Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.1 CrAccepted-AOC | ₹5.1 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹5.2 CrRejected-Finance | ₹5.2 Cr | L2 | Rejected-Finance L2 |
| 3 | L3₹5.3 CrRejected-Finance 553 GOLF COURSE ROAD SECTOR 43 GURUGRAM 122009 | ₹5.3 Cr | L3 | Rejected-Finance L3 |
| 4 | L4₹5.4 CrRejected-Finance | ₹5.4 Cr | L4 | Rejected-Finance L4 |
| 5 | Rejected-Technical KASANA TOWER V FLOOR ALPHA 1 GR NOIDA COMMERCIAL BELT GAUTAM BUDDHA NAGAR UTTAR PRADESH 201307 | NOIDA | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201307 | - | - | Rejected-Technical DISQUALIFIED |
Tender Value
₹5.7 Cr
EMD Value
₹11.5 L
Closing Date
26 Dec 2025, 5:00 pmClosed
OSD M
YAMUNA EXPRESSWAY INDUSTRIAL DEVELOPMENT AUTHORITY
Construction of 33/11kv Sub-station ESS No-01 In Sector-29 yea
2025_YEIDA_1098419_6
YEA/OSD(M)/2025/349 DT-05/12/2025
Open Tender
Electrical Works
365 days
YAMUNA EXPRESSWAY INDUSTRIAL DEVELOPMENT AUTHORITY
REFER TENDER DOC
5 documents required · 5 mandatory
₹6,770
₹11.5 L
18 Mar 2026
11 Dec 2025
29 Dec 2025
11 Dec 2025
26 Dec 2025
11 Dec 2025
Supply, Installation, Testing & Commissioning of 33 KV HT Panels Indoor type 6 panel board Vacuum circuit breaker (With 1 No. Incomer 1250 Amps, 2 No. Outgoing 1250 Amp, 2 No. Tie Feeder 1250 Amp & 1 No. Bus Coupler 1250 Amp), 3 phase, 31.5 KA for 1 sec. , HT switch gear with all necessary protection, metering and other accessories as required. as per the directions of the Engineer-in-charge. YEIDA SOR-73
Supply , Installation, Testing & Commissioning of 33kV HT Panels Indoor type 2 panel board Bus PT, 3 phase, 31.5 KA for 1 sec with all necessary protection, metering and other accessories as required as per the directions of the Engineer-in-charge. YEIDA SOR-71
Supply, Installation, testing & commissioning of outdoor type 10 MVA Power Transformer with on load tap changer as per ISI specification including loading, unloading, local carriage & erection of the same on plinth & making all necessary connection etc. Complete in all respects as per specification (Make ABB/ Crompton/ Schneider). Cable termination box with disconnecting facility for 33 KV XLPE cable at 33 KV side. Cable termination box with disconnecting facility for 11 KV XLPE cable at 11 KV side. On load tap changer+/- [email protected]%, Bi directional roller, Conservator with drain valve, Earthing ferminals, Double diaphragm explosion vent, Radiator with top & bottom shut off valve, First filling of oil including makeup fill, Silica gel breather with oil seal, Rating and diagram plate, Air Release plug, Buchholz relay with shut off valve, Winding temperature indicator (WTI), Oil temperature indicator (OTI), Megenatic oil level guage, Pressure relief device, Marshalling box. No load losses-7Kw, load losses 50KW, Toleronce as per I.S. code as per the directions of the Engineer-in-charge. YEIDA SOR-75
Supply Installation Testing & Commissioning of 11kV HT Panels Indoor type 12 panel board Vacuum circuit breaker (2 No. Incomer 1250 Amps, 1 No. bus coupler 1250 Amps and 9 Nos.630Amp Outgoing) 11 KV, 3 phase, 25 KA for 1 sec. HT switch gear VCB breaker with all necessary protection, metering and other accessories as required. as per the directions of the Engineer-in-charge. YEIDA SOR-72
Supply, Installation, Testing & Commissioning of 11kV HT Panels Indoor type 2 panel board Bus PT, 3 phase, 25 KA for 1 sec with all necessary protection, metering and other accessories as required. Complete in all respect.as per the directions of the Engineer-in-charge. YEIDA SOR-70
Supplying, Assembling, Installation, Commissioning of Sealed maintenance free (SMF) 110V D.C., 150 AH batteries. The batteries shall rest on treated wooden planks fabricated from MS angle and free standing floor mounted rack with acid resistant finish and complete with series connecting electrical leads and charging of batteries. The batteries shall be accompanied with tester. This shall have incoming leads as well as outgoing leads and of suitable battery charger for 8 hrs. charge of 150AH battery charger enclosed in sheet metal with fan on top and it should automatically charge the batteries With booster and trickle charge. Charger shall be complete with incoming & outgoing leads and D.C. Distribution board will have one set of 63 amps MCB as incomer and ten number of suitable rated MCB (as per coil rating of VCB) on outgoing side enclosed in metal sheet enclosure of 2mm thick and suitably painted. The unit will be complete with bus bars, accessories, links, terminal strip, clamps etc. along with cables up to incoming & outgoing to VCB panels. Complete in all respect.as per the directions of the Engineer-in-charge. Complete in all respect.as per the directions of the Engineer-in-charge. YEIDA SOR-69
Supply, delivery, laying, testing & commissioning of 33KV (E) XLPE cable having compact circular stranded aluminium conductor The conductor should have screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semin conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 33 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and at the top surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I with Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job as per direction of Engineer-in-charge. Make- CCI, Gloster, Asian, Universal, Nicco, ICL, Diamond, Havells & KEI YEIDA SOR-3 3C X 400 sq. mm. from 33kV HT Panel to 33/11kV Power transformer.
Supply, delivery, laying, testing & commissioning of 11KV (E) XLPE cable having compact circular stranded aluminium conductor the conductor should have screening of extruded semi conducting compound, cross linked polythylene (XLPE), insulation screening of the extruded semi conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 11 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand all-round and protected with bricks on sides and at the top surface. The cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the E/I. with Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respect and as per requirement of the job under the direction of Engineer-in-charge. Make- CCI, Gloster, Asian, Universal, Nicco, ICL, Diamond, Havells & KEI YEIDA SOR-2 3C X 300 sq. mm. (From 33/11 Power Transformer to 11 KV HT Panles).
Supply, Delivery, Installation, Testing & Commissioning of 33KV, Indoor type cable termination kit complete in all respects aAs per direction of Engineer-in-charge. (Make Raychem, CCI, Frontec) YEIDA SOR-9 3C X 400 sqmm.
Supply, Installation, Testing & Commissioning of 11KV, indoor type cable termination kit of 3 core cable with cable termination at the panel & transformer complete in all respect as required for proper completion of work as per direction of Engineer-in-charge.(Make- Raychem/C.C.I./Frontec) YEIDA SOR-4 3C X 300 sqmm.
Supply, Delivery, Installation, Testing & Commissioning of 33KV, Outdoor type cable termination kit complete in all respects as required for proper completion of work. (make Raychem, CCI, Frontec) YEIDA SOR-9 3C X 400 sqmm.(33kV HT Panel to 33/11kV Power transformer.)
Supply, Installation, Testing & Commissioning of 11 KV Out door type cable termination kit of 3 core cable with cable termination at the panel & transformer complete in all respect as required for proper completion of work as per direction of Engineer-in-charge.(Make Raychem/C.C.I./Frontec) YEIDA SOR-5 3C X 300 sqmm.
Supply, Installation, testing and commissioning of Control cables of following sizes to be laid buried in ground or laid on cable trays for transformers and VCB. 1.1kV Grade Stranded Copper Conductor PVC Insulated Wrapped PVC inner & Outer sheathed cable. complete in all respect.as per the directions of the Engineer-in-charge. YEIDA SOR-1 4CX2.5 sqmm
Supply, Installation, testing and commissioning of Control cables of following sizes to be laid buried in ground or laid on cable trays for transformers and VCB. 1.1kV Grade Stranded Copper Conductor PVC Insulated Wrapped PVC inner & Outer sheathed cable. complete in all respect.as per the directions of the Engineer-in-charge. YEIDA SOR-1 19CX1.5sqmm
Supply and fixing of TPN MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc of DB's (For Lighting & Small Power ). Note- Each incoming and outgoing MCB's shall have Ics = 10 kA minimum (Analysis of Rate from PS) S & F surface/ Flush mounting 12ways TPN distribution board with additional metal door without MCB complete in all respect,as directed at site by Engineer in charge. PWD-2018/PS No-1029( A ). Incoming:- S&F of 1 No. , 100 Amp. T.P. Isolator, V 1007(B ) , S&F and making connection of 3Nos. , 40A 2 pole 30mA ELCB/RCCB of Din Rail Mounting complete in all respect as per direction and satisfaction to the Engineer in charge, PWD-2018/PS No-393, Outgoing :- S&F of 36 Nos, 6 Amp to 32 Amp. MCB (10 KA) C Curve, PWD-2018/PS No-1002
Supply and fixing of power plug with 15A/250 volt flush type switch and 5 pin 15A/250V flush type universal socket in suitable M.S. box of 175mm x 100mm x 50mm size with phenolic laminated bakelite sheet cover 3mm thick fixed with brass machine screw and cup washer. & Add for plug point with modular switch & socket in place of piano type switch & socket. (UPS socket for computer). PWD-2018/PS No-1139 & 187C
Supply and fixing of 63 Amp. 415 V metal clad T.P. rewireable type switch fuse unit on angle iron bracket complete in all respect. PWD-2018/PS No-313
Supply and fixing of LED Tube Light with batten suitable for upto 1X22 Watt LED Tube Light fitting including tube on surface complete in all respect. PWD-2018/PS No-1413
Supply and fixing of LED Street Light Fitting Having die cast aluminium body and diffuser with driver set suitable for 140 to 150 Watt. Confirming to IP 66 Protection complete in all respect. PWD-2018/PS No-1425
Supply and fixing of 40mm. dia 1.5mtr. Long G.I. pipe ‘B’ Class bracket with 2 Nos. ‘D’ clamps 50X6mm. flat iron on steel tubular pole / PCC pole with bolts, nuts etc. complete in all respect, as directed by Engineer in charge. YEIDA SOR-35
Supply, Installation, testing and commissioning of 1200mm dia sweep ceiling fan with standard down rod. Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-62
Supply, Installation, testing and commissioning of 300mm dia heavy duty 900 RPM exhaust fan complete with louvered shutters. Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-63
Wiring point for light with 1.5 sq. mm. FRLSH PVC insulated multistrand single core copper conductor cable in in PVC conduit with 1.5 sq. mm.FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside. each partly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete with GP Box, Modular type switch & ceiling rose/angle/batten holder on 3mm thick phenolic paminated backalite sheet etc complete in all respect as directed including matching colour wash. PWD-2018/PS No-138( C) +187(A)
Wiring point for fan / fresh air fan (light duty exhaust fan) with 1.5 sq.mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit with 1.5 sq. mm.FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit. partly concealed in wall and partly laid in slab alongwith the reinforcement before concreting, complete GP Box ,Modular type switch & ceiling rose on 3 mm. thick backelite sheet etc., complete in all respect including matching colour wash. PWD-2018/PS No-140( C) +187(A)
Supply and fixing of power plug with 15A/250 volt Modular type switch and 5 pin 15A/250V flush type universal socket in suitable M.S. box of 175mm x 100mm x 50mm size with phenolic laminated bakelite sheet cover 3mm thick fixed with brass machine screw and cup washer PWD-2018/PS No-1139+187(C)
Supply and wiring of submains with 2 nos. 2.5 sq mm & with 1 no earth wire of 1.5 sq mm FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in existing PVC conduit complete, including supply of all material, labour and T & P etc. & Supply and laying of 20 mm dia heavey duty (2mm Thick) PVC conduit of 25mm dia.complete with bends and other acessories as required in slab alongwith reinforcement, before concreting and plastering etc, required for proper completion of the work as directed by Engineer in charge.(For computer terminals from UPS DBs), PWD-2018/PS No-291&282(A )
Supply and wiring of submain with two number 4 sq.mm. FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in20 mm dia heavy duty (2 mm thick) PVC conduit with one no. 2.5 sq. mm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire drawn in conduit. Submain in conduit (partly laid in slab and partly concealed in wall ( 2 Wire 1100 V Grade) PWD-2018/PS No-221(C )
Supply and wiring of submain with two number 6 sq. mm. FRLSH PVC insulated 1100 V grade multistrand single core aluminium conductor cable but in 25 mm dia heavy duty (2 mm thick) PVC conduit with one number 4 sq. mm. FRLSH PVC insulated multistrand copper conductor cable as earth continuity wire drawn in conduit etc. complete in all respect. (For 20A AC sockets), PWD-2018/PS No-222(C )
Supply and wiring of 4 number 16 sq. mm. PVC insulated 1100 V grade single core Copper conductor cable in 40 mm dia PVC conduit partly concealed in wall and partly laid in slab alongwith reinforcement before concreting, with two number 10 sq mm single core Copper conductor cable as earth continuity wiredrawn in coudit including matching colour wash etc, complete in all respect (For 63A sockets).PWD-2018/PS No-279(C )
Supply & Burying of 600mm X 600mm X 6.00mm G.I. plate verticalley for Earthing with its top at least 3.00 mtr below ground level complete with 20mm Dia. G.I. pipe & Funnel for watering and one earthing lead of one no. 8 to 10 SWG G.I. wire in 15mm dia. GI pipe upto Switch Board (From approan to switch board the cost of GI pipe & GI wire will be ex
tra) 30cm square C.I. frame with hinged cover masonory housing alternate layers of charcole/ coke and salt at least 150mm thick alround etc. as per direction of Engineer-in-charge complete in all respects. as per drawing (this will apply for earthing of poles also). PWD-2018/PS No-702
Supply & Burying of 600mm X 600mm X 3.00mm Cu. plate verticalley for Earthing with its top at least 3.00 mtr below ground level complete with 20mm Dia. G.I. pipe & Funnel for watering and one earthing lead of one no. 8 to 10 SWG Cu. wire in 15mm dia. GI pipe upto Switch Board (From approan to switch board the cost of GI pipe & Copper. wire will be extra) 30cm square C.I. frame with hinged cover masonory housing alternate layers of charcole/ coke and salt at least 150mm thick alround etc. as per direction of Engineer-in-charge complete in all respects. PWD-2018/PS No-704
Supply & Burying of 40mm dia. X 4.5 mtr long G.I. pipe verticalley for Earthing haveing 12mm dia. Holes spaced 75mm apart drilled upto 2mtr from the bottom complete with earthing lead of No.6 to 8 SWG G.I. wire in G.I. pipe upto appron (and from appron to switch board the cost of G.I. wire & pipe will be Extra) upto Switch Board, 30cm squre C.I. Box hinged cover masonory inclosure , funnel at top, alternet layers of charcole/ coke and salt at least 150mm thick alround etc. as per direction of Engineer-in-charge complete in all respects. as per drawing. PWD-2018/PS No-701
Supply & Laying of 32 x 6 mm GI strip, complete in all respects as per approved by Engineer-in-charge, PWD-2018/PS No-717
Supply & Laying of 32 x 6 mm Copper strip,complete in all respects as per approved by Engineer-in-charge, PWD-2018/PS No-718
Supply and fixing of 25 x 3 mm GI strip with G.I clamps on surface complete in all respects as per approved by Engineer-in-charge.PWD-2018/PS No-710
Supply and fixing of 25 x 3 mm Copper Strip with G.I. Clamps on surface complete in all respects as per approved by Engineer-in-charge.PWD-2018/PS No-711
Supply and Installation of Perforated type trays– Prefabricated 2.5mm G.I.(Hot Dip Galvanised), 75mm flange height with all accessories such as coupling plates, bends, tees, reducers, coupling nut-bolts etc. of following width. The cost of installation shall include connection, bolting, cutting, etc. The supporting steel for cable trays shall be painted type and Cable trays, accessories and covers shall be painted with one shop coat of red oxide zinc chromate primer and two site coats of aluminium alkyd paint. Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-66 300 mm width.
Supply and Installation of Perforated type trays– Prefabricated 2.5mm G.I.(Hot Dip Galvanised), 75mm flange height with all accessories such as coupling plates, bends, tees, reducers, coupling nut-bolts etc. of following width. The cost of installation shall include connection, bolting, cutting, etc. The supporting steel for cable trays shall be painted type and Cable trays, accessories and covers shall be painted with one shop coat of red oxide zinc chromate primer and two site coats of aluminium alkyd paint. Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-66 150 mm width.
Supply and Installation of Perforated type trays– Prefabricated 2.5mm G.I.(Hot Dip Galvanised), 75mm flange height with all accessories such as coupling plates, bends, tees, reducers, coupling nut-bolts etc. of following width. The cost of installation shall include connection, bolting, cutting, etc. The supporting steel for cable trays shall be painted type and Cable trays, accessories and covers shall be painted with one shop coat of red oxide zinc chromate primer and two site coats of aluminium alkyd paint. Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-66 100 mm width.
Supplying, fixing, testing & commissioning heavy duty PVC pipe with all necessary conduit accessories etc., 110mm dia conduit, PWD-2020, Civil-33(iii), Page No. 6
Supply & Laying of 120mm dia. DWC pipe for drawing of power cable across the road by drilling of 150mm dia. at 1mtr. Below the road level the work should be done by manual Trenchless method. Complete in all respect per direction of Engineer-in-charge YEIDA SOR-13
Supply & Laying of 200mm dia. H.D.P.E pipe for drawing of power cable across the road by drilling of 220mm dia. at 1mtr. Below the road level thereby doing the work of providing H.D.P.E pipe by Trenchless method PE-63/PN-6.Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-54.
Supply and fixing of testing joint of G.I. strip 32mm x 6mm and 150mm long with G.I. bolts and nut etc. complete in all respect PWD-2018/PS No-719
Supply and burying of 40mm dia x 4.5 metres long G.I. Pipe vertically for earthing having 12mm dia. Holes spaced 75mm apart drilled up to 2 metre from the bottom complete with earthing lead of No. 6 to 8SWG GI wire in G.I. Pipe up to appron (and from appron to switch board the cost of G.I. wire and pipe will be extra) upto switch board, 30cm square C.I. box with hinged cover masonary enclosure, funnel at top, alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing. PWD-2018/PS No-701
Supply & Fixing of Danger Board Fabricated from 10 gauge M.S. Sheet. (11 kV Danger Caution Boards as per IS 2551 & IS 8923, PWD-2018/PS No-1109
Supply and fixing of shock treatment chart (prescribed under I.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T&P for proper completion of work. PWD-2018/PS No-1134
Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete
with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. PWD-2018/PS No-1131
Supply and fixing of fire bucket 6Nos round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. PWD-2018/PS No-1133
S/F of cross arm made of 100X50X6 mm M.S. channel 2.5 mtr. long on poles with packing, piece, M.S. clamp, Nut bolts etc. complete in all respect, as directed by Engineer in charge YEIDA SOR-30
Supply and fixing of 33kv HV insulating mats confirming to IS 15652-2006. The mats should have been type tested by CPRI or another third party lab of equivalent stature. The mats shall be moisture proof, fire retardant and resistant to acids, alkalies & transformer oil. Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-58
S/E of Section Double pole structure on ST pole 410 SP-62 with 1/6 over length of poles grouted with cement concrete in 1:3:6 (one cement : 3 coarse sand :6 Stone ballast) including plingthing of pole 30 cm above grade level, plastering of plinth including excavation & back filling etc. The double pole structure consist of 100X50X6mm 2.50 mtr. & 75X40X6mm 2.50 mtr. M.S. channel and bracings with M.S. clamp packing piece Nuts Bolts etc. The rates includes all materials labour T&P etc. required for proper completion f work as per direction of E/I. YEIDA SOR-25
Painting of the electric pole with two coat of Al-paint over red oxide primer complete in all respect. PWD-2018/PS No-634
Supply & fixing of MS rod for earthing with 2.5 m long, solid, 20 mm dia hot dipped galvanised MS rod buried till the top reaches 1.7 mts. Below the GL complete with bolts & nuts & GI earth wire 7/14. Complete in all respects as per direction of the Engineer-in-charge. YEIDA SOR-52
Supply and fixing of G.I Pipe 150MM dia "B"class Zindal/tata make including required material T&P etc. Complete in all respect, as directed by Engineer in charge. as per the directions of the Engineer-in-charge. YEIDA SOR-65
Supply, Installation, testing and commissioning of Outdoor type distribution transformer. Specification and also confirming to IS: 1180. Level-2 as per the directions of the Engineer-in-charge Analysis of Rates (a) 63 KVA Aluminium wound YEIDA SOR-34
Supply, delivery, laying testing & commissioning of 11KV (E), XLPE cable having compacted circular staranded aluminium conductor, conductor screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semi conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 11 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and top on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I. Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job. (CCI, Gloster, Asian, Universal, Nicco , ICL,Havels,Dimond,KEI make) P.S. 506 (a) 3CX70 Sqmm.
Supply, Installation, Testing & Commissioning of 11 KV Out door type cable termination kit of 3 core cable with cable termination at the panel & transformer complete in all respect as required for proper completion of work as per direction of Engineer-in-charge. (Make Raychem/C.C.I. /Frontec) YEIDA SOR-5 3CX50 Sq.mm.
Supply and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer- Incharge. PWD-2018/PS No-504
Earth work in excavation in ordinary soil in all type of foundation trenches including dressing of the side and ramming of bottom. Lifts upto 1.5m including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50m. All kinds of soil. (MORTH/A.R./YEIDA/Based on UPPWD/SOR-2020) Depth from 0.0 to 1.5 M below G.L.
Earth work in rough excavation banking excavated earth in layers not exceeding 20 cm in depth, breaking clods watering, rolling each layer with 1/2 formes roller or wooden or steel rummer and rolling every 3rd and top most layer with power roller of minnimum 8 tonnes and dressing up in embank mind for roads, flood banks, marginal banks. and guide banks or filling up ground depressions, all leads as per (MOST/ A.R./ YEIDA) for all kind of soil.(A.R./YEIDA/Based on UPPWD/SOR-2020) All leads
Cement concrete with 4cm gauge approved stone ballast, coarse sand & cement in the proportion of 8:4:1 including supply of all materials, labour, tools & plants etc. required for proper completion of the work. (UPPWD/SOR-2020/281)
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. “(Note:- Cement content considered in this item is @ 330 kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately). All works upto plinth level. (DAR/5.33.1/Based on UPPWD/SOR-2020)
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and
durability as per direction of Engineer-in-charge. “(Note:- Cement content considered in this item is @ 330 kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately). All works above plinth level upto floor V level. (DAR/5.33.2/Based on UPPWD/SOR-2020)
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.Thermo-Mechanically Treated bars of grade Fe-500D or more./Cold twisted bars. (DAR/5.22.6/Based on UPPWD/SOR-2020)
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500 D or more. (DAR/5.22A.6/Based on UPPWD/SOR-2020)
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. (DAR/10.25.2/Based on UPPWD/SOR-2020)
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Foundations, footings, bases of columns, etc. for mass concrete. (DAR/5.9.1/Based on UPPWD/SOR-2020)
Suspended floors, roofs, landings, balconies and access platform (DAR/5.9.3/Based on UPPWD/SOR-2020)
durability as per direction of Engineer-in-charge. “(Note:- Cement content considered in this item is @ 330 kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately). All works above plinth level upto floor V level. (DAR/5.33.2/Based on UPPWD/SOR-2020)
Lintels, beams, plinth beams, girders, bressumers and cantilevers. (DAR/5.9.5/Based on UPPWD/SOR-2020))
Columns, Pillars, Piers, Abutments, Posts and Struts. (DAR/5.9.6/Based on UPPWD/SOR-2020))
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured). Suspended floors, roofs, landing, beams and balconies (Plan area to be measured). (DAR/5.11.1/Based on UPPWD/SOR-2020)
M-150 brick work in 1:4 one cement and four coarse sand 2.20 F.M. mortar in foundation and plinth including supply of all material, labour, T&P etc. required for proper completion of the work. (UPPWD/SOR-2020/305(a)
M-150 brick work in 1:4 one cement and four coarse sand 2.20 F.M. mortar including supply of all material, labour, T&P etc. required for proper completion of the work. But in superstructure including necessary Cutting & moulding of brick as required thickness of walls not to be less than 1½ brick. Add extra labour to above items. (UPPWD/SOR-2020/309)
Half brick masonry with bricks of class designation 150 in superstructure above plinth level upto floor V level. Cement mortar 1:4 (1 cement : 4 coarse sand). (DAR/6.13.2/Based on UPPWD/SOR-2020)
12mm cement plaster of mix: 1:6 (1 cement : 6 coarse sand) (DAR/13.4.2/Based on UPPWD/SOR-2020)
6mm cement plaster of mix: 1:3 (1 cement : 3 fine sand) (DAR/13.16.1/Based on UPPWD/SOR-2020)
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand). (DAR/13.11/Based on UPPWD/SOR-2020)
White washing Three coats including supply of all material, labour, tools & plants etc. required for proper completion of the work. (UPPWD/SOR-2020/673)
Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade : Two or more coats on new work. (DAR/13.60.1/Based on UPPWD/SOR-2020)
Finishing wall with water proof cement paint of approved make and quality on new wood with two coat to give an even shade including supply of all materials, labour, Tools & plant etc. required for proper completion of the work. (UPPWD/SOR-2020/660)
Painting with acid proof paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work. (DAR/13.64.1/Based on UPPWD/SOR-2020)
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. (DAR/8.31/Based on UPPWD/SOR-2020)
Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18mm thick. (DAR/11.6.1/Based on UPPWD/SOR-2020)
Painting with acid proof paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work. (DAR/13.64.1/Based on UPPWD/SOR-2020)
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600mm (DAR/11.41.2/Based on UPPWD/SOR-2020)
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work. (DAR/8.3.2/Based on UPPWD/SOR-2020)
Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18mm thick. (DAR/11.6.1/Based on UPPWD/SOR-2020)
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. (DAR/11.27/Based on UPPWD/SOR-2020)
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including pointing the joints with white cement and matching pigment etc., complete. (DAR/11.37/Based on UPPWD/SOR-2020)
Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand). Acid and alkali resistant tile (DAR/11.21.1.1/Based on UPPWD/SOR-2020)
Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade : Two or more coats on new work. (DAR/13.60.1/Based on UPPWD/SOR-2020)
Distempering (first coat) with oil bound distemper of approved brand and manufacture and of required shade on undecorated wall surface to give an even shade over and including a priming coat with cement primer of approved brand and manufacture such as Berger, J&N, Shalimar, Asian Paint after thoroughly brushing the surface free from mortar dropping and other foreign matters and also including the surface even with plaster of Paris or approved synthetic materials and sand papered smooth including supply of all materials, labour, Tools & plants etc. required for proper completion of the work. (but for every coat after the first coat).(UPPWD/SOR-2020/649+650)
Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm). (DAR/13.46.1/Based on UPPWD/SOR-2020)
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 m
m nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. (DAR/4.17/Based on UPPWD/SOR-2020)
Providing and fixing Heat Resistant terrace Tiles (300mmX300mmX20mm) having an initial solar reflectance of no less than 0.70 and an initial emittance no less than 0.75. Solar reflectance shall be determined in accordance with ASTM E903 -96 and emittance shall be determined in accordance with ASTM E408-71 (RA1996), on water proof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 Coarse sand) and grouting the joints with mix of white cement and marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150mm height along the parapet walls in the same manner all complete as per direction fo engineer-in-charge. (UPPWD/SOR-2020/New Items-3/P-29)
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design : In 75x75mm deep chase (DAR/12.21.1/Based on UPPWD/ SOR-2020)
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws. (DAR/9.20.1/Based on UPPWD/SOR-2020)
Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:Profile C - Fixing with adjustable lugs with split end tail to each jamb (DAR/10.14.2.1/Based on UPPWD/SOR-2020)
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25mm M.S. laths with 1.25mm thick top cover. (DAR/10.6.1/Based on UPPWD/SOR-2020)
Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per specifications, drawings and direction of Engineer-in-charge complete. (DAR-19/21.10 /Based on UPPWD/SOR-2020)
Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests. (DAR/17.1.1/Based on UPPWD/SOR-2020)
Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid. (DAR/17.3.1/Based on UPPWD/SOR-2020)
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White vitreous China wash basin size 630x450 mm with a pair of 15mm C.P. brass pillar taps. (DAR/17.7.1/Based on UPPWD/SOR-2020)
Providing and fixing toilet paper holder: C.P. brass (DAR/17.34.1/Based on UPPWD/SOR-2020)
Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : One urinal basin with 5 litre white P.V.C. automatic flushing cistern. (DAR/17.4.1/Based on UPPWD/SOR-2020)
Supplying & Installation / fixing (Complete). Of 15 mm CP health faucet of approved with necessary CP flexible hose 1000mm long nozzle, CP wall flange, C.P Holder CP angle cock etc., complete (CP Health Faucet ) (Mkt)
Providing and fixing C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms. 15mm nominal bore (DAR/18.50.1/Based on UPPWD/SOR-2020)
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 8931 : 15mm nominal bore (DAR/18.53.1/Based on UPPWD/SOR-2020)
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. (DAR/18.48/Based on UPPWD/SOR-2020)
Providing and fixing soil, waste and vent pipes: 100mm dia: Centrifugally cast (spun) iron socket & spigot (S&S) pipe as per IS: 3989. (DAR/17.35.1.2/Based on UPPWD/SOR-2020)
Providing and fixing soil, waste and vent pipes: 75mm diameter: Centrifugally cast (spun) iron socketed pipe as per IS: 3989. (DAR/17.35.2.2Based on UPPWD/SOR-2020)
Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes and fittings of diameter : 100mm (DAR/17.58.1/Based on UPPWD/SOR-2020)
Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes and fittings of diameter : 75mm (DAR/17.58.2/Based on UPPWD/SOR-2020)
Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. 100x100x100 mm: Sand cast iron S&S as per IS - 3989 (DAR/17.43.1.2/Based on UPPWD/SOR-2020)
Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. 75x75x75 mm: Sand cast iron S&S as per IS - 3989 (DAR/17.43.2.2/Based on UPPWD/SOR-2020)
Providing and fixing terminal guard: 100 mm: Sand cast iron S&S as per IS - 1729 code-17.56.22
Providing and fixing terminal guard: 75 mm: Sand cast iron S&S as per IS - 3989 code 17.8.1
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : 100 mm inlet and 75 mm outlet: Sand cast iron S&S as per IS: 3989 (DAR/17.60.2.1/Based on UPPWD/SOR-2020)
Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 m
m nominal size), including cost of cutting holes and making good the walls etc. : For 100mm dia pipe (DAR/17.37.1/Based on UPPWD/SOR-2020)
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) : With brick of class designation-150 (DAR/19.7.1.1/Based on UPPWD/SOR-2020)
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 15 mm nominal outer dia pipes (DAR/18.8.1/Based on UPPWD/SOR-2020)
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge.Concealed work, including cutting chases and making good the walls etc. 20 mm nominal outer dia pipes (DAR/18.8.2/Based on UPPWD/SOR-2020)
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge.Concealed work, including cutting chases and making good the walls etc. 25 mm nominal outer dia pipes (DAR/18.8.3/Based on UPPWD/SOR-2020)
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 250 mm dia R.C.C. pipe (DAR/19.6.3/Based on UPPWD/SOR-2020)
Providing and laying cement concrete 1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) all -round S.W. pipes including bed concrete as per standard design: 150 mm diameter S.W Pipe DSR 2018 (Item 19.2.2) P-349
Providing and fixing brass bib cock of approved quality: 15 mm nominal bore (DAR/18.15.1/Based on UPPWD/SOR-2020)
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. (DAR/17.31/Based on UPPWD/SOR-2020)
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade.Area of slab over 0.50 Sqm. (DAR/8.2.2.2/Based on UPPWD/SOR-2020)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.42 MB
6.pdf
Tender Documents • 1.50 MB
BOQ_2023200.xls
BOQ • 0.45 MB
Download all tender documents and submit your bid