| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.2 LAdmitted-Finance E 2 216 GROUND FLOOR SHIV RAM PARK NEAR LUCKY GARDEN NANGLOI NEW DELHI 110041 | WEST DELHI | DELHI | 110041 | ₹29.2 L | L1 | Admitted-Finance |
| 2 | L2₹29.5 L+₹27,444 (0.94%)Admitted-Finance X 125 NEW ROSHANPURA SHAHEED RAJESH GILL MARG NAJAFGARH SOUTH WEST DELHI DELHI 110043 UDYAM DL 10 0019190 06AADCJ2143B1Z8 B 07AADCJ2143B1Z6 R MSME STATUS AS VERIFIED | WEST DELHI | DELHI | 110043 | ₹29.5 L+₹27,444 (0.94%) | L2 | Admitted-Finance |
| 3 | L3₹35.6 L+₹6.4 L (22.1%)Admitted-Finance | ₹35.6 L+₹6.4 L (22.1%) | L3 | Admitted-Finance |
| 4 | Rejected-Technical PLOT NO 89 90 UDYOG KENDRA II ECOTECH III GREATER NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201310 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201310 | - | - | Rejected-Technical Documents not submitted as per NIT |
| Sl No | Description | Qty | Unit | Supertech Engineers L1 | Hemcool Engineers L3 | JUHI AND JAI CONTRACTORS PVT LTD L2 |
|---|---|---|---|---|---|---|
| 1.00 | Supply Installation Testing and Commissioning of Induced draught counter flow FRP Cooling Tower of 350 TR having dimensions (3720 mm x 4330 mm x3385 mm) with cooling tower components, FRP casing, FRP basin, base frame (galvannised), Fills, fittings with Louvers dynamically balanced axial flow type fan direct driven TEAO induction motor,suitable Inspection external Ladder,Electrical cables and connections to the existing motor starters (star-delta), panel including of emergency push button, Anti Vibration Mountings, etc along with connection to the old existing system as required along with dismantling and buy-back of existing cooling tower.The new cooling must have following properties:
Water Flow rate: 1120.00 USGPM, Refrigeration Capacity : 280 TR,
Heat Rejection Capacity : 350 TR, Hot water Temp.: 97.5 deg. Farenheit,
Cold water Temp. : 90.0 deg. Farenheit, for which the condenser selection is made.,
Wet Bulb approcah: 7 degree fahrenheit, Evaporation Loss: Not more than 0.7%,
Drift Loss: Not more than 0.05%,Fan Material: Cast Alluminium alloy blades with MSHDG Hub Motor rating : 7.5 HP X 2 Nos., Motor make: ABB/Havells/BHARAT BIJLEE/New India (NIEC) /Hindustan, Motor Type: Squirrel Cage (IP55), TEAO, IE-3 , Fills :- high efficiency PVC fills with UV stabilization ,Tower Structure- Casing: FRP, Basin: FRP , Fill Support: HOT DIPPED GALVANISED FRAME/Pultruded FRP, Bird Screen: HOT DIPPED GALVANISED FRAME/Pultruded FRP, Distribution Support: HOT DIPPED GALVANISED FRAME, HARDWARE: Stainless Steel,
Ladder: MSHDG, Base frame: Galvanised,
Cooling Tower Make: BELL/ MIHIR/PAHARPUR/Advance | 2 | job | 7,33,620 ₹14,67,240 Lowest | 8,59,040 ₹17,18,080 | 7,92,664 ₹15,85,328 |
| 2.00Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect including dismantling and buyback of existing damaged pipe. Note:-The Pipes size 150mm & below shall be M.S 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia. and above. MAKE: TATA/SAIL/JINDAL | ||||||
| 2.01 | 250 mm dia | 40 | Metre | 6,804 ₹2,72,160 | 8,374.81 ₹3,34,992.4 | 4,892 ₹1,95,680 Lowest |
| 2.02 | 200 mm dia | 15 | Metre | 5,498 ₹82,470 | 6,764.11 ₹1,01,461.65 | 3,896 ₹58,440 Lowest |
| 2.03 | 150 mm dia | 10 | Metre | 3,540 ₹35,400 | 4,328.24 ₹43,282.4 | 2,177 ₹21,770 Lowest |
| 3.00 | Supplying,laying,fixing, testing and commissioning of 40 mm dia 'C' class heavy duty MS pipe confirming to IS : 1239 /IS :3589 including welding,fittings like elbow tees.flanges,tapers, nuts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enemal paints of required shade complete as required. | 20 | Metre | 1,187 ₹23,740 | 1,430.21 ₹28,604.2 | 449 ₹8,980 Lowest |
| 4.00Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified after buyback of existing damaged valve. MAKE: CASTLE/ADVANCE/AUDCO | ||||||
| 4.01 | 200 mm dia | 2 | Each | 16,915 ₹33,830 Lowest | 22,234.27 ₹44,468.54 | 22,533 ₹45,066 |
| 4.02 | 150 mm dia | 4 | Each | 11,920 ₹47,680 | 14,339.36 ₹57,357.44 | 10,149 ₹40,596 Lowest |
| 5.00 | Supplying, fixing, testing and commissioning of 40 mm dia ball valve for condenser water circulation as per specifications etc. as required. MAKE: CASTLE/ADVANCE/AUDCO/ ZOLOTO | 6 | Each | 5,339 ₹32,034 | 7,454.23 ₹44,725.38 | 3,001 ₹18,006 Lowest |
Tender Value
₹35.2 L
EMD Value
₹70,400
Closing Date
24 Nov 2025, 3:00 pmClosed
Manager Electrical
Manager Electrical, Bharat Mandapam, New Delhi
Supply Installation testing and commissioning of 350 TR cooling towers along with connecting accessories condensing pipe valve etc.for Trane Chillers units of hall No. 8-11 at Bharat Mandapam New Delhi.
2025_ITPO_885852_1
169-ITPO(8)E-E/25-26/100
Open Tender
Electrical Works
Works
90 days
Bharat Mandapam
Please refer Tender documents.
6 documents required · 6 mandatory
₹590
Yes
ITPO
₹70,400
Yes
1 Dec 2025
17 Nov 2025
25 Nov 2025
17 Nov 2025
24 Nov 2025
17 Nov 2025
Amount
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect including dismantling and buyback of existing damaged pipe. Note:-The Pipes size 150mm & below shall be M.S 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia. and above. MAKE: TATA/SAIL/JINDAL
250 mm dia
200 mm dia
150 mm dia
Supplying,laying,fixing, testing and commissioning of 40 mm dia 'C' class heavy duty MS pipe confirming to IS : 1239 /IS :3589 including welding,fittings like elbow tees.flanges,tapers, nuts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enemal paints of required shade complete as required.
Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified after buyback of existing damaged valve. MAKE: CASTLE/ADVANCE/AUDCO
200 mm dia
150 mm dia
Supplying, fixing, testing and commissioning of 40 mm dia ball valve for condenser water circulation as per specifications etc. as required. MAKE: CASTLE/ADVANCE/AUDCO/ ZOLOTO
Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.BALANCING VALVE WITH BUILT IN MEASURING FACILITY with CI body flanged construction with EPDM coated disc with long pitch with protected outpipe insulation & PN 16 pressure rating for chilled /hot water circulation as specified after buy-back of existing damaged balancing valve. MAKE: CASTLE/ADVANCE/ AUDCO
200 mm dia.
Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. BUTTERFLY VALVE (GEAR OPERATED MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified after buyback of existing damaged valve. MAKE: CASTLE/ADVANCE/ AUDCO
300 mm dia.
Supplying and laying/fixing of 3x1/2 core PVC insulated and PVC sheathed armoured XPLE, Aluminium comnductor power cable of 1.1 KV garde of following sizes on surface /Tray etc as required. Make: Polycab, Plaza, Havells, KEI.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 25 sq. mm. (28mm)
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Supplying and installation following size of perforated painted with powder coating M.S Cable tray with perforation not more than 17.5%, in convenient sections,joined with connectors, suspeneded from the ceiling with M.S suspenders including bolts & nuts, painting suspenders etc as reqd.
100 mm Width x 50 mm depth x 1.6 mm thickness
200 mm Width x 50 mm depth x 1.6 mm thickness
Construction of suitable hight of RCC vertical (0.25x0.25 )mtr. Size column having 100 mm x100 mm size, 100 mm deep pocket on top to provide 100 mm long bolt for installation of cooling towers on ground complete with shuttering , reinforcement ,plastering etc. as required as per the direction of engineer in charge.
JUHI AND JAI CONTRACTORS PVT LTD (BID ID -3321905)
Hemcool Engineers (BID ID -3321318)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
Tenderdocument.pdf
Tender Documents • 1.21 MB
BOQ_931128.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .