Executive Engineer
33/11KV S/S RDC, Gzb.
Increasing Capacity of 33/11KV Substation Sudamapuri, Ghaziabad.
2020_PVVNL_474147_1
03/2020-21
Open Tender
Electrical Works
Item Rate
30 days
Ghaziabad
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
PVVNL, ECWD (D), Gzb.
₹15,000
Yes
6 Jun 2020
22 May 2020
3 Jun 2020
22 May 2020
3 Jun 2020
22 May 2020
180 days
Safe carriage of following stock material, from Store Center, Ghaziabad to site of 33/11KV S/S Sudamapuri, Distt. Ghaziabad (Distance approx. 15-Kms.) a) Switchyard items and other materials, such as Isolators, Disc/Post Insulators, Stay Rods, Conductor, etc. and Steel Items, such as R.S.Joist, Angles and Channels, etc.
b) P.C.C. Poles-8.5M. long/S.T.Poles-11M.long
c) 11KV XLPE Alumn. Cable-3x300/3x120Sq.mm
d) Safe carriage of following equipments, from Store Center, Ghaziabad to site of 33/11KV S/S Sudamapuri, Distt. Ghaziabad (Distance approx. 15-Kms.) i) 33KV VCB, with Structure
ii) 33KV C.T.
iii) 33KV Control Panel for Single T/F
iv) Battery Charger with Battery Set
v) 11KV I/C Switchgear, including P.T.
vi) 11KV O/G Switchgear
vii) 33KV L.A.
2. Earthing of Outdoor Equipments in Switchyard, details as given below:- a) Digging of Trench of size-0.50x0.75x45M.,for laying of Earth mat throughout in switchyard and re-filling &ramming of the same earth in the to the trenches after completion of earth mat work.
b) Laying of 32mm.dia M.S.Bar in Trench, properly in alignment along the length and width in switchyard.
C) Cutting of 32mm.dia M.S.Bar-3M.long and making one end in conical shape, by forging process and driving it into the earth, in trench at fixed distance as per drawing and properly welding with M.S.Bar Earthmat.
d) Proper continuous electric welding of overlap joints of M.S.Bar upto a length of 150mm. On both sides,along the length of M.S.Bar and an extra piece of 12mm M.S.Round-150mm.long, providing on both sides of Overlap Joints and continuous electric welding on both side, along the length of M.S.Bar. All joints shall be painted with black bituminous paint.
e) Proper electric welding at X-joints of M.S.Bar and welding by providing 25x6mm.”U” type Clamp of M.S.Flat, and proper continuous electric welding with M.S.Electrode and M.S.Bar at each X-joints. All joints shall be painted with black bituminous paint.
f) Providing & laying of G.I.Strip of size 40x6mm for connecting the earthmat with each equipment (Terminal Gantry, Bus Gantry, Bus Isolators, Line Isolator, 33KV C.T., 33KV V.C.B., L.As., Fuse Set, Post Insulators, T/F Body & its neutral and M.S.Frame of Cable Supporting Structure), various steel structures. The work also includes cutting, bendidng, straightening, over-laping and welding the earth strip with earth mat and by using high quality arc welding in already digged trenches.
3. Earthing of indoor equipment, details as given below:- a) Cutting of 32mm.dia M.S. Bar-3Mtr.long and making one end in conical shape by forging process and driving it into the earth at each corner of bridge outside control room and proper welding with M.S.Bars.
b) Digging of Pits for making Bridge on both side of control room by laying 32mm. dia M.S.Round in rectangular shape. Electric welding on cross joints by providing “U” Clamp in size 25x6mm. of M.S.Flat and inter connecting both by M.S.Round 32mm.dia through control room trench, with over lap joint by providing M.S.Round-12mm dia, on both sides of over lap joints of M.S.Round, by electric welding. All joints shall be painted with black bituminious paint.
c) Making earthing of all 11KV Switchgears, P.T. and other equipments on both earth terminal inside the control room by providing G.I.Strip in size 40x6mm. with 32mm. dia M.S.Round laid in trench with proper electric welding.
4. Boring and lowering by providing of G.I.Pipe size 40mm dia of 2mm thickness, into the ground upto water level or minimum 50Mtr, which ever is more, with the lower end of solid copper cone Approx 224mm long and 750gm in weight shall be provided and screwed in pipe as well as bringing out a continuous 6SWG copper wire, from the cone upto the ground surface where it will be bolted to the G.I. Strip for Transformer neutral connection, the G.I.Strip will be connected to star point through providing Copper Bond Strip of size-50x6mm.
5. Construction of 1No. Plinth for 5MVA, 33/11KV T/F, in size-4x3 Meters., as per drawing, details as given below:- a) Excavation of earth in foundation.
b) Cement concrete in foundation in ratio 1:6:12, Cement, Sand & Brick ballast.
c) First Class Brick work in ratio 1:4 with Cement & Coarse sand mortar.
d) Cement concreting inner side of plinth in ratio 1:4:8, Cement, Coarse sand and stone shingle.
e) M.S.work for re-inforcement 12mm. Tor at a distance of 15Cms. apart, including cutting, bending & binding by wire to each other for making JAL in two layer, 12 to 15Cms. apart.
f) Fixing of 4Mtr.long, 2No. Rail Pices, 90Lbs, on top of Plinth at proper distance in alignment by C.C.
g) Cement concrete in ratio 1:2:4, Cement, Coarse sand & Stone shingle, on top of the plinth, including fixing of M.S.Tor Jal.
h) 12mm.thick Cement Plaster in ratio 1:4, Cement & Sand mortar, on all side of plinth.
i) Neat cement coating 3mm.thick on top surface of plinth.
6). Fabrication, excavation, erection, grouting (with cement, coarse sand and stone shingle) and making of plinth of following structures,as per RESPO Drawing:- I) Line/ Bus Isolator Structure a) Fabrication of structure, including cutting, straightening & drilling of holes in Channel/Angle
b) Excavation of earth 2x(1.10x0.60x1.00)
c) Supply & fixing of stone pad of size 300x300x75mm
d) Erection of Line / Bus isolator structure in proper alignment
e) Grouting of structure in C.C ratio 1:3:6 2x(1.10x0.60x1.00)
f) Making plinth by C.C ratio 1:3:6, in size 2x(1.10x0.60x0.30)
g) 12mm thick plastering on plinth in ratio 1:4 of size 2x(1.10x0.30)x2+2x(0.60x0.30)x2+2x(1.10x0.60)x1
II) L.A.'s, P.I.'s, C.T's, Fuse Set Unit structure:- a) Fabrication of structure, including cutting, straightening & drilling of holes in Channel/Angle
b) Excavation of earth 2x(0.90x0.90x1.00) x1+2x(0.45x0.45x1.00)x3
c) Supply & fixing of stone pad of size 300x300x75mm
d) Erection of Line / Bus isolator structure in proper alignment
e) Grouting of structure in C.C ratio 1:4:8 2x(0.90x0.90x1.00)x1+2x(0.45x0.45x1.00)x3
f) Making plinth by C.C ratio 1:3:6, in size 2x(0.90x0.90x0.30)x1+2x(0.45x0.45x0.30)x3
g) 12mm thick plastering on plinth in ratio 1:4 of size 2x(0.90x0.30)x2+2x(0.50x0.30)x2+2x(0.90x0.50)+2x(0.45x0.30)x3x2+2x(0.45x0.30)+2x(0.45x0.45)x3
III) M.S.FRAME FOR SUPPORT OF 11KV CABLE (1No.): i) Fabrication of structure, including cutting, straightening, drilling of holes and electric welding.
ii) Excavation of earth (0.60x0.30x1.00)
iii) Grouting with C.C. in ratio 1:4:8 (0.60x0.30x1.00)
F) CONSTRUCTION OF PLINTH OF 33KV VCB (1No.): i) Excavation of earth (2.30x2.30x1.00)M
ii) Cement, Concrete in foundation with C.C.ratio 1:4:8, Brick ballast, size (2.30x2.30x0.15)M.
iii) Ist Class brick work in ratio 1:4, size 2x(2.00x0.23x1.15) + 2x(1.54x0.23x1.15)
iv) Cement concreting in ratio 1:4:8 under plinth, size (1.54x1.54x1.15)M.
v) Cement concreting in ratio 1:2:4 on top, size (2.00x2.00x0.10)
vi) Fixing of structure on plinth by providing 4No. Eye bolt-20mm. on plinth by C.C. 1:2:4
vii) 12mm.thick Cement Plaster on Wall in ratio 1:4, size 2x(2.00x0.40)+2x(2.00x0.40)
7. i) Mounting & fixing of all above outdoor equipments such as VCB, CT, Fuse Set, P.I. and Isolators etc., by providing Bolt, Nuts &Washers.
ii) Providing & fixing M.S.Plate of size 450x450x4mm, at bottom of each C.T.
8. Laying, Stringing & Sagging of ACSR Dog Conductor from main Bus Bar to Power T/F, through Post Insulator, Bus Isolator, C.Ts, VCB and L.As., by providing P.G.Clamp/Connectors, suitable for Dog.
9. a) Erection of 11KV Switchgears in proper alignment, in Control Room, including safe shifting, from Dump Place. Making 4No. Pockets for each and providing/fixing of Reg Bolt by CC in ratio 1:2:4, with tightening also, including safely mounting of 11KV P.T. on 11KV I/C Switchgear, filling of oil (if required), making all electrical connections. i) 11KV Incoming VCB 600/300/5A, 350MVA
ii) 11KV Outgoing VCB 400/200/5A, 350MVA
iii) 11KV bus coupler VCB 350MVA
b). Assembling and installation of the cabinet of 24V. battery and battery charger & 1No. I/C Control Panel for Single T/F, including grouting of foundation bolts as per drawing of manufacturer, in proper alignment, in Control Room, including safe shifting from Dump Place. The electrical connection, between battery & battery charger, with flexible copper lead of size 7/20SWG, shall be done properly. The work includes wiring upto control pannels, testing & commissioning, in all respect.
c). Commissioning & fixing of Bus bar (Copper), between each Switchgear, by bolt, nut & washers and HT compound and providing & tapping HT Tape, Empire Tape & PVC Tape, on each joint.
10. i) Dragging/lifting of 33/11KV, 5MVA T/F on Plinth from the unloaded place.
ii) Erection of 33/11KV, 5MVA Power T/F on Plinth, by fixing all accessories, like Radiators, Conservator Tank, filling the T/f Oil to desired level and ensuring that there is no leakage, complete job in all respect.
11. a) Erection of Double Pole Structure on STP 11M./PCC 8.5M. long, with fabrication of all accessories, such as Channel/Angle. Fixing of all accessories on Double Pole, by providing M.S.Clamp, made of 50x6mm. M.S.Flat and Bolt,Nut&Washers. Earthing to be provided on each supports by driving M.S.Earthing Rod and connecting between Rod &Supports, by providing M.S.Strip of size-35x6 mm, by electric welding.
b) Grouting of STP 11M./PCC 8.5M. long, with CC in ratio 1:4:8, complete in all respect, as per RESPO Norms.
12). Erection of Stay Set-16x1800mm. on Double Pole, includidng digging of pits of size-0.75x0.75x1.5M. Grouting in CC ratio 1:4:8 Cement, Sand & Stone Shingle. Binding and nozelling of Stay Wire, complete in all respect, by providing Stay Clamp, made of 50x6mm size M.S.Flat, as per RESPO Norms.
13 a) Digging of Trench of size 0.45x0.6M., for laying of 11KV Cable for incoming/outgoing feeder and Stn. T/F, in “S” shape.
b) Laying of 11KV XLPE 3x300/3x120Sq.mm. Alumn.Cable in the Trench, for T/F and Feeders, from Control Room, by providing Ist Class Bricks on both sides and on Top of the Cable. Filling the Sand, inside the Bricks and refilling of loose earth in the Trench.
c) Laying of 11KV XLPE 3x300/3x120Sq.mm. Alumn.Cable in air/pipe/on pole/Double Pole or Ladder in puckka Trench in Control Room.
d) Filling of river sand in Control Room Cable Trench.
14 a) Making of joints by 11KV Heat Shrink type Jointing Kits, Indoor/Outdoor type, providing & fixing of Alumn. Lugs of proper size, by crimping on each phase of the Cable at both ends.
b) Fixing of Cable Box on 5MVA T/F, 11KV Switchgears, by Bolt & Nuts and tapping the joints by providing HT/Empire/PVC Tape and Copper Strip of size 50x6mm., 75mm.long, including proper tapping.
c) Mounting of 11KV Cable boxes on Double Pole, by providing & fixing of M.S.Clamp, made of 50x6mm. M.S.Flat, with Bolts,Nuts & Washers, including providing & fixing 3mm. thick 100mm. dia G.I.Pipe-4M.long, with pipe supporting Clamp-2No. on each, made of 35x6mm M.S.Flat.
15. CONSTRUCTION OF CONTROL CABLE TRENCH IN SWITCHYARD, AS PER DETAILS (LENGTH-30MTR.): i) Excavation of earth in size 0.750x0.40m.
ii) C.C.work in foundation in ratio 1:4:8 (Cement, sand & Brick Ballast) with proper ramming in size 0.750x0.15m.
iii) Ist Class Brick work in cement mortar in ratio 1:4 in size 0.23x0.35m.
iv) 25mm thick C.C. in floor of Cable Trench in ratio 1:2:4 (Cement, coursend and Stone ballast) 20mm guage in size 0.3m width.
v) Grouting of M.S.Strip of size 450x25x6mm in cable trench 100mm above floor level and at equal space distance 300mm
vi) Grouting of M.S.Angle Iron of size 50x50x6mm in upper edge of trench.
vii) C.C.work on the Top in the ratio 1:2:4 in the grouting of Edge of the Trenches. (30x2x0.23x0.06)
viii) Plastering of Trench in Cement, Mortar in ratio 1:4, 12mm thick in cable trench.
ix) Fabrication and fixing cable trench cover of M.S.Angle Iron size 40x40x6mm of size 0.3m wide 0.5 to 1.0 mtr length with proper welding of 8mm size of bar 2Nos. In length and 6Nos. in width. a) 0.5 Mtr long
b) 1.00 Mtr long
15 b). Laying of different size of (2x2.5)Sq.mm/(4x2.5)Sq.mm/ (6x2.5) Sq.mm Control Cable in Packka Trench, from Buchholz relay to Marshalling box, Marshalling box to indication protection board in switch gear room, 33KV CTs to CTs Junction Box, C.T. 33KV, V.C.B. Control Panel Junction box to 33KV VCB control panel and control panel to 33KV VCB outdoor operating mechanism panel from T/F etc. in the cable trench including making proper connection at Buchholz Relay, Marshalling box and indication board as per required for installed equipment.
16. Fabrication of L.T.Board in Control Room of M.S.Angle Iron 50x50x6mm in rectangular shape, with 1.5M long legs, including providing & fixing Ply Board of size 1x1M, 25mm thick by G.I.Bolt, including Providing &fixing 1No.MCB Box-63Amp TPN & 6No. 32Amp SPN (MDS/Havells/Standard make), 1No. Power Plug with socket for Battery Charger. Grouting of legs with C.C. in ratio 1:2:4 includidng making Pits, Painting of complete Board with one coat of Red Oxide & two coats of Steel Gray Paint.
17. Painting of the following structure with one coat of ready mixed primer and two coats of ISI Mark Alumn. Paint after rubbing with sand paper to the surface of the structure includidng labour and T&P complete in all respect.: a) Terminal Gantry Structure
b) Bus Bar Gantry Structure
c) Line Isolator, Bus Isolator, Fuse Set Structure
d) Post Insulator, L.A.Structure
e) 11KV Double Pole Structure on SP-55 STP
f) Cable Support and T/F Neutral Structure
18. Providing & Fixing Water Tight Sodium Vapour Light-250W, with pre-fabricated G.I.Pipe, mounting of bracket on PCC Pole and Wall, by using M.S.Clamp, made of 50x6mm. M.S.Flat with Bolt,Nut&Washers, making the connections on all poles providing & laying 2x4Sq.mm PVC Cable, with L.T.Line.
19. Providing & Laying 2x6Sq.mm. PVC Cable and making connection with 63Amp TPN (MDS/Havells/Standard), inside Control Room from T/F at one end and L.T.Line on other end for Switching ON/OFF of Street Light.
20. Fabrication of Fire buckets Frame, made of M.S.Angle-50x50x6mm., including cutting, straightening & fixing of M.S.Channel-100x50mm., for base of the Frame by electric welding, 8No. ‘J’ hooks of 18mm. dia M.S.Bar to be fixed on Top of the Angle, by electric welding. Providing 8No. Fire buckets of standard size, duly painted as per norms.
21. Providing of Chequerred Rubber Sheet of size-1800x900x10mm. in Control Room.
22. Hiring of D/G Set, including carriage, loading, unloading & operating charges (with fuel) at 33/11KV Substation under construction in case L.T.Supply is not available near S/S, within prescribed accessible limit: a) 20 KVA, 3 Phase D/G Set for testing of equipments installed at Sub-station.
b) 5 KVA, Single Phase D/G Set for testing of equipments installed at Sub-station.
23. Providing required No. of Technicians to work on power T/F, HT/LT Panels, during testing as assisting technical hands of test team during commissioning & energisation.
24. Construction of S.S.Os. Approach Road-1.2M wide in switch yard by laying dry brick-ballast in 15Cm layer, 115mm thick brick work 1:4 in both side of edge, providing 10Cm thick CC in ratio 1:2:4. the work includes proper plastering top & side of road and making groove, leveling & dressing of earth beneath the brick work on edge.
25. Construction of Fire wall, as per drawing, made of cement, sand, concrere, bricks, etc., which will be arranged by the contractor. (Dimention-4.5x5Mtr or as per drawing/site requirement).
26. Supply & Fabrication of copper bus bar of size (2500x50x6)mm in L.V. side of 5 MVA 33/11 KV, power transformer, Work includes connection of outside bus bar in L.V. side busing rod of Power Transformer and other side with outdoor 11 KV cable box as well as providing empire tape and H.T. tape etc. for proper insulation work.
27. Draining of oil from conservator & radiators of the 5MVA T/F, already available at 33/11KV S/S into the dry & clean drums and staking at the safe place.
28. Dismantling of conservator, radiators and other accessories from above 5MVA Transformer at 33/11KV S/S under PVVNL
29. Shifting of 05MVA T/F main body and other accessories from the Substation switchyard to loading point out side the switchyard of 33/11KV Substation under PVVNL.
30. Loading of main tank of Transformer alongwith conservator, radiators, Transformer’s Oil Drums, and other accessories on the Trailer/Truck at 33/11KV S/S under PVVNL
31. Carriage of main tank of Transformer alongwith conservator, radiators, Transformer’s Oil Drums and other accessories from 33/11KV S/S to 33/11KV S/S under PVVNL i) Upto 60Km
ii) Upto 120Km
iii) Upto 180Km
32. Unloading of main tank of Transformer alongwith conservator, radiators, Transformer’s Oil Drums, and other accessories on the Trailer/Truck at 33/11KV S/S under PVVNL
33. Supply and replacement of damaged Gasket/Cork sheet of radiators / bushings etc. of above T/F complete in all respect.
34. Supply and replacement of damaged HV / LV bushing complete in all respect.
35. Cleaning & painting of 05MVA Power T/F complete with radiators etc.
Vivek Electricals
M/S RAGHAV and BROTHERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .