Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.2 LAccepted-AOC SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | ₹47.2 L | L1 | Accepted-AOC The lowest e-tenderer |
| 2 | L2₹54.2 L+₹7.0 L (14.8%)Rejected-Finance 1 NEAR AKBARIYA MASJID WIMBERLYGUNJ SOUTH ANDAMAN ANDAMAN NICOBAR 744206 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744206 | ₹54.2 L+₹7.0 L (14.8%) | L2 | Rejected-Finance Not Meeting eligibility criteria |
| 3 | L3₹58.2 L+₹10.9 L (23.1%)Rejected-Finance | ₹58.2 L+₹10.9 L (23.1%) | L3 | Rejected-Finance Not Meeting eligibility criteria |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not Meeting eligibility criteria |
Tender Value
₹44 L
EMD Value
₹88,000
Closing Date
31 Oct 2024, 6:00 pmClosed
Shri Vinay Kumar, IDSE, SE (SAG)
Headquarters Commander Works Engineer (Army) 24 Assaye Building, Colaba Mumbai-400 005
PROVN OF POWER BACKUP 02 X DG SET 100KVA ALONGWITH SHED FOR POWER BACKUP TO CLASS ROOMS WITH VIDEO PROJECTION UNITS ELECTRONIC TRAINING AIDS TECHNICAL EQUIPMENT FOR TRG REQUIRING AIR CONDITIONING COMPUTER INSTALL AND SERVER ROOMS OF 6TTR PONDA GOA
2024_MES_662773_2
85122/P/E8
Open Tender
Civil Works
Item Rate
120 days
Garrison Engineer Panaji Goa
Please ref tender documents
7 documents required · 7 mandatory
₹500
Yes
GE Panaji Goa
₹88,000
30 Dec 2024
10 Oct 2024
1 Nov 2024
10 Oct 2024
31 Oct 2024
19 Oct 2024
10 Oct 2024 - 24 Oct 2024
Amount
B/R PORTION S & F for prepaid galvalue aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strenth of 550Mpa in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed.
S & F for prepaid galvalue aluminium zinc coating GI based plain steel sheet 0.50mm thick of any colour having tensile strenth of 550Mpa in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed.
S & F rolled mild steel in roof trusses (faaned) trussed, purlins, crane gantries rails and fastening and heavy bracket framing (Beam, tee, angle, channel or flat section) including distance pieces, cleats etc. confirming to quality 'A' Fe-290 (Gde E-165) Complete all as specified and directed.
S & F Compound girders and stanchions, lattice girders, aerial masts, staging for water tank and the like including caps, bases splices etc. built up form up from two or more beam or channel section or angles with plates, including all lattice bars, stiffeners, gusset plates etc. confiming to quality 'A' Fe-290 (Gde E-165) complete all as specified and directed.
S & F rolled sections as in main and cross beam hips and jack, rafters, purlines where connected to common rafters and running rail and guide for sliding doors fixed with angle cleats Fe- 290-W (gde-E-165)
Material & Labour for applying two coats of synthetic enamel paint over a coat of red oxide primer including preparation of new steel surfaces of any descriptions, over 10cm in width or girth complete all as specified and directed.
Excavation in post holes for similar holes each n exe 0.5 cum in soft/loose soil returning filling in and ramming earth.
Supply, lay and connect cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 cor.
Ditto as per item No. 9, but of size 70 sq mm 3.5 core
Ditto as per item No. 9, but of size 50 sq mm 3.5 core
Material & Labour for brick protection using old size sub classs 'B' New bricks laid flat dry but jointed laid length wise perpendicular to the axis of cable all as specified and directed by the Engineer-in-Charge
Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for laying of cables and getting out complete all as specified and directed by Engineer-in-Charge.
Material and labour for sand cushioning with a layer of sand 8cm thick before layingof cable and 15cm thick after lying of cable in trenches complete all specified.
Returning, filling in, including spreading, leveling watering and well ramming inlayers not exceeding 25 cms thick each layer compete all as specified and directed by Engineer-in-Charge.
Removal of surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-charge.
Supply and fixing galvanised pipe light grade of ISI marked 80 mm bore for passing of cable fixed to poles/walls/lay under floor complete with and including fittings as required compete all as specified and directed by Engr-in-charge.
Earthing complete for Transformers/ LT Panels with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25 metres below normal ground level with top edge of the plate at a depth not less than 1.5 metres below normal ground level, connected with and including GI strip 32mm x 6mm in and including GI pipe 50mm bore medium grade as protection pipe (from top of earth plate up to the test point) and connecting strip to earth plate by means of GI bolts, nuts, check nuts and washers and thimbles at two places (minimum), earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick, all around including top and bottom and watering pipe 20mm bore of GI pipe light grade with funnel and wire mesh, PCC chamber of size 300x300x300mm(top of chamber minimum 15 cm above the normal ground level (1:3:6) using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate of 25mm thick with 2 nos MS handles of 12mm dia including necessary excavation/ earth work in any type of soil/rock and as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified.
Supply, install, testing and commissioning of CPRA approved Feeder pillar, outdoor cubicle type weather and vermin proof totally enclosed made out of 3 mm thick CRCA sheet machine pressed of suitable size, suitable to operate on 3 phase 4 wire system , 415volts, 50 Hz double door with front and rear openable with locking arrangement incl frame of panel with angle iron of size 50 x 50 x 6mm, inner shutters for mounting switchgears etc, independent bottom gland plate for each incoming & outgoing cable of suitable size as per switchgear rating, having apron on 3 sides of panel from base to ground level prewired complete duly powder coated with 7 tank process comprising with following complete all as specified:- (i) Bus bar strip,four pole and capacity 450 Amps copper strip of suitable size based on 1.5 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red,Yellow, blue and black) fixed on porcelain insulators with necessary nuts and bolts and washers etc (ii) INCOMING : - (a) MCCB 200 Amp, 415 V, 36 KA, 4 pole with fixed thermal magnetic release -01 Nos. (b) Panel meters with LCD display -1 No (c) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -01 set (d) Change Over Switch 4P 200A -01 No (iii) OUTGOING:- (a) MCCB 100 Amp, 415 V, 25 KA, 4 pole with fixed thermal magnetic release -02 Nos. (b) MCCB 63 Amp, 415 V, 25 KA, 4 pole with fixed thermal magnetic release -02 Nos. (c) MCB SPN 40 Amp, 240 V, 10 KA, C-Curve - 04 Nos. (d) Indicator with neon lamps for RYB , 3 Phase with MCBs set of three -04 sets
Re-outing /re-lying /Lt cable of size by taking up cable protection cover by excavation carefully all as specified and directed (Note :- Re-lying of servicecable protection cove/DWC pipe shall deemed to be included in unit quoted rate. (ii) Exc removal and returning filling of soil will be measured under appropriate item of Sch 'A'
Material and labour for fixing cable route indicators made of PCC (1:3:4) duly engraved “MES LT CABLE" /"LT CABLE JOINT"coloured with two coats of synthetic paint in brown of size 150 x 150 x 900 mm fixed 300mm below ground level.
M&L for cement concrete in foundation, filling and mass concrete using type D2(1:4:8) 40 mm agregate complete all as specified and directed by Engr in Charge.
M&L rendering 10 mm thick on fair faces of brick work or concrete surfaces using cement plaster (1:3) complete all as specified and directed by engr in Charge.
SBS Enterprises (BID ID -3147915)
BRITE INDUSTRIES (BID ID -3149223)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .