodate one feeder in each compartment. A vertical cable alley of suitable width shall be provided to serve one or two vertical feeder sections. Also the openings between the busbar chamber and the feeder section shall be shrouded with Bakelite/hylam sheet with minimum 3 mm thickness. All the hardware used in fabrication of panel shall be galvanized with zinc passiveness. The scope of work includes the following including dismantling & taking out old unserviceable complete :-
Main LT Panel Supply, fixing, testing and commissioning of factory made and tested (incl proto type being CPRI test certified) cubicle type MV panel out door type consisting of the 3 phase, 415 volt, 25 MVA rupturing capacity made of 3.15 mm thick 2500 x 2000 x 750 mm (approx) CRCA sheet powder coated conforming to IP-64, out door type including interconnection wiring (internal wiring with PVC insulated, copper conductor, FRLS cables IS-694 marked of adequate size but not less than 1.5 sqmm.), indicating lamps etc. The cubicle panel shall be free floor standing type, complete with interlocking arrangement & earth bus. The panel shall have compartmentalized arrangement to accommodate one feeder in each compartment. A vertical cable alley of suitable width shall be provided to serve one or two vertical feeder sections. Also the openings between the busbar chamber and the feeder section shall be shrouded with Bakelite/hylam sheet with minimum 3 mm thickness. All the hardware used in fabrication of panel shall be galvanized with zinc passiveness. The scope of work includes the following including dismantling & taking out old unserviceable complete :-
S&F in repair glossy sign board made of stainless steel for Central AC plant 2x80 TR and 2 x 60 TR installation size 2.5X1.5 (LxW) as per sample the `Military Engineer Services, MES logo and plant details to be written on the board including necessary excavation, PCC work in 1:2:4, and providing SS pole 50mm dia 2x2 mtr high above ground level, complete all as specified and directed Note : Details of plant shall be written on board as directed by the Engineer-in-Charge.
Supply & fixing in replacement Finned strip heater 3.0 KW suitable for fixing in various AHU of AC Plants complete all as specified and directed.
Flint India
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .